Silent Knight SD500-AIM Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Silent Knight SD500-AIM (2 pagina's) in de categorie Detector. Deze handleiding was nuttig voor 30 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
P/N 151071
SD500-AIM Input Module and
SD500-MIM Mini Input Module
Installation Instructions
The following instructions are a quick reference
guide, refer to the control panel installation
manual P/N 151139, 151274, 151280, 151295,
151209, or 151302 for detailed system
information.
Wiring the SD500-AIM / MIM
Note: Installation and wiring of these devices must be done in
accordance with NFPA 72 and local ordinances.
Terminate the wiring as shown in Table 1. See
also Figure 1 or Figure 2
Specifications
Table 2 lists the operating specifications for the
SD500-AIM and the SD500-MIM.
Impedance for Earth Ground Fault is 0 Ω for all
terminals.
Figure 1: Class B Wiring the SD500-AIM & SD500-MIM
Table 1: Wire Connections
SD500-AIM
SD500-MIM
Terminals
To:
FACP or SLC
Loop Terminals Contact
SLC –SLC
OUT
SC–
+ S+
Contact
A out CLASS A
OR B
To N.O. Contact
B out To N.O. Contact
A IN CLASS A ONLY
(SD500-AIM Only)
End of Loop A
End of Loop B
B IN
Table 2: SD500-AIM and SD500-MIM Specifications
Specifications
Max. Line resistance 50Ω
Max. Alarm
Current
One device in alarm
23mA. 46 mA for two
devices in alarm.
.5 mA for each addi-
tional device in
alarm.
Max. Voltage 33 V
Operating Temperature 0° to 49° C
(32° to 120° F)
Indoor use only
Table 2: SD500-AIM and SD500-MIM Specifications
Specifications
Alternate
Construction
SD500-AIM Input Module and SD500-MIM Mini Input Module Installation Instructions
2
7550 Meridian Circe, Suite 100
Maple Grove, MN 55369-4927
763-493-6455 or 800-328-0103
Fax: 763-493-6475
www.silentknight.com
© 2008 Honeywell International Inc. PN 151071 Rev G
Figure 2: Class A Wiring the SD500-AIM
Mounting the SD500-AIM
Mount the SD500-AIM into a double gang box
as shown in Figure 3.
Mounting the SD500-MIM
Install the SD500-MIM into a single gang box
see Figure 1 and Figure 3.
Figure 3: Mounting the SD500-AIM and SD500-MIM
Setting the Devices Address
The range of valid addresses is 1 - 127 (0 is an
invalid address). Refer to Figure 4 to set the dip
switches to the desired address.
Figure 4: Setting the Device Address:
Note: The dip switch settings shown in Figure 4 apply to the
SD500-MIM also.
Status LED


Product specificaties

Merk: Silent Knight
Categorie: Detector
Model: SD500-AIM
Gewicht: 120.1 g
Breedte: 124 mm
Diepte: 25 mm
Hoogte: 124 mm
Certificering: NFPA 71, NFPA 72, UL, CSFM, MEA, FM
Aantal per verpakking: 1 stuk(s)
Compatibele producten: 5820XL, 5820XL-EVS, 5808, 5700

Heb je hulp nodig?

Als je hulp nodig hebt met Silent Knight SD500-AIM stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Detector Silent Knight

Handleiding Detector

Nieuwste handleidingen voor Detector

Seaward

Seaward LLT MK2 Handleiding

5 November 2024
K40

K40 RL200di Handleiding

11 September 2024
Noyafa

Noyafa NF-820 Handleiding

5 September 2024
STI

STI BIO-7505 Handleiding

4 September 2024
ORNO

ORNO OR-DC-633 Handleiding

22 Augustus 2024
STI

STI -8201-W Handleiding

21 Augustus 2024
STI

STI -9623 Handleiding

21 Augustus 2024