Installation Instructions
Electronic pressure sensor
PX9224
PX9227
704904 / 00 08 / 2010
UK
2
1 Safety instructions
• Please read the product description prior to installing the unit.
• Ensure that the product is suitable for your application without any restrictions.
• If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
• Please check for all applications that the product materials (see Technical data)
are compatible with the media to be measured.
For the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size Maximum protective device rating
Ampere
AWG (mm2)
26 (0.13) 1
24 (0.20) 2
22 (0.32) 3
20 (0.52) 5
18 (0.82) 7
16 (1.3) 10
The Sensor shall be connected only by using any R/C (CYJV2) cord, having
suitable ratings.
Contents
1 Safety instructions ................................................................................................2
2 Function and features ...........................................................................................3
2.1 Applications ....................................................................................................3
3 Installation ............................................................................................................3
4 Electrical connection.............................................................................................3
5 Scale drawing .......................................................................................................4
6 Technical data .......................................................................................................5
3
UK
2 Function and features
The pressure sensor detects the system pressure and converts it into an analog
output signal.
• 1...5 V
2.1 Applications
• Type of pressure: relative pressure
Order no. Measuring range Permissible
overload pressure
Bursting
pressure
PSI PSI PSI
PX9224 0...100 1 087 2 175
PX9227 0...15 145 450
Static and dynamic overpressures exceeding the indicated overload
pressure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the bur-
sting pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
3 Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
► Insert the unit in a ¼“ NPT process connection.
â–º Tighten firmly.
4 Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply to EN50178, SELV, PELV.


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: PX9227

Heb je hulp nodig?

Als je hulp nodig hebt met IFM PX9227 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM TAD981 Handleiding

26 November 2024
IFM

IFM TAD961 Handleiding

26 November 2024
IFM

IFM TAD091 Handleiding

26 November 2024
IFM

IFM TAD181 Handleiding

26 November 2024
IFM

IFM MK5344 Handleiding

15 November 2024
IFM

IFM OL5029 Handleiding

15 November 2024
IFM

IFM EVC284 Handleiding

15 November 2024
IFM

IFM OB5022 Handleiding

15 November 2024
IFM

IFM AL4302 Handleiding

15 November 2024
IFM

IFM AC1006 Handleiding

12 November 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd