Mean Well NPB-1200-24 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Mean Well NPB-1200-24 (33 pagina's) in de categorie Batterij-oplader. Deze handleiding was nuttig voor 22 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/33
N P B & N P P S e r i e s
I n sta l l a ti on M a n u a l
 High Reliable Intelligent Battery Charger
Intelligent Battery Charger
nIt is suitable for lead-acid batteries (flooded water type, el colloid type,g
AGM adsorption glass fiber) or (lithium iron, lithium manganese, lithium
ternary…etc.)
nThe charger must be installed in a dry and well ventilated area. It should
not be exposed to rain or snow.
nAll failures should be examed by the qualified technician.
nThe cables between charger and battery should be kept as short as
possible to prevent excessive voltage drop (suggested cable length:
50cm~100cm). Too much voltage drop will lead to longer charging period.
nMake sure charging voltage and current meet battery's specification.
nRefrain from connecting new and old batteries in series.
nCharger should be in the OFF mode before making battery connection or
disconnection.
nFor auto ranging. Please refer to the manual before using this function.
And note that, it must work together with battery that built-in BMS.
nThis equipment is not suitable for use in locations where children are likely
to be present.
nThe protective earthing is used as a safeguard, the instructions shall
require connection of the equipment protective earthing conductor to the
installation protective earthing conductor (for example, by means of a
power cord connected to a socket-outlet with earthing connection).
1 Safety Guidelines.
1
1
nIndoor use only.
2
NPB-360 series
5
INPUT
MODEL
BOOST CHARGE VOLTAGE
(Vboost)(default)
FLOAT CHARGE VOLTAGE
(Vfloat)(default)
RECOMMENDED BATTERY
CAPACITY (AMP HOURS)
VOLTAGE ADJUSTABLE RANGE
OUTPUT CURRENT Note.5
CURRENT ADJUSTABLE RANGE
MAX. POWER
NPB-360-12
=XLR,AD1,TB
NPB-360-24 NPB-360-48
14.4V 28.8V 57.6V
13.8V 27.6V 55.2V
10.5 ~ 15.2V 21 ~ 30.4V 42 ~ 60.8V
20A
50% ~ 100%
12A 6A
304W 364.8W 364.8W
65 ~ 195AH 40 ~ 125AH 20 ~ 65AH
OUTPUT
90 ~ 264VAC 127 ~ 370VDC
Note.4
Note.3
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
PF>0.98/115VAC, PF>0.95/230VAC at full load
87%
87%
88.5%
XLR
AD1
TB
91%
91%
92%
92%
92%
92.5%
4.5A/115VAC 2.2A/230VAC
INRUSH CURRENT (Typ.) COLD START 50A at 230VAC
SHORT CIRCUIT Protection type : Constant current limiting charger will shutdown after 5 sec re power, , -
on to recover
Note.6
OVER VOLTAGE 16 ~ 20V 32 ~ 40V 64 ~ 75V
Protection type : Shut down and latch off o/p voltage, re-power on to recover
REVERSE POLARITY By internal fuse open
OVER TEMPERATURE Shut down O/P voltage, recovers automatically after temperature goes down
PROTECTION
CHARGING CURVE
FAN CONTROL (Typ.)
2 or 3 stage adjustable by DIP S.W
Internal RTH3 50 Fan ON, 45 Fan OFF≧ ℃ ≦ ℃
FUNCTION
WORK TEMP. -30 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ± ℃ 0.05%/ (0 ~ 50 )
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRON-
MENT
MTBF
DIMENSION
PACKING
180*96*49mm (L*W*H)
OTHER
434.8K hrs min. Telcordia SR-332(Bellcore) ; 173.9K hrs min. MIL-HDBK-217F (25 )
1.3Kg; 10pcs/14Kg/1.13CUFT
VOLTAGE RANGE Note.5
2
7
NPB-750 series
INPUT
MODEL
BOOST CHARGE VOLTAGE
(Vboost)(default)
FLOAT CHARGE VOLTAGE
(Vfloat)(default)
RECOMMENDED BATTERY
CAPACITY (AMP HOURS)
LEAKAGE CURRENT
FROM BATTERY (Typ.)
CHARGE VOLTAGE RANGE
MAX. OUTPUT CURRENT
(CC)
MAX. POWER
<1mA
OUTPUT
VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC
Note.5
Note.4
Note.6
Note.7
Note.4
Note.3
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
PF>0.98/115VAC, PF>0.95/230VAC at full load
8.7A/115VAC 4A/230VAC
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
COLD START 50A at 230VAC
<1mA/240VAC
SHORT CIRCUIT Protection type : Constant current limiting charger will shutdown after 5 sec re power, , -
on to recover
Note.8
Note.9
OVER VOLTAGE Protection type : Shut down and latch off o/p voltage, re-power on to recover
REVERSE POLARITY
OVER TEMPERATURE Shut down O/P voltage, recovers automatically after temperature goes down
PROTECTION
CHARGING CURVE
230*158*67mm (L*W*H)
NPB-750-12 NPB-750-24 NPB-750-48
14.4V 28.8V 57.6V
13.8V 27.6V 55.2V
10.5 ~ 21V 21 ~ 42V 42 ~ 80V
43A 22.5A 11.3A
722.4W 756W 759.36W
150 ~ 500AH 80 ~ 260AH 40 ~ 130AH
92% 93% 93%
21.5 ~ 26V 43 ~ 52V 82 ~ 100V
CANBUS INTERFACE
CHARGER OK
REMOTE CONTROL
TEMPERATURE COMPENSATION
FAN SPEED CONTROL
CHARGING PARAMETERS
PROGRAMMABLE
AUTO RANGING CHARGING
CURVE (Typ.)
FUNCTION
WORK TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRON-
MENT
MTBF
DIMENSION
PACKING
OTHER
BATTERY FULL SIGNAL
Protected internal reverse detection, No damage, re-power on to recover after fault
condition is removed
2 or 3 stage selectable through DIP S.W on panel, or SBP-001 with computer
Programmable: Constant current(CC),Tapper current(TC), Constant voltage(CV) and
Float voltage(FV) can be set through SBP-001 with computer
Manual setting: 4 built-in charging curves adjustable via DIP S.W on panel, Please refer
to function manual for more detail
Please refer to functin manual for more detail (page 8)
Charging current adjustable 50~100% by via potentiometer on panel (Only for auto ranging mode)
CANBus 2.0B, Can control, Setting and monitoring(V ,I ,charging curve, internal temp.O O
and DC output ON/OFF)
The TTL signal out, Charger OK = H(4.5 ~ 5.5V) ;
Charger failure or protection status =L( -0.5 ~ +0.5V)
The TTL signal out, Battery full = H(4.5 ~ 5.5V ); Charging = L(-0.5 ~ +0.5V)
-30 ~ +70 (Refer to "Derating Curve")
By external NTC
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing
± ℃ 0.05%/ (0 ~ 50 )
Depends on internal temperature
Short : Charger normal work Open : Charger stop charging
227.6K hrs min. Telcordia SR-332(Bellcore) ; 67.7K hrs min. MIL-HDBK-217F (25 )
1.84Kg; 4pcs/9Kg/1.63CUFT
2
9
NPB-1700 series
INPUT
MODEL
BOOST CHARGE VOLTAGE
(Vboost)(default)
FLOAT CHARGE VOLTAGE
(Vfloat)(default)
RECOMMENDED BATTERY
CAPACITY (AMP HOURS)
LEAKAGE CURRENT
FROM BATTERY (Typ.)
CHARGE VOLTAGE RANGE
MAX. OUTPUT CURRENT
(CC)
MAX. POWER
<1mA
OUTPUT
VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC
Note.5
Note.4
Note.6
Note.7
Note.4
Note.3
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
PF>0.98/115VAC, PF>0.95/230VAC at full load
14.8A/115VAC 9.3A/230VAC
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
COLD START 50A at 230VAC
<0.75mA/240VAC(60335-1/2-29), <1.5mA Peak/240VAC(62368-1)
NPB-1700-12 NPB-1700-24 NPB-1700-48
14.4V 28.8V 57.6V
13.8V 27.6V 55.2V
10.5 ~ 21V 21 ~ 42V 42 ~ 80V
85A 50A 25A
1428W 1680W 1680W
300 ~ 1000AH 200 ~ 640AH 100 ~ 330AH
92% 93% 94%
SHORT CIRCUIT Protection type : Constant current limiting charger will shutdown after 5 sec re power, , -
on to recover
Note.8
Note.9
OVER VOLTAGE Protection type : Shut down and latch off o/p voltage, re-power on to recover
REVERSE POLARITY
OVER TEMPERATURE Shut down O/P voltage, recovers automatically after temperature goes down
PROTECTION
CHARGING CURVE
307*184*76.35mm (L*W*H)
21.5 ~ 26V 43 ~ 52V 82 ~ 100V
CANBUS INTERFACE
CHARGER OK
REMOTE CONTROL
TEMPERATURE COMPENSATION
FAN SPEED CONTROL
CHARGING PARAMETERS
PROGRAMMABLE
AUTO RANGING CHARGING
CURVE (Typ.)
FUNCTION
WORK TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRON-
MENT
MTBF
DIMENSION
PACKING
OTHER
BATTERY FULL SIGNAL
Protected internal reverse detection, No damage, re-power on to recover after fault
condition is removed
2 or 3 stage selectable through DIP S.W on panel, or SBP-001 with computer
Programmable: Constant current(CC),Tapper current(TC), Constant voltage(CV) and
Float voltage(FV) can be set through SBP-001 with computer
Manual setting: 4 built-in charging curves adjustable via DIP S.W on panel, Please refer
to function manual for more detail
Please refer to functin manual for more detail (page 8)
Charging current adjustable 50~100% by via potentiometer on panel (Only for auto ranging mode)
CANBus 2.0B, Can control, Setting and monitoring(V ,I ,charging curve, internal temp.O O
and DC output ON/OFF)
The TTL signal out, Charger OK = H(4.5 ~ 5.5V) ;
Charger failure or protection status =L( -0.5 ~ +0.5V)
The TTL signal out, Battery full = H(4.5 ~ 5.5V ); Charging = L(-0.5 ~ +0.5V)
-30 ~ +70 (Refer to "Derating Curve")
By external NTC
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing
± ℃ 0.05%/ (0 ~ 50 )
Depends on internal temperature
Short : Charger normal work Open : Charger stop charging
190.0K hrs min. Telcordia SR-332(Bellcore) ; 45.1K hrs min. MIL-HDBK-217F (25 )
2.93Kg; 4cs/14Kg/2.58CUFT
2
NPP-450 series Power supply mode-
11
INPUT
MODEL
DC VOLTAGE
VOLTAGE ADJUSTABLE RANGE
RATED CURRENT
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
OUTPUT
VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
PF>0.98/115VAC, PF>0.95/230VAC at full load
4.5A/115VAC 2.2A/230VAC
INRUSH CURRENT (Typ.) COLD START 50A at 230VAC
SHORT CIRCUIT
OVERLOAD
OVER VOLTAGE Protection type : Shut down and latch off o/p voltage, re-power on to recover
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
OVER TEMPERATURE Shut down O/P voltage, recovers automatically after temperature goes down
PROTECTION
REMOTE CONTROL
Depends on internal temperature
FUNCTION
WORK TEMP. -30 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ± ℃ 0.05%/ (0 ~ 50 )
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRON-
MENT
MTBF
DIMENSION
PACKING
205*135*55mm (L*W*H)OTHER
Note.3
NPP-450-12 NPP-450-24 NPP-450-48 NPP-450-72
14.4V 28.8V 57.6V 72V
10.5 ~ 21V
By built-in potentionmeter
21 ~ 42V 42 ~ 80V 54 ~ 100V
25A 13.5A 6.8A 5.5A
420W
180mVp-p
±±±0.5% 0.5% 0.5%
±0.5%
±0.5%
±0.5%
±±±±1.0% 1.0% 1.0% 1.0%
± ±1.0% 1.0%
1800ms, 60ms/230VAC at full load
16ms/230VAC at 75% load 10ms/230VAC at full load
300mVp-p 480mVp-p 600mVp-p
453.6W 457W 462W
92% 93% 93% 93%
21.5 ~ 26V 43 ~ 52V 82 ~ 100V 102 ~ 120V
352.3K hrs min. Telcordia SR-332(Bellcore) ; 118.5K hrs min. MIL-HDBK-217F (25 )
1.02Kg; 8pcs/10Kg/1.71CUFT
CURRENT ADJUSTABLE RANGE
12.5 ~ 25A 6.75 ~ 13.5A 3.4 ~ 6.8A 2.75 ~ 5.5A
105 ~ 115% rated output power
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
Open : Power OFF Short : Power ON
The TTL signal out, DC OK = H(4.5 ~ 5.5V) ; Power supply failure or protection = L(-0.5 ~ +0.5V)
FAN SPEED CONTROL
DC OK
2
13
NPP-750 series Power supply mode-
SHORT CIRCUIT
OVERLOAD
OVER VOLTAGE Protection type : Shut down and latch off o/p voltage, re-power on to recover
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
OVER TEMPERATURE Shut down O/P voltage, recovers automatically after temperature goes down
105 ~ 115% rated output power
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
WORK TEMP. -30 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ± ℃ 0.05%/ (0 ~ 50 )
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRON-
MENT
MTBF
DIMENSION
PACKING
OTHER
REMOTE CONTROL
Depends on internal temperature
FUNCTION
Open : Power OFF Short : Power ON
The TTL signal out, DC OK = H(4.5 ~ 5.5V) ; Power supply failure or protection = L(-0.5 ~ +0.5V)
FAN SPEED CONTROL
DC OK
INPUT
MODEL
DC VOLTAGE
VOLTAGE ADJUSTABLE RANGE
RATED CURRENT
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
OUTPUT
VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
PF>0.98/115VAC, PF>0.95/230VAC at full load
8.7A/115VAC 4A/230VAC
INRUSH CURRENT (Typ.) COLD START 50A at 230VAC
230*158*67mm (L*W*H)
Note.3
1800ms, 60ms/230VAC at full load
16ms/230VAC at 75% load 10ms/230VAC at full load
92% 93% 93%
21.5 ~ 26V 43 ~ 52V 82 ~ 100V
NPP-750-12 NPP-750-24 NPP-750-48
14.4V
43A 22.5A 11.3A
28.8V 57.6V
10.5 ~ 21V 21 ~ 42V 42 ~ 80V
By built-in potentionmeter
722.4W 756W 759.36W
180mVp-p 300mVp-p 480mVp-p
±±±0.5% 0.5% 0.5%
±±±1.0% 1.0% 1.0%
±±±1.0% 1.0% 0.5%
294.5K hrs min. Telcordia SR-332(Bellcore) ; 95.7K hrs min. MIL-HDBK-217F (25 )
1.84Kg; 4pcs/9Kg/1.63CUFT
PROTECTION
CURRENT ADJUSTABLE RANGE
21.5 ~ 43V 11.25 ~ 22.5V 5.65 ~ 11.3V
15
NPP-1200 series Power supply mode-
2
MODEL
DC VOLTAGE
VOLTAGE ADJUSTABLE RANGE
1800ms, 60ms/230VAC at full load
NPP-1200-12 NPP-1200-24 NPP-1200-48
14.4V 28.8V 57.6V
10.5 ~ 21V 21 ~ 42V 42 ~ 80V
By built-in potentionmeter
SHORT CIRCUIT
OVERLOAD
OVER VOLTAGE Protection type : Shut down and latch off o/p voltage, re-power on to recover
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
OVER TEMPERATURE Shut down O/P voltage, recovers automatically after temperature goes down
105 ~ 115% rated output power
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
WORK TEMP. -30 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ± ℃ 0.05%/ (0 ~ 50 )
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRON-
MENT
MTBF
DIMENSION
PACKING
OTHER
REMOTE CONTROL
Depends on internal temperature
FUNCTION
Open : Power OFF Short : Power ON
The TTL signal out, DC OK = H(4.5 ~ 5.5V) ; Power supply failure or protection = L(-0.5 ~ +0.5V)
FAN SPEED CONTROL
DC OK
INPUT
RATED CURRENT
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
OUTPUT
VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
PF>0.98/115VAC, PF>0.95/230VAC at full load
12A/115VAC 6.5A/230VAC
INRUSH CURRENT (Typ.) COLD START 50A at 230VAC
250*158*67mm (L*W*H)
Note.3
92% 93% 94%
21.5 ~ 26V 43 ~ 52V 82 ~ 100V
208.4K hrs min. Telcordia SR-332(Bellcore) ; 63.6K hrs min. MIL-HDBK-217F (25 )
1.93Kg; 4pcs/10Kg/1.72CUFT
PROTECTION
CURRENT ADJUSTABLE RANGE
35 ~ 70V 18 ~ 36V 9 ~ 18V
70A 36A 18A
1176W 1209.6W 1209.6W
180mVp-p 300mVp-p 480mVp-p
±±±0.5% 0.5% 0.5%
±±±1.0% 1.0% 1.0%
±±±1.0% 1.0% 0.5%
16ms/230VAC at 75% load 10ms/230VAC at full load
17
NPP-1700 series Power supply mode-
2
*For the detail of NOTE information, please refer to the specification on
official website.
CURRENT ADJUSTABLE RANGE
INPUT
MODEL
DC VOLTAGE
VOLTAGE ADJUSTABLE RANGE
RATED CURRENT
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
OUTPUT
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.) 14.8A/115VAC 9.3A/230VAC
INRUSH CURRENT (Typ.)
Note.3
1800ms, 60ms/230VAC at full load
16ms/230VAC at 75% load 10ms/230VAC at full load
NPP-1700-12 NPP-1700-24 NPP-1700-48
14.4V
85A 50A 25A
28.8V 57.6V
10.5 ~ 21V 21 ~ 42V 42 ~ 80V
By built-in potentionmeter
1428W 1680W 1680W
180mVp-p 300mVp-p 480mVp-p
±±±0.5% 0.5% 0.5%
±±±2.0% 1.0% 1.0%
±±±2.0% 1.0% 0.5%
LEAKAGE CURRENT <0.75mA/240VAC
SHORT CIRCUIT
OVERLOAD
OVER VOLTAGE Protection type : Shut down and latch off o/p voltage, re-power on to recover
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
OVER TEMPERATURE Shut down O/P voltage, recovers automatically after temperature goes down
105 ~ 115% rated output power
Protection type : Constant current limiting, unit will shutdown after 5 sec, re-power on to recover
WORK TEMP. -30 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT ± ℃ 0.05%/ (0 ~ 50 )
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRON-
MENT
REMOTE CONTROL
Depends on internal temperature
FUNCTION
Open : Power OFF Short : Power ON
The TTL signal out, DC OK = H(4.5 ~ 5.5V) ; Power supply failure or protection = L(-0.5 ~ +0.5V)
FAN SPEED CONTROL
DC OK
21.5 ~ 26V 43 ~ 52V 82 ~ 100V
PROTECTION
42.5 ~ 85V 25 ~ 50V 12.5 ~ 25V
MTBF
DIMENSION
PACKING
OTHER 307*184*76.35mm (L*W*H)
192.5K hrs min. Telcordia SR-332(Bellcore) ; 58.5K hrs min. MIL-HDBK-217F (25 )
2.96Kg; 4pcs/14Kg/2.58CUFT
COLD START 50A at 230VAC
92%
PF>0.98/115VAC, PF>0.95/230VAC at full load
47 ~ 63Hz
90 ~ 264VAC 127 ~ 370VDC
93% 94%
2
2.5 Derating curve
90 100 115 120 140 160 180 190 200 220 240 264
100
90
78
80
85.5
60
70
50
40
DC INPUT VOLTAGE
NPB-120,NPB-240,NPB-360,NPB/NPP-450,NPB/NPP-750
NPB/NPP-1700
NPB/NPP-1200
LOAD (%)
LOAD (%)
AMBIENT TEMPERATURE ( )
-25 0-10 10 20 30 4540 50 60 70-30 (HORIZONTAL)
NPB-120,NPB-240,NPB-360
NPB/NPP-450,NPB/NPP-750,NPB/NPP-1200,NPB/NPP-1700
30
20
10
0
40
50
60
65
70
80
85
90
100
230VAC Input only
for NPB/NPP-450~1700
19
Unit mm:
Model A
205
230
250
307
B
39
42.5
47.5
76.35
C
127
145
155
155
DE
135 121
158 147
158 147
184 173
F
5.5
7
7
7
G
55
67
67
70
NPB/NPP-750
NPB/NPP-1200
NPB/NPP-1700
NPB/NPP-450
NPB/NPP-450/750/1200/1700
G
B
C A
F
D
E
2
Air flow
direction
21
ON
AC INPUT
OFF
I
O
3
3 Installation & Wiring.
3.1 Precautions
Figure 3-1 set up recommendation-
>15cm
Charger
>15cm
lPlease do not install in places with high moisture or near water.
lPlease make sure the ventilation is not blocked with force air cooling
models. We recommend that there should be no barriers within 15cm
of the ventilating slits, which is shown as follow.
23
Charger
+
-
+
-
+
-
BatteryBattery
+
-
Please turn off the charger first.
Select proper cable for connection between battery and charger
by referring to section 3.3
Connect the positive polarity of battery to the positive of charger,
and connect the negative polarity of battery to the negative of
charger.
Turn the power switch to“ON”position. If LED show in GREEN, it
states that the unit is in either charging or normal operation.
Please refer to chapter 4.2 for detail explanation of LED indication.
1
2
3
4
Installation procedures.2
Air flowAir flow
Charger
SW
Stat us
Io A dj.
CN71
14
2
13
1
DC O UTPUT
V+ V-
NPB-450
NPB-750/1200
HA
B
BA
D
F
E
C
D
F
E
I
I
4
27
NPB-1700
BA CH
D
F
E
I
H
C
Front panel
Front panel
Front panel
Back panel
Back panel
Back panel
O
I
ON OFF
AC INPUT
CN 71
V+ V
Status
Io Adj.
SW
12
1314
DC OUTPUT
ON
AC INPUT
OF F
I
O
ON
OF F
I
OAC INPUT
V-
V+
SW
St at u s
Io Ad j.
CN7 1
14
2
13
1
D C O U T P U T
4
4.2 LED Indicator
NPB series model
NPP series model
NPB-120
NPP-450
NPB-240
NPP-750
NPB-360
NPP-1200
NPP-1700
NPB-450
NPB-750
NPB-1200
NPB-1700
Green
Green
Green
Red
Red
No Light
No Light
Green
No Light
Orange
Orange
(Flashing)
Red
LED Indicator
LED Indicator
LED Indicator
Status
Status
Status
Charger Default( )
Power supply mode
Float stage(stage 3)or fully
Float stage(stage 3)or fully
Charging with auto ranging
Float stage(stage 3)or fully
charged
charged
function
charged
Normal working
Abnormal
Abnormal
Charging(stage 1or stage 2)
Charging(stage 1or stage 2)
Abnormal
Charging(stage 1or stage 2)
Abnormal(OTP,OVP,short circuit,
reverse polarity, time out )
Red
(Flashing) Unit over heated internally
29
1,2,
11~14 NC -----
Open: Batter y charger, Color of LED loading indicator : Reference to
chapter 4.2.
Short: Power supply, Color of LED loading indicator :Green.
8 +12Vaux
9,10 GND-AUX The signal return is isolated from the output terminal. (+V & -V)
Note: Isolated signal, referenced to GND-AUX
NC NC
NCNC
NCNC
Remote
ON-OFF
Battery
OK
Charger
OK
Charger
PSU/
Charger
PSU/
+12Vaux
GND-AUX GND-AUX
2
14
1
13
14 13
2 1
4.4 Pin assignment of NPP-450/750/1200/1700)(
5
7
6
3,4
Remote
ON/OFF
Charger OK
31
4
It is controlled by the Remote ON-OFF control.
Battery OK
Charger/
PSU
Battery OK Signal, referenced to GND-AUX(Pin 9 & 10).The Signal is a TTL
level signal. The maximum sourcing current is 10mA and only for
output(Note). Low (-0.5 ~ 0.5V) : When the battery is charging. High (4.5 ~
5.5V) : When the battery is full.
Pin No. Function Description
Charger OK Signal, referenced to GND-AUX(Pin 9 & 10).The Signal is a TTL
level signal. The maximum sourcing current is 10mA and only for output
(Note). Low (-0.5 ~ 0.5V) : When the charger fails or the protect function is
activating. High (4.5 ~ 5.5V) : When the charger is working properly.
Remote charger ON/OFF Function. The charger can turn the output ON/OFF
by dry contact between Remote ON-OFF and +12V-AUX(Note). Short (10.8 ~
13.2V) : Charger ON ; Open (-0.5 ~ 0.5V) : Charger OFF ; The maximum input
voltage is 13.2V.
Stat us
Io A dj.
CN71
14
2
13
1
DC O UTPUT
V+ V-
Vo Adj .
33
NPB-450/750/1200/1700 ( , )Default set as 3 stage Default programmable
21 3
OFF
OFF: 3 stage
ON: 2 stage
OFF
ON OFF
OFF ON
ON ON
Description
Default, programmable
Pre-defined, Gel battery
Pre-defined, flooded battery
Pre-defined, AGM battery,LiFe04
SwitchDIP
ONOFF
2
1
3
5.2.2 (NPP only)Charger mode/ power supply modes witchings
5 2 3 NPP. . (NPB/ -450/750/1200/1700)Remote ON/OFF
Charger
/PSU
Charger
/PSU
Remote
ON-OFF
+12Vaux
2
2
14
14
1
1
13
13
4
8
3
7
By using the DIP switch to change
the operation status.
Open
Short
Between PIN3 PIN4and
Between PIN 7 and PIN 8
Short
Open
Charger
Modes
Power supply
Remote ON
Charger
Remote OFF
5
Use this function to set the working
mode of the NPP series.
lCharger mode: can be used to
charge the battery.
lPower supply mode: can be used
directly with general loads.
35
NOTE:
1.If the necessary parameter is different from factory setting, SBP-001
or CANbus shall be used to correct the parameter.
2.The compensation will only activate during stage 3.
5
T h e RT H t h a t c o m e s w i t h t h e
products, can be connected to the
b a t t e r y f o r s e n s i n g t h e
temperature battery.of The charge
is able to work normally without
the sensor RTH.
The parameter is default as -3mV/℃
/Cell, ith the NTC NSG05C250J5-w
500V the comes with the product,
and connect to RTH+/RTH- panel.
5 2 6 NPB-450/750/1200/1700). . (Temperature compensation
24V
48V
72V
( - )NPB 450 only
30.6V
61.2V
76 5V.
26.4V
0 ~ 40℃52.8V
66V
12V
Model
15.3V
Upper limit of voltage
compensation
13.2V
Lower limit of voltage
compensation
Compensation
range of Temperature
RTH- RTH+
2
14
1
13
l
l
The MCU built-in charger will calculate the configuration and
parameter of the battery pack and finish the charging
sequence automatically. Through the auto ranging function,
users can easily finish charging sequence without setting
charging curves.
5 2 7 NPB-450/750/1200/1700). . (Auto ranging function
Caution :
NPB-450/750/1200/1700 Covers 3 different char ging
voltage r ange10.5V 21V ( 12V Model); 21V 42V(24V
Model); 42V– 80V(48V Model) 7254 100V( V Model,NPB-
450 only)Li-ion battery could be dangerous if wrong voltage
or sequence is applied. Ex: One battery possess 14.6V as
highest charging voltage, NPB-xxx-12 is suitable in this case.
Please ensure that auto ranging function only work with
lithium batteries with BMS function.
l
39
Figure5 2 Defult).(3 stage charging curve
Charging
current
(CURVE_CC)
stage 1 stage 2 stage 3
(CURVE_CV)
Battery Full
(CURVE_FV)
Start
Charging
voltage 100% of rated
current
Boost voltage
10% of rated
current
Orange
Red
Green
(NPB )-450/750/1200/1700
(NPB-120/240/360, NPP )-450/750/1200/1700
Green
Color of LED
Color of LED
Float voltage
State
Boost voltage
Float voltage
14.4V
13 8V.
28.8V
27 6V.
57.6V
55 2V.
12V model 24V model 48V model 72V model
NPB-120 Constant Current
NPB-240 Constant Current
NPB-360 Constant Current
NPB/NPP-450 Constant Current
NPB/NPP-750 Constant Current
NPB/NPP-1200 Constant Current
NPB/NPP-1700 Constant Current
6.8A
13.5A
20A
25A
43A
70A
85A
4A
8A
12A
13.5A
22.5A
36A
50A
2A
NA
NA
72V
69V
4A
6A
6.8A 5.5A
11.3A
18A
25A
5
NPB, -450/750/1200/1700NPP 3 stage charging curve
In the initial stage of charging, the charger charges the battery
with the maximum current, and the fan is ON (built-in fan
model). After a period of time (depending on the battery
capacity), the charging current gradually decreases. When the
charging current drops to 10% of the rated current. LED
indicator lights up green, indicating that the charging is
complete. And the charger remains float charging stage.
..3 2 3 stage charging(DIP switch turn to 3 stage
41
55.2
69
54.4
68
53.6
67
56.0
70
Vfloat
Vfloat
N :OTE Voltage tolerance of 2± %
57.6
56.0
56.8
58.4
2
2
DIP S.W position
DIP S.W position
OFF
OFF
ON
ON
OFF
OFF
ON
ON
3
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
6.8A
NPB-450
11.3A
NPB-750
18A
NPB-1200
25A
NPB-1700
Description
Description
Default, programmable
Default, programmable
Pre-defined, gel battery
Pre-defined, gel battery
Pre-defined, flooded battery
Pre-defined, flooded battery
Pre-defined, AGM battery,LiFe04
Pre-defined, AGM battery,LiFe04
48V model
72V model
CC (default)
CC (default)
Vboost
Vboost
1
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
5
27.6
13.8
13.6
13.4
14.0
Vfloat
Vfloat
Built-in stage charging curves3
2
DIP S.W position
OFF
ON
OFF
ON
3
OFF
OFF
ON
ON
25A
NPB-450
43A
NPB-750
70A
NPB-1200
85A
NPB-1700
Description
Default, programmable
Pre-defined, gel battery
Pre-defined, flooded battery
Pre-defined, AGM battery,LiFe04
12V model
CC (default) Vboost
14.4
14.0
14.2
14.6
1
OFF
OFF
OFF
OFF
2
DIP S.W position
OFF
3
OFF
Description
Default, programmable
24V model
CC (default) Vboost1
OFF 28.8
27.2ON OFF 13.5A
NPB-450
22.5A
NPB-750
36A
NPB-1200
50A
NPB-1700
Pre-defined, gel batteryOFF 28.0
26.8OFF ON Pre-defined, flooded batteryOFF 28.4
28.0ON ON Pre-defined, AGM battery,LiFe04OFF 29.2
72
70
71
73
5.5A
NPB-450 NA
N :OTE Voltage tolerance of 2± %
57.6
72
56.0
70
56.8
71
58.4
73
2
2
DIP S.W position
DIP S.W position
OFF
OFF
ON
ON
OFF
OFF
ON
ON
3
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
6.8A
NPB-450
5.5A
NPB-450
11.3A
NPB-750
NA
18A
NPB-1200
25A
NPB-1700
Description
Description
Default, programmable
Default, programmable
Pre-defined, gel battery
Pre-defined, gel battery
Pre-defined, flooded battery
Pre-defined, flooded battery
Pre-defined, AGM battery,LiFe04
Pre-defined, AGM battery,LiFe04
48V model
72V model
CC (default)
CC (default)
Vboost
Vboost
1
1
ON
ON
ON
ON
ON
ON
ON
ON
43
lCommunication Timing
Min. request period (Controller to PSU/CHG): 20mSec。
Max. response time (PSU/CHG to Controller): 5mSec。
Min. packet margin time (Controller to PSU/CHG): 5mSec。
PSU CAN-RX
(form Controller)
PSU CAN-TX
Request period
(Controller to PSU/CHG)
Response time
(PSU/CHG to Controller)
RX data
TX data
RX data
Packet Margin time
(Controller to PSU/CHG)
5. CAN us ( - / / / )5 B NPB 450 750 1200 1700Protocol
5. .15 CANBus specifications
lPhysical layer specification
This protocol follows CAN ISO-11898 with Baud rate of 250Kbps.
lData frame
This protocol uses Extended CAN 29-bit identifier frame format
or CAN 2.0B.
5
With CAN us protocol, control and monitoring function can beB
realized. It is helpful when user inten to modify the parameterss d
remotely. Users can access the aster and modify the parameterm s
through CANBus, which include, ON/OFF, output voltage/current,
temperature. More to that, user can even change the charging curves
parameters, such as constant current level, boost voltage, float
voltage and timeout function. For detail, please refer to following
chapter.
45
Command
Code
0x00B2
0x00B3
0x00B4
0x00B5
0x00B6
0x00B7
0x00B8
0x00C0
0x00C1
0x00C2
Command
Name
CURVE_FV
CURVE_TC
CURVE_CONFIG
CHG_STATUS
SCALING_FACTOR
SYSTEM_STATUS
SYSTEM_CONFIG
CURVE_CC_TIMEOUT
CURVE_CV_TIMEOUT
CURVE_FV_TIMEOUT
Transaction
Type
R W/
R W/
R/W
R/W
R/W
R/W
R
R
R
R/W
# of data
Bytes
2
2
2
2
2
2
2
2
2
2
Description
Scaling ratio
Charging status reporting
System status
System configuration
0x0086
0x00B0
0x00B1
0x0084
0x0085
0x0087
0x0088
0x0083
MFR_DATE_B0B5
CURVE_CC
CURVE_CV
MFR_SERIAL_B0B5
MFR_SERIAL_B6B11
MFR_REVISION_B0B5
MFR_LOCATION_B0B2
MFR_MODEL_B6B11
R
R/W
R/W
R/W
R/W
R/W
R/W
R
6
2
2
6
3
6
6
6
Manufacturer date
Constant current setting
of charge curve
(format: value, F=0.01)
Constant voltage setting
of charge curve
(format: value, F=0.01)
Floating voltage setting
of charge curve
(format: value, F=0.01)
Taper current setting
value of charging curve
(format: value, F=0.01)
Firmware revision
Product serial number
Product serial number
5
0x0081
0x0082
MFR_ID_B6B11
MFR_MODEL_B0B5
R
R
6
6
Manufacturer's name
Manufacturer's model
name
Manufacturer's model
name
CC charge timeout setting
of charging curve
CV charge timeout setting
of charging curve
FV charge timeout setting
of charging curve
Manufacturer's factory
location
Configuration setting
of charge curve
MFR_ID_B0B5 R 6 Manufacturer's name0x00 08
Valid when CURVE_CONFIG: CUVE = 1


Product specificaties

Merk: Mean Well
Categorie: Batterij-oplader
Model: NPB-1200-24

Heb je hulp nodig?

Als je hulp nodig hebt met Mean Well NPB-1200-24 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Batterij-oplader Mean Well

Handleiding Batterij-oplader

Nieuwste handleidingen voor Batterij-oplader