Mean Well ICL-28L Handleiding


Lees hieronder de ๐Ÿ“– handleiding in het Nederlandse voor Mean Well ICL-28L (5 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 30 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/5
โ– Description
โ– Model Encoding
Shape
Continuous rated current
Series name
- RICL - 28
(ICL-28R) (ICL-28L)
โ– Features
๎˜ƒ48A inrush limiting current, 28A continuous
๎˜ƒ180 264VAC AC input~
๎˜ƒIntegrated bypass relay, no simple NTC
๎˜ƒInternal thermal protection
๎˜ƒInstalled on DIN Rail TS-35/7.5 or 15 (ICL-28R)
๎˜ƒ-30~+70 C wide working temperatureยฐ
๎˜ƒOver voltage category โ…ข
๎˜ƒOperating altitude up to 5000 meters(Note. 2)
๎˜ƒ3 years warranty
๎˜ƒAllow connecting multiple power supply
at same line
๎˜ƒAllows smaller and faster Circuit Breaker
๎˜ƒCapacitive load
๎˜ƒProtects against unintended tigger of
circuit breaker
โ– Applications
The ICL-28 is a 28A inrush current limiter that can be used to reduce the high starting current
due to capacitive load causing the circuit breaker to be false triggered. Several power supplies
can be installed on the same AC line after the implementation of an ICL-28.
R: DIN Rail typ Rail mounted )e (
{
L: Linear type ( Terminal block mounted )
I C L - 2 8 R / 2 8 L
28A AC Inrush Current Limiter
File Name:ICL-28-SPEC 2020-09-07
SPECIFICATION
ICL-28L
AC LINE FREQUENCY
INRUSH CURRENT LIMITING
AC CONTINUOUS RATED CURRENT
AC INPUT POWER
AC INPUT CONSUMPTION
INTERNAL RELAY LIMITING TIME
(TON POWER ON)
LIMITING CYCLES
INTERNAL PROTECTION
ALLOWED CAPACITIVE LOAD
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP.
TEMP. COEFFICIENT
VIBRATION
OPERATING ALTITUDE
SAFETY STANDARDS
180 ~ 264VAC
47 ~ 63Hz
48A
28A continuous
6440VA (28A x 230VAC)
<2W at 264VAC, 50Hz input
150 50msยฑ
3 cycle / 1 min
Thermal fuse protects overload and fire
6000 F max.
ฮผ
ฮผ
ฮผ
ฮผฮผ
-30 ~ +70 (Refer to "Derating Curve")โ„ƒ
20 ~ 90% RH non-condensing
-40 ~ +85โ„ƒ
ยฑ โ„ƒ โ„ƒ0.03%/ (0 ~ 60 ) RH non-condensing
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes;
Mounting: Compliance to IEC60068-2-6
5000 meters
1601.76K hrs min. MIL-HDBK-217F (25 )โ„ƒ
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 โ„ƒ
of ambient temperature.
2. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with โ„ƒ โ„ƒ
fan models for operating altitude higher than 2000m(6500ft).
3. The power supply is considered as an independent unit, but the final equipment still need to
re-confirm that the whole system complies with the EMC directives. For guidance on how to
perform these EMC tests, please refer to ๎˜ปEMI testing of component power supplies.๎˜ผ
(as available on )http www meanwell com:// . .
RELEASE TIME 100 50msยฑ
OVER VOLTAGE CATEGORY
POLLUTION DEGREE 2
IEC62368-1(LVD)
โ…ข; According to IEC62368-1; altitude up to 5000 meters
MODEL
MTBF
DIMENSION
NOTE
PACKING
EMC IMMUNITY
EMC EMISSION
Parameter
Conducted
Radiated
Harmonic Current
Voltage Flicker
Test Level / Note
Class B
-------
Class A
Parameter
ESD
Radiated Susceptibility
EFT/Burest
Surge
Test Level /Note
Level 3, 8KV air; Level 2, 4KV contact, criteria A
Level 4,2KV/L-N, criteria A
Magnetic Field
Voltage Dips and interruptions
Level 3, criteria A
Level 3, criteria A
Level 4, criteria A
๏ผž .95% dip 0 5 periods, 30% dip 25 periods,
95% interruptions 250 periods๏ผž
Class B
AC INPUT VOLTAGE
Note. 2
0 16Kg; 80pcs/13 8Kg/1 23CUFT. . .
EN55024, EN55035,EN61000-6-2
Standard
EN61000-3-2
EN61000-3-3
Standard
EN55032
EN55032
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-8
EN61000-4-11
EN61000-4-6Conducted Level 3, criteria A
ICL-28R
INTERNAL RELAY
SAFETY &
EMC
( )
Note 3.
52.5 90 54 5* * . mm L*W*H)(175 42 24* * mm L*W*H)(
1626.62K hrs min. MIL-HDBK-217F (25 )โ„ƒ
I C L-2 8R / 28 L
28A AC Inrush Current Limiter
0 155Kg; 84pcs/14Kg/0 91CUFT. .
File Name:ICL-28-SPEC 2020-09-07
180 ~ 264VAC
BLOCK DIAGRAM
L
N
L
N
Control
Relay
R
Circuit
N O
N C
I C L-2 8R / 28 L
28A AC Inrush Current Limiter
File Name:ICL-28-SPEC 2020-09-07
-30 0 10 20 30 40 50 70 (HORIZONTAL)
100
AMBIENT TEMPERATURE ( )โ„ƒ
LOAD (%)
Derating Curve
60
80
50
80


Product specificaties

Merk: Mean Well
Categorie: Niet gecategoriseerd
Model: ICL-28L

Heb je hulp nodig?

Als je hulp nodig hebt met Mean Well ICL-28L stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Mean Well

Handleiding Niet gecategoriseerd