Seaward LLT MK2 Handleiding

Seaward Detector LLT MK2

Lees hieronder de 📖 handleiding in het Nederlandse voor Seaward LLT MK2 (4 pagina's) in de categorie Detector. Deze handleiding was nuttig voor 8 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/4
LLT MK2
Live Line Tester
Operating Instructions
Bracken Hill
South West Industrial Estate
Peterlee
Co Durham
SR8 2SW
ENGLAND
Tel: +44(0)191 5863511
www.seaward.com
sales@seaward.com
service@seaward.com
Part Number 423A650 Revision 1
© 20 Seaward Electronic Ltd 22
Limited Warranty & Limitation of Liability
SEAWARD Electronic Limited guarantees this product to be free
from defects in material and workmanship under normal use and
service for a period of 1 year. The period of warranty will be
eective at the day of delivery.
(c) Copyright 20 22
All rights reserved. Nothing from this edition may be multiplied,
or made public in any form or manner, either electronically,
mechanically, by photocopying, recording, or in any manner,
without prior written consent from SE ARD Electronic Limited. AW
This also applies to accompanying drawings and diagrams.
Due to a policy of continuous development SE ARD Electronic AW
Limited reserves the right to alter the equipment specication and
description outlined in this publication without prior notice and no
part of this publication shall be deemed to be part of any contract
for the equipment unless specically referred to as an inclusion
within such contract
1 Important Information
These operating instructions are intended for the use of
adequately trained personnel.
Before use, ensure that the live line tester is clean and dry;
visually inspect all parts. Any damage must be rectied prior to
use.
Never hold a Live Line Tester between the hand-guard and
the contact electrode.
Always prove the Live Line Tester before AND after use.
1. Holding the live line tester by the handles, above the
handguards, connect the instrument to a Seaward
PH3-LLT proving unit and verify that the LED
indicators are illuminated.
2. Reverse the connections to the PH3-LLT and repeat
step 1. This proves the LLT in both polarities.
3. Holding the live line tester by the handle, above the
handguards, place the contact electrodes in contact
with the circuit under test.
4. If the LED indicators are illuminated there is a
voltage greater than the threshold voltage present at
the probe tips.
5. If the LED indicators do not illuminate, replace PP3
9V battery inside PH3 and repeat step 1 and 2. If LED
indicator not illuminate still, this suggests LLT s do
is faulty and should NOT be used. Contact the
manufacturer or an authorised Seaward Service
Agent for advice.
6. Repeat step 1 and 2 above to verify that the
instrument is still operational.


Product specificaties

Merk: Seaward
Categorie: Detector
Model: LLT MK2

Heb je hulp nodig?

Als je hulp nodig hebt met Seaward LLT MK2 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Detector Seaward

Seaward

Seaward LLT MK2 Handleiding

5 November 2024

Handleiding Detector

Nieuwste handleidingen voor Detector