Installation Instructions
Temperature transmitters
TA3xxx
TA4xxx
TA5xxx
TU3xxx
TU4xxx
TU5xxx
80288981 / 00 09 / 2019
UK
2
1 Safety instructions
• The device described is a subcomponent for integration into a system.
- The manufacturer of the system is responsible for the safety of the system.
- The system manufacturer undertakes to perform a risk assessment and to
create a documentation in accordance with legal and normative requirements
to be provided to the operator and user of the system. This documentation
must contain all necessary information and safety instructions for the operator,
the user and, if applicable, for any service personnel authorised by the
manufacturer of the system.
• Read this document before setting up the product and keep it during the entire
service life.
• The product must be suitable for the corresponding applications and
environmental conditions without any restrictions.
• Only use the product for its intended purpose (→ Functions and features).
• Only use the product for permissible media (→ Technical data).
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
• Installation, electrical connection, set-up, operation and maintenance of the unit
must be carried out by qualified personnel authorised by the machine operator.
• Protect units and cables against damage.
2 Functions and features
The unit detects the medium temperature and converts it into an analogue output
signal.
3
UK
3 Function
Fig. 1: Current output TAxxxx:
In the measuring range the output
signal is between 4 and 20 mA.
If the temperature is above or below
the measuring range, the analogue
output behaves as follows:
Temperature above the measuring
range: 20...20.6 mA.
Temperature below the measuring
range: 4...3.7 mA.
MAW MEW
20
20.6
4
3.7
T [°C/°F]
I [mA]
Fig. 2: Voltage output TUxxxx:
In the measuring range the output
signal is between 0.5 und 4.5 V.
If the temperature is above or below
the measuring range, the analogue
output behaves as follows:
Temperature above the measuring
range: 4.5...5V.
Temperature below the measuring
range: 0.5..0 V.
MAW MEW
4.5
5
0.5
T [°C/°F]
U [V]
T = Temperature
MAW = initial value of the measuring range
MEW = final value of the measuring range


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: TA5105

Heb je hulp nodig?

Als je hulp nodig hebt met IFM TA5105 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM TAD981 Handleiding

26 November 2024
IFM

IFM TAD961 Handleiding

26 November 2024
IFM

IFM TAD091 Handleiding

26 November 2024
IFM

IFM TAD181 Handleiding

26 November 2024
IFM

IFM MK5344 Handleiding

15 November 2024
IFM

IFM OL5029 Handleiding

15 November 2024
IFM

IFM EVC284 Handleiding

15 November 2024
IFM

IFM OB5022 Handleiding

15 November 2024
IFM

IFM AL4302 Handleiding

15 November 2024
IFM

IFM AC1006 Handleiding

12 November 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd