LG LKAEH18B Handleiding


Lees hieronder de đŸ“– handleiding in het Nederlandse voor LG LKAEH18B (4 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 17 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/4
ELECTRIC HEATERS
INSTALLATION INSTRUCTIONS
Models: LKAEH052, LKAEH102, LKAEH152,
LKAEH09B, LKAEH18B, LKAEH36B, LKAEH36BL
• Please read this instruction sheet completely before installing the product.
• Installation work must be performed in accordance with national wiring standards by authorized
personnel only.
P/No.: 3828A30038B
2
Table 1 Accessory Heaters Electrical Data
Ton
3RT
4/5RT
6.25/7.5RT
8.5/10/12.5
RT
15/17.5RT
20/25RT
Heater
Model No.
LKAEH052
LKAEH102
LKAEH052
LKAEH102
LKAEH152
LKAEH09B
LKAEH18B
LKAEH09B
LKAEH18B
LKAEH18B
LKAEH36B
LKAEH36BL
Heater
KW Rating
3.6/5.0
7.2/10.0
3.6/5.0
7.2/10.0
14.4/15.0
7.8/9.0
15.6/18.0
7.8/9.0
15.6/18.0
15.6/18.0
31.2/36.0
31.2/36.0
Control
Stages
1
1
1
1
1
1
1
1
1
1
2
2
27.6/32.2
47.4/55
29.6/34.2
49.4/57.0
69.0/79.7
30.4/35.1
50.9/58.7
35.7/41.2
56.2/64.8
56.2/64.8
97.1/112.1
97.1/112.1
60/60
60/60
60/60
60/60
90/90
60/60
70/70
60/60
70/70
70/70
125/125
125/125
60/60
60/60
60/60
60/60
90/90
60/60
70/70
60/60
70/70
70/70
125/125
125/125
-
-
-
-
-
33.0/38.1
53.3/61.5
42.0/48.4
62.4/72.0
62.4/72.0
103.4/119.3
103.4/119.3
-
-
-
-
-
60/60
70/70
60/60
80/80
80/80
125/125
125/125
-
-
-
-
-
60/60
70/70
60/60
80/80
80/80
125/125
125/125
Heater
Rated Volts
208-240/60/1
208-240/60/1
208-240/60/1
208-240/60/1
208-240/60/1
208-240/60/3
208-240/60/3
208-240/60/3
208-240/60/3
208-240/60/3
208-240/60/3
208-240/60/3
Standard indoor fan motor
M.C.A M.C.AM.F.S M.F.SM.C.B M.C.B
Over size indoor motor
Note; Heater KW ratings are at 208/240V for 220V unit.
M.C.A; Minimum Circuit Ampere
M.F.S; Maximum Fuse Size
M.C.B; Maximum Circuit Breaker
* HACR type Circuit Breaker per NEC.
Installation
1. Loosen the screw that secures heater
compartment access panel. Lift up, pull
towards you and slide it down to remove.
2. Remove four(4) screws from block off panel
to expose heater cavity and heaterʼs back
support bracket. Save screws for installing
heater later.(See Figure 2.)
Heater Access Panel
Compressor Access Panel
Figure 1
Figure 2
: Open and lock unit disconnect
switch before installing this accessory to prevent
injury or death due to electrical shock or contact
with moving parts.
WARNING
Support
Bracket
Block off panel
Heater Cavity
3
Heater and Control Box Assembly
3. Insert heater into the opening hole of heater
control box.
4. Align holes and secure screws to the control
box as shown in Figure 3.
Single Bank Heater Installation
-
LKAEH052, LKAEH102, LKAEH152,
LKAEH09B, LKAEH18B, LKAEH36BL
5. Place the heater control assembly in the
heater cavity.
6. Secure the heater control assembly of
heater cavity using four(4) screws. (See
Figure 4.)
Important: Make sure the heater arm slides
into heaterʼs back support bracket.
Two Bank Heaters Installation
-
LKAEH36B
7. For two heaters installation, align holes and
secure screws to the control box as shown
in Figure 3.
8. Secure the heater control assembly on
heater cavity using four(4) screws.(See
Figure 5)
Important: Make sure the heaterʼs arm slides
into heaterʼs back support bracket.
Heater Control Box
Heater
Figure 3
Figure 4
Figure 5


Product specificaties

Merk: LG
Categorie: Niet gecategoriseerd
Model: LKAEH18B

Heb je hulp nodig?

Als je hulp nodig hebt met LG LKAEH18B stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd LG

LG

LG FFH-976AD Handleiding

25 November 2024
LG

LG LX-330 Handleiding

23 November 2024
LG

LG LRE3027ST Handleiding

22 November 2024
LG

LG LDG3015SW Handleiding

22 November 2024
LG

LG ST-750X Handleiding

4 November 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd