User Manual ADR-out Network Analyser
English
Contents
Safety warnings Page 30
Technical specifications Page 30
Description of instrument Page 31
Keys Page 32
Setting the parameters Page 32
Displaying the measurement pages Page 39
Measurement and calculation method Page 49
Reference standards Page 50
ADR-R out dimensions and connection diagrams Page 24-25
ADR-D out dimensions and connection diagrams Page 26-27
- 30 -
User Manual ADR-out Network Analyser
English
During the installation and operation of the instrument, the following
should be noted:
1) The instrument should be installed by a competent person
2) Follow the connection diagrams to the letter when installing the
instrument
3) When connecting the instrument, always use the TA x/5 A
4) The appliance should be installed in a panel where the terminals will be
inaccessible after installation
5) The voltage and current circuit terminals may be connected with a
maximum rated voltage of 300 V eff. with respect to earth
6) The panel should be wired in line with the relevant CEI standards
7) Do not power or connect the instrument if any part of it is damaged
NOTE:
The VEMER network analysers are designed for use in environments with
over-voltage category III and pollution level 2, in accordance with the
CEI-EN 61010-I standard.
The electrical system of the building where the instrument is to be
installed should contain a switch or isolator. This should be close to the
instrument and within easy reach of an operator.
An over-current protection device should be fitted.
Important: when the power supply is cut off, there should be no signal
at the measurement inputs (current or voltage).
Power supply: 230 VAC (-15%/+10%)
Frequency: 50/60 Hz
Maximum consumption: 5 VA
Display: rear-lit LCD
Voltmeter inputs: max 500 VAC, 47÷63Hz (phase-phase concatenated)
Ammeter inputs: max 6 A, 47÷63 Hz
Scales: 1 voltage with end of scale 500 V (phase-phase concatenated)
2 current with end of scale at 1.25 A and 6 A
• Precision:
- Voltage: 0.5% of the end of scale value (min 10 V)
- Current: 0,5% of the end of scale value (min. 20 mA)
- Power: 1% of the end of scale value
TECHNICAL SPECIFICATIONS
SAFETY WARNINGS
- 31 -
User Manual ADR-out Network Analyser
English
- Frequency: ±0,1 Hz (47÷63 Hz)
- Active energy CEI-EN 61036 class 2
- Reactive energy CEI-EN 61268 class 3
TV available: primary 1÷9999 V +10÷65kV; secondary 230 V
TA available: primary 1÷9999 A; secondary 5 A
2 x 250 VAC 2 A relay outputs (105 x VDE0435 operations)
Operating temperature: 0÷ +50 °C
Relative humidity: 10%÷90% non-condensing
• Containers:
Rear panel version: material in class V0 in accordance with the UL 94 standard,
standard dimensions 72x72 mm in accordance with the DIN 43700 standard
Modular version: material in class V0 in accordance with the UL 94 standard,
4 DIN module containers, colour RAL-7035 grey
Network analyser
Code ModelDescription
VN794400 ADR-R-outNetwork analyser with relay output, rear panel version
VN795100 ADR-D-outNetwork analyser with relay output, modular version
Display
-Numerical fields for the display of the values measured
- Type of measurement taking place
-Measurement unit
-Phase symbols
DESCRIPTION OF INSTRUMENT
1
cos
APPARENT
REACTIVE
ENERGY
VOLTAGE
CURRENT
FREQUENCY
POWER
2
GMk Wh
Hz VARh
AV
3
1
2
2
3
1
3
4
pK
T
ADR
GMk Wh
Hz VARh
cos
AV
1
2
2
31
3
APPARENT
REACTIVE
ENERGY
VOLTAGE
CURRENT
FREQUENCY
POWER


Product specificaties

Merk: Vemer
Categorie: Niet gecategoriseerd
Model: ADR-D Out

Heb je hulp nodig?

Als je hulp nodig hebt met Vemer ADR-D Out stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Vemer

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd