CE1N3035en
25.09.2003
Siemens Building Technologies
HVAC Products
3035
Room Temperature Controllers
with 7-Day Time Switch and LCD
RDE10...
for heating systems
2-position control with ON/OFF output for heating
Operating modes: normal operation and energy saving mode
7-day time switch and manual operation
Mains-powered AC 230 V (RDE10) or battery-powered DC 3 V (RDE10.1)
Use
The RDE10... is used for the control of the room temperature in heating systems.
Typical applications:
β€’ Apartments
β€’ Commercial spaces
β€’ Schools
For the control of the following pieces of equipment:
β€’ Thermic valves or zone valves
β€’ Gas or oil burners
β€’ Fans
β€’ Pumps
2/8
Siemens Building Technologies Room temperature controllers CE1N3035en
HVAC Products 25.09.2003
Functions
The controller acquires the room temperature with its integrated sensor and maintains
the setpoint by delivering control commands. The switching differential is 1 K.
Q14
T[Β°C]
ON
OFF W
SD
3030D01
T Room temperature
SD Switching differential
W Room temperature setpoint
Q14 Output signal for heating
Operating modes
The RDE10... provides normal operation and, optionally, energy saving mode or OFF.
The difference between normal operation and energy saving mode is only the room
temperature setpoint. The changeover between the operating modes can be made
either automatically according to the 7-day time switch or manually with the operating
mode selector.
When normal operation is activated, symbol β€œ β€œ appears on the display. The setpoint
can be readjusted by pressing buttons , + and -.
When energy saving mode is activated, symbol β€œ β€œ appears on the display. The set-
point can be readjusted by pressing buttons , + and -.
In energy saving mode, the unit can also be switched to β€œOff”. This is accomplished by
selecting a setpoint of 5 Β°C and then keeping button - depressed for 4 seconds. In
that case, symbol ' ' does not appear.
The changeover between the operating modes can take place either automatically
( ) or manually ( , ), depending on the position of the operating mode selector.
When the operating mode selector is in position β€œ ”, changeover will take place
automatically according to the selected switching pattern. For every weekday, a specific
switching pattern can be selected.
Factory setting:
Day(s) Normal operation Energy saving mode
Mo (1) – Fr (5) 6:00 – 8:00 h and
17:00 – 22:00 h
22:00 – 6:00 h and
08:00 – 17:00 h
Sa (6) – Su (7) 7:00 – 22:00 h 22:00 – 7:00 h
The current setpoint can be temporarily readjusted by pressing
buttons + and -. The setpoint will then be reset to its initial value the next time auto-
matic or manual changeover takes place.
When the operating mode selector is set to” β€œ or β€œ β€œ, the RDE10... will maintain
normal operation or energy saving mode respectively.
Function diagram
Normal operation
Energy saving mode
or OFF
7-day time switch
3/8
Siemens Building Technologies Room temperature controllers CE1N3035en
HVAC Products 25.09.2003
The digital display shows the actual room temperature, the time of day, the weekday,
the current switching pattern and the symbol of the operating mode currently active.
The switching pattern shows normal operation as a double bar and energy saving
mode as a single bar with a flashing time pointer. When the heating output is activated,
the triangle symbol appears.
0 6 12 18 24 0 6 12 18 24 0 6 12 18 24
Automatic changeover according Normal operation Energy saving mode
to the switching pattern
In the event of a power failure, the setpoints and the information required for operating
mode changeover are retained for 3 minutes. This is enough to cope with power fail-
ures of short duration (with RDE10) or when changing the batteries (with RDE10.1).
Type summary
Type reference Features
RDE10 Mains-powered AC 230 V
RDE10.1 Battery-powered DC 3 V
Ordering
When ordering, please give name and type references, e.g. room temperature con-
troller RDE10.
Valve actuators are to be ordered as separate items.
Equipment combinations
Type of unit Type reference Data sheet
Motoric on/off actuator SFA21... 4863
Thermal actuator (for radiator valve) STA21... 4893
Thermal actuator (for small valve 2,5 mm) STP21... 4878
Accessories
Description Type reference
Adapter plate 120 x 120 mm for 4β€œ x 4β€œ conduit boxes ARG70
Adapter plate 96 x 120 mm for 2β€œ x 4β€œ conduit boxes ARG70.1
Adapter plate for surface wiring 112x130 mm ARG70.2
Display
Backup
.
.
.
.
.
.
.
.
.


Product specificaties