Test Report: H G-2 -RP 00 12
2 W Single Output with PFC Function 00
DESIGN VERIFY TEST
Output Function Test
Input Function Test
Protection Function Test
Control Function Test
Component Stress Test
SAFETY & E.M . TEST .C
Safety Test
E.M.C. Test
RELIABILITY TEST
ENVIRONMENT TEST
HRPG-200 series
Model: HRPG-200-12 Test Report 2 8 /
DESIGN VERIFY TEST
OUTPUT FUNCTION TEST
NO
TEST ITEM
TEST CONDITION
RESULT
VERDICT
1
RIPPLE & NOISE
V1120
mVp-p (Max )
I/P 230VAC
O/P FULL LOAD
Ta25
V1
92.8
mVp-p (Max )
P
2
OUTPUT VOLTAGE
ADJUST RANGE
I/P 230 VAC
I/P 115 VAC
O/P MIN LOAD
Ta25
9.183
9.185
V ~
V ~
14.759
14.765
V/ 230 VAC
V/ 115 VAC
P
3
OUTPUT VOLTAGE
TOLERANCE
I/P 100 VAC / 264 VAC
O/P FULL/ MIN LOAD
Ta25
V1
0.1
%~
-0.1
%
P
4
LINE REGULATION
I/P100VAC ~ 264 VAC
O/P FULL LOAD
Ta25
V1
0.05
%~
-0.05
%
P
5
LOAD REGULATION
I/P 230 VAC
O/P FULL ~MIN LOAD
Ta25
V1
0.1
%~
-0.1
%
P
6
SET UP TIME
230VAC
1000
ms (Max)
I/P 230 VAC
I/P 115 VAC
O/P FULL LOAD
Ta25
230VAC/
273
ms
P
115VAC
2500
ms(Max)
115VAC/
546
ms
7
RISE TIME
230VAC
50
ms (Max)
I/P 230 VAC
I/P 115 VAC
O/P FULL LOAD
Ta25
230VAC/
21
ms
P
115VAC
50
ms (Max)
115VAC/
20
ms
8
HOLD UP TIME
230VAC
16
ms (TYP)
I/P 230 VAC
I/P 115 VAC
O/P FULL LOAD
Ta25
230VAC/
46
ms
P
115VAC
16
ms (TYP)
115VAC/
38
ms
9
OVER/UNDERSHOOT
TEST
I/P 230 VAC
O/P FULL LOAD
Ta25
TEST
< 5
%
P
10
DYNAMIC LOAD
V1
1200
mVp-p
I/P 230 VAC
O/P FULL /Min LOAD 90%DUTY/
1KHZ
Ta25
518
mVp-p
P
HRPG-200 series
Model: HRPG-200-12 Test Report 3 8 /
INPUT FUNCTION TEST
NO
TEST ITEM
SPECIFICATION
TEST CONDITION
RESULT
VERDICT
1
INPUT VOLTAGE RANGE
85VAC~264 VAC
I/PTESTING
O/P FULL LOAD
Ta25
V~264V64
P
I/P
LOW-LINE-3V= 82 V
HIGH-LINE+15%=300 V
O/P FULL/MIN LOAD
30 Sec . OFF 30 Sec 10MIN ON: :
( AC POWER ON/OFF NO DAMAGE )
TEST OK
2
INPUT FREQUENCY
RANGE
47HZ ~63 HZ
NO DAMAGE OSC
I/P85 VAC ~ 264 VAC
O/P FULL~MIN LOAD
Ta25
TEST OK
P
3
POWER FACTOR
0.95
/ 230 VAC(TYP)
I/P 230 VAC
I/P 115 VAC
O/P FULL LOAD
Ta25
PF=
0.9614
/ 230 VAC
P
0.99
/ 115 VAC(TYP)
PF=
0.9966
/ 115 VAC
4
EFFICIENCY
88 % (TYP)
I/P 230 VAC
O/P FULL LOAD
Ta25
88.087
%
P
5
INPUT CURRENT
230V/
1.1
A (TYP)
I/P 230 VAC
I/P 115 VAC
O/P FULL LOAD
Ta25
I =
1.0082
A/ 230 VAC
P
115 V/
2.2
A (TYP)
I =
1.988
A/ 115 VAC
6
INRUSH CURRENT
230V/
70
A (TYP)
I/P 230 VAC
I/P 115 VAC
O/P FULL LOAD
Ta25
I =
62
A/ 230 VAC
P
115V/
35
A(TYP)
I =
31
A/ 115 VAC
COLD START
7
LEAKAGE CURRENT
<
1
mA / 240 VAC
I/P 264 VAC
O/P Min LOAD
Ta25
L- FG
0.48
mA
P
N-FG
0.34
mA
8
NO LOAD POWER
CONSUMPTION
< 0.5W
I/P 2 VAC 40
O/P LOAD NO
RC+/RC- SHORT
Ta25
0.32
W
P


Product specificaties

Merk: Mean Well
Categorie: Niet gecategoriseerd
Model: HRPG-200-12
Kleur van het product: Metallic
Gewicht: 760 g
Breedte: 98 mm
Diepte: 199 mm
Hoogte: 38 mm
Geluidsniveau: - dB
Certificering: ITE EN/UL/IEC 60950
Duurzaamheidscertificaten: RoHS
Totaal vermogen: 200 W
AC-ingangsspanning: 90 - 305 V
Power Factor Correctie (PFC) type: Actief

Heb je hulp nodig?

Als je hulp nodig hebt met Mean Well HRPG-200-12 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Mean Well

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd