INSTALLATION INSTRUCTIONS
No.59-1881-3 131115UL
No.59-1881-3
PHOTOELECTRIC DETECTOR
• Quad high power beams
• Double modulated beam
• Smart design
- Slim body design
- Easy-to-see vivid interior color for optical alignment
- IP65*1 waterproof structure
• 4 channel beam frequency selector
• Alignment level indicator
• Viewfinder with 2X magnification
• Various options (refer to page 20)
( HU-3*1, ABC-4*1, BC-4*1, CBR-4, PSC-4*1, BAU-4*1 )
• UL/c-UL Listed
• Beam interruption adjustment function
• D.Q. circuit (environmental disqualification)
• Tamper function
• Beam power control selector
• Alarm memory
• Sound assist function
-
Optical alignment
- Beam reception status
- Walk test
[ SL-QDM only ]
• Auto Transmit Power Control (A.T.P.C*2) to optimize the beam power
• Integrated Alignment Status Communication (I.A.S.C*
2) to
communicate the transmitter and receiver
• Re-transmitting circuit function
• Solar Battery Unit SBU-4*1 (option)
PHOTOELECTRIC DETECTOR
A photoelectric detector consists of an infrared light
source that generates IR(Infrared) beams, and an IR
receiver that detects the IR beams. The transmitter
and receiver are installed on opposite sides of the
area to be monitored. The receiver detects when the
IR beams are physically interrupted by an intruder,
and sends an alarm signal to be a control panel.
FEATURES
INTRODUCTION
1-1 BEFORE YOUR OPERATION ....................... 2
1-2 PRECAUTIONS
.......................................................
2
1-3 PARTS IDENTIFICATION
.....................................
3
INSTALLATION
2-1 SEPARATING................................................. 4
2-2 WIRING .......................................................... 4
2-3 TERMINAL ..................................................... 5
2-4 WIRING DIAGRAM ........................................ 5
2-5 WIRING DISTANCE BETWEEN POWER
SUPPLY AND DETECTOR ............................ 6
2-6 WALL MOUNTING ......................................... 6
2-7 POLE MOUNTING ......................................... 8
2-8 MOUNTING IN THE BEAM TOWER.............. 9
2-9
INSTALLATION EXAMPLE AT PARTICULAR CASE
... 9
FUNCTION SETTING
3-1 DIP SWITCH ................................................. 10
3-2 BEAM POWER CONTROL SELECTOR....... 10
1
2
3
4
6
7
8
9
CONTENTS
3-3 FUNCTION.................................................... 11
OPTICAL ALIGNMENT
4-1 OPTICAL ALIGNMENT FOR UPPER AND
LOWER BEAM.............................................. 15
4-2 OPERATION CHECK.................................... 17
TROUBLESHOOTING
5-1 TROUBLESHOOTING .................................. 17
OPTIONAL SETTING
6-1 HEATER UNIT HU-3 (OPTION) .................... 18
6-2 SOLAR BATTERY UNIT SBU-4 (OPTION)... 18
DIMENSIONS
7-1 DIMENSIONS ............................................... 19
SPECIFICATIONS
8-1 SPECIFICATIONS......................................... 19
OPTIONS
9-1 OPTIONS ...................................................... 20
Detection range
SL-200QDM
SL-350QDM
SL-650QDM
SL-200QDP
SL-350QDP
SL-650QDP
Advanced Standard
5
Transmitter Receiver
Smart Line series
Smart Line series
â„¢
â„¢ 60m/200ft.
100m/350ft.
200m/650ft.
*1 not evaluated by UL
*2 not require any additional tool
-2-
1-2 PRECAUTIONS
This symbol indicates prohibition. This symbol indicates recommendation.
Receiver
Transmitter
(different
model)
Receiver
(different
model)
Transmitter
At least 1 m (3.3 ft.)
Warning
Caution
• Read this instruction manual carefully prior to installation.
• After reading, store this manual carefully in an easily accessible place for reference.
• This manual uses the following warning indications for correct use of the product, harm to you or other people and damage to your assets, which
are described below. Be sure to understand the description before reading the rest of this manual.
INTRODUCTION
1
1-1 BEFORE YOUR OPERATION
Failure to follow the instructions provided with this indication and improper handling may cause
death or serious injury.
Failure to follow the instructions provided with this indication and improper handling may cause
injury and/or property damage.
This symbol indicates prohibition. The specific prohibited action is provided in and/or around the figure.
This symbol requires an action or gives an instruction.
Do not install the unit on an
unstable surface.
Do not install the pole in a
location where sufficient
stability can not be ensured.
Do not install the unit in a
location where trees, leaves, or
other objects that may swing in
the wind and block the beam.
Do not install the receiver in a
location where it is exposed to
direct sunlight.
Install the unit at a height
where an object can be
detected without fail.
Do not allow the infrared beam
from a different model to reach
the receiver.
Install the unit at least 1 m (3.3
ft.) away from the wall or fence
that may be running parallel to
the beam.
The pole size should be
34 - 48 mm
( 1.34 - 1.89 inch).
Warning
Caution
Do not use the product for purposes other than the detection of moving objects such as
people and vehicles. Do not use the product to activate a shutter, etc., which may
cause an accident.
Do not touch the unit base or power terminals of the product with a wet hand (do not
touch when the product is wet with rain, etc.). It may cause electric shock.
Never attempt to disassemble or repair the product. It may cause fire or damage to the
devices.
Do not exceed the voltage or current rating specified for any of the terminals during
installation, doing so may cause fire or damage to the devices.
Do not pour water over the product with a bucket, hose, etc. The water may enter,
which may cause damage to the devices.
Clean and check the product periodically for safe use. If any problem is found, do not
attempt to use the product as it is and have the product repaired by a professional
engineer or electrician.
[Receiver]
Transmitter Receiver
For UL/c-UL installations ;
• Reference to UL681, Standard for Installation and Classification of Burglar and Holdup Alarm System.
• Reference to CAN/ULC-S302, ULC Standard for Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises.
Safes and Vaults, & CAN/ULC-S310, ULC Standards for Installation and Classification of Residential Burglar Alarm.
• Conduit is required for all Outdoor Use Application with Conduit Bracket Kit, Model CBR-4, employing appropriate wiring methods.
• Products to be installed within the protected premises.
-3-
<Transmitter>
U-brackets: 4
Pole brackets: 4
4×20 self tapping for wall mounting: 4
M4×30 screws for pole mounting
(with rubber washer): 8
Beam blocking plate: 2
(attached on the back of the cover)
3×6 self tapping for pole bracket: 4
FUNCTION SETTING SECTION >>
ACCESSORIES >>
SL-QDM
SL-QDP
<Receiver>
<Transmitter> <Receiver>
Banding bands: 4
1-3 PARTS IDENTIFICATION
Cover Main unit Chassis
Cover lock screw View finder
Terminals
Cut bush
for wiring
Main unit base
Mounting screw holes
Pole mounting
screw holes
Pole mounting
screw holes
Wall mounting
screw holes
Vertical alignment dial
Vertical alignment dial
Horizontal alignment dial
Optical lens
I.A.S.C lens
[QDM only]
Horizontal alignment dial
Viewfinder
Beam blocking plate
T R
T R
Upper/Lower beam selection button
Upper/Lower beam selection button
Upper/Lower beam selection button
Monitor jack (+)
Monitor jack (-)
Power indicator LED
Upper beam indicator LED
Lower beam indicator LED
Power indicator
LED
Upper beam
indicator LED
Lower beam
indicator LED
Power supply selector
Sound assist switch
Beam power control selector
Dip switch
Alignment level
indicator LED
Upper/Lower beam selection button
Power supply selector
Sound assist switch
Dip switch
Alignment level
indicator LED
Beam power control selector
Dip switch
Sound assist switch
Dip switch
Alignment level
indicator LED
Optical lens
Tamper
lock plate
Tamper
button
Power indicator LED
Alarm memory indicator LED
Alarm indicator LED
Upper beam indicator LED
Lower beam indicator LED
Power indicator LED
Alarm memory indicator LED
Alarm indicator LED
Upper beam indicator LED
Lower beam indicator LED
Monitor jack (+)
Monitor jack (-)
Monitor jack (+)
Monitor jack (-)
Beam power control selector


Product specificaties

Merk: Optex
Categorie: Niet gecategoriseerd
Model: SL-650QDP-BT

Heb je hulp nodig?

Als je hulp nodig hebt met Optex SL-650QDP-BT stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Optex

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd