Measurement of differential pressure; optional: humidity and
temperature
Flat housing allows flush surface integration in the
cleanroom wall
Ethernet, relay and analog outputs allow optimum
integration into individual automation systems
Self-monitoring of the transmitter and early warning function
guarantee high system availability
The P2A software for parameterization, adjustment and
analysis saves time and costs in commissioning and
maintenance
Configurable alarm management with adjustable response
delay and alarm acknowledgement
Dierential pressure transmitter in
cleanroom-conform panel design
testo 6383
The differential pressure transmitter testo 6383 was
developed specially for monitoring low differential pressures
in the measuring range from 10 Pa to 10 hPa. In cleanroom
technology, the maintenance of positive pressure prevents
the entry of contaminated air in critical zones. Thanks to
an optional internal or external probe from the probe series
6610, the additional recording of humidity and temperature
with one instrument is also possible.
The testo 6383 is particularly outstanding thanks to the
automatic zero-point adjustment which ensures high
accuracy and long-term stability.
The integrated self-monitoring and early warning function
also guarantees the operator high system availability.
www.testo.com
hPa
°C
%RH
testo 6383 – Dierential pressure transmitter in cleanroom-conform panel design
Technical data
Supply
Analog outputs
Other outputs
Meas. cycle 1/sec
Quantity Standard: 1;
with optional humidity probe: 3
Scaling Differential pressure: scalable ±50% of
measuring range final value;
freely scalable within measuring range
Resolution 12 bit
Max. load max. 500 Ω
Humidity/temperature optional
Parameters
Probe
Type
Parameters
Measurement
uncertainty*
%RH / °C/°F / °Ctd / °Ftd / g/kg / gr/lb / g/m3 / gr/ft³ / ppmV
/ °Cwb / °Fwb / kJ/kg / mbar / inch H2O / °Ctm (H2O2)/°Ftm
(H2O2) / % Vol
for deviations from media temp. ±25 °C:±0.02 %RH/K
Meas. range
Humidity /
trace humidity
Humidity
Dewpoint
Temperature
Temp. at
+25°C /
+77°F
Inputs/outputs
Output type 0/4 to 20 mA (4-wire) (24 VAC/DC)
0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
Ethernet Optional
Relay Optional: 4 relays (free allocation to
measurement channels or as collective alarm
in operating menu/P2A), up to 250 VAC/3A
(NO or NC)
Digital Mini-DIN for P2A software
Voltage supply 20 to 30 VAC/DC, 300 mA current
consumption, galvanically separate signal
and supply line
Integrated
probe
testo 6613 testo 6614 testo 6615 testo 6617
Channel Duct heated Cable trace
humidity
Cable with
cover elec-
trode moni-
toring
Integrated
probe testo 6613 testo 6614 testo 6615 testo 6617
±(1.0 + 0.007 * MV) %RH
for 0 to 90 %RH
±(1.4 + 0.007 * MV) %RH
for 90 to 100 %RH
±(1.0 + 0.007*MV)
%RH
for 0 to100 %RH
±(1.2 + 0.007*MV)
%RH for 0 to 90 %RH
±(1.6 + 0.007*MV)
%RH for 90 to 100
%RH
±1 K at 0 °Ctd
±2 K at -40°Ctd
±4 K at -50 °C
td
±0.15 °C / 32.2 °F
Pt1000 Class AA
±0.15 °C/
32.2 °F
Pt100 Class
AA
±0.15 °C/
32.2 °F
Pt1000 Class
AA
0 to 100 %RH 0 to 100 %RH-60 to +30 °C td
-20 to +70 °C
-4 to +158 °F
-40 to +180 °C
-40 to +356 °F
-40 to +120 °C
-40 to +248 °F
-40 to +180 °C
-40 to +356 °F
Display
Model
Miscellaneous
Display 3-line LCD
with multi-language operating menu
0.1 %RH
0.01 °C / 0.01 °F
General technical data
Material Front plate stainless steel, housing
plastic
Dimensions without humidity/temperature:
246 x 161 x 47 mm
with humidity/temperature:
396 x 161 x 78 mm
Resolution
Differential pressure
Humidity
Temperature
Measuring range Resolution
Operation temperature -5 to +50 °C / +23 to +122 °F
Storage temperature -20 to +60 °C / -4 to +140 °F
Process temperature -20 to +65 °C / -4 to +149 °F
Protection class IP 65
Connection nipple Ø 6 mm --> suitable hoses
4 mm + 4.8 mm
Operating conditions
Weight Version without humidity: 0.9 kg;
Version with integrated humidity
probe:1.35 kg; version with preparation
for external humidity probe: 1.26 kg
0 to 10 Pa 0.1 Pa
0 to 50 Pa 0.1 Pa
0 to 100 Pa 0.1 Pa
0 to 500 Pa 0.1 Pa
0 to 10 hPa 0.01 hPa
-10 to 10 Pa 0.1 Pa
-50 to 50 Pa 0.1 Pa
-100 to 100 Pa 0.1 Pa
-500 to 500 Pa 0.1 Pa
-10 to 10 hPa 0.01 hPa
Dierential pressure
Parameters
Measuring range 0 to 10 Pa
0 to 50 Pa
0 to 100 Pa
0 to 500 Pa
0 to 10 hPa
-10 to +10 Pa
-50 to +50 Pa
-100 to +100 Pa
-500 to +500 Pa
-10 to +10 hPa
Measurement
uncertainty*
±0.3% of measurement range final value
±0.3 Pa
Temperature gain drift: 0.02% of measuring
range per Kelvin deviaton from nominal
temperature 22 °C
Zero point drift: 0% (thanks to cyclic zero-
point adjustment)
Selectable units Differential pressure in Pa, hPa, kPa,
mbar, bar, mmH2O, kg/cm2, PSI, inch
HG, inch H2O
Sensor Piezoresistive sensor
Autom. zero-point
adjustment
via magnetic valve
Frequency adjustable: 15 sec, 30 sec, 1 min,
5 min, 10 min
Overload Measuring range Overload
0 to 10 Pa 20000 Pa
0 to 50 Pa 20000 Pa
0 to 100 Pa 20000 Pa
0 to 500 Pa 20000 Pa
0 to 10 hPa 200 hPa
-10 to 10 Pa 20000 Pa
-50 to 50 Pa 20000 Pa
-100 to 100 Pa 20000 Pa
-500 to 500 Pa 20000 Pa
-10 to 10 hPa 200 hPa
+-+-+-+-
+
-
CH1 CH2 CH3
24V
1
20-30 V
AC/DC
0V
161 mm
246 mm
175 mm
396 mm
396 mm
47 mm
47 mm
78 mm
161 mm 161 mm
3 mm 3 mm 3 mm
testo 6383 – Dierential pressure transmitter in cleanroom-conform panel design
Technical drawings / Connection plan
Technical drawings
Connection plan
The determination of measurement uncertainty takes place according to
GUM (Guide to the Expression of Uncertainty in Measurement):
For the determination of measurement uncertainty, the accuracy of
the measuring instrument (hysteresis, linearity, reproduceability), the
uncertainty contribution of the test site as well as the uncertainty of
the adjustment site (works calibration are taken into account. For this
purpose, the value of k=2 of the extension factor, which is usual in
measurement technology is used as a basis, which corresponds to a
trust level of 95%.
Measurement uncertainty differential pressure ±0.5% of measuring
range final value ±0.3 Pa


Product specificaties

Merk: Testo
Categorie: Niet gecategoriseerd
Model: 6383

Heb je hulp nodig?

Als je hulp nodig hebt met Testo 6383 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Testo

Testo

Testo 6681 Handleiding

6 September 2023
Testo

Testo 6651 Handleiding

6 September 2023
Testo

Testo 550 Handleiding

1 September 2023
Testo

Testo 6621 Handleiding

1 September 2023
Testo

Testo 6631 Handleiding

1 September 2023
Testo

Testo 557 Handleiding

1 September 2023
Testo

Testo 184 H1 Handleiding

29 Augustus 2023
Testo

Testo 184 Handleiding

5 Juli 2023

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd