Installation Instructions
Flow sensor
SF ceramics
701777 / 03 06 / 2011
UK
2
1 Functions and features
In conjunction with the VS3000 control monitor the flow sensor monitors flows
in liquids. The sensor / control monitor combination senses whether there is a
preset flow rate (= medium flowing) or not (= medium not flowing) and provides a
switched signal.
2 Installation
The sensor tip must be completely immersed in the medium.
• In the case of horizontal pipes mount the unit from the side, if possible (fig. 1).
- When the unit is to be mounted at the bottom of the pipe, it should be free
from deposits.
- When the unit is to be mounted at the top of the pipe, it should be completely
filled with the medium to be monitored.
• In the case of vertical pipes mount the unit in a place where the medium flows
upwards (fig. 2).
A
B
1
A
B
2
A: mounting bush; B: packing washer
for units with thread
G¼ G½
Mounting bush (A) 15 mm 33 mm
Max. tightening torque 8 Nm 30 Nm
The thread of the mounting bush must be clean, undamaged and comply
with the standard (pipe thread to DIN ISO 228).
For sealing use the supplied PTFE packing washer.
3
UK
To avoid malfunction a minimum distance between the flow monitor and bends,
valves or such like must be observed. Min. 5 x pipe diameter upstream (A), min.
3 x pipe diameter downstream (B).
D
A
B
min.
5 x D
min.
3 x D
3
3 Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Connection to control monitor VS3000; voltage supply to EN50178, SELV,
PELV.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a sec-
ondary Listed fuse rated either
a) max 5 amps for voltages 0~20 Vrms (0~28.3 Vp) or
b) 100/Vp for voltages of 20~30 Vrms (28.3~42.4 Vp).


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: SF2405

Heb je hulp nodig?

Als je hulp nodig hebt met IFM SF2405 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM MK5344 Handleiding

15 November 2024
IFM

IFM OL5029 Handleiding

15 November 2024
IFM

IFM EVC284 Handleiding

15 November 2024
IFM

IFM OB5022 Handleiding

15 November 2024
IFM

IFM AL4302 Handleiding

15 November 2024
IFM

IFM AC1006 Handleiding

12 November 2024
IFM

IFM AC1345 Handleiding

12 November 2024
IFM

IFM CR3122 Handleiding

12 November 2024
IFM

IFM DV1531 Handleiding

12 November 2024
IFM

IFM DV1501 Handleiding

12 November 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd