Operating instructions
(Ex protection related part) for Inductive proximity switches / Capacitive
proximity switches / Photoelectric sensors / Speed monitors / Pressure
sensors / Flow sensors according to EU directive 94/9/EC Annex VIII
(ATEX) group II, equipment category 3D
2
Instructions for the safe use in hazardous areas
Function and features
Use in hazardous areas according to the classification•
II 3D
(group II, category 3D, apparatus for dust atmosphere).
The requirements of the EN50014 and EN50281-1-1 standards are met.
Shock test to EN60947-5-2 with 0.5 Joule.
Marking (see unit or technical data sheet)•
II 3D IP67 T = 80°C X -20°C =< Ta <= 60°C
II 3D IP65 T = 80°C X -20°C =< Ta <= 60°C
II 3D IP65 T = 95°C X -20°C =< Ta <= 60°C
Permissible operating temperature of the application (proper usage):•
- 20 to + 60 °C
Installation / Set-up
The units should only be mounted, connected and set up by qualified staff. The qualified
staff must have knowledge of protection classes, regulations and provisions for apparatus in
hazardous areas.
Check whether the classification (see „Marking“ above and marking on the unit) is suitable
for the application.
Installation remarks / Mounting
Adhere to the respective national regulations and provisions as well as the relevant •
installation regulations.
Avoid electrostatic charging from plastic units and cables.•
To avoid electrostatic charging clean the unit with a damp cloth only.•
Do not mount the unit in the dust flow.•
Avoid dust deposits on the units.•
Protect the units and the cables efficiently against damage.•
For the connections and the electrical technical data please see the unit marking or the •
technical data sheet.
Remove any cover plugs from the cable gland or the plug upon introducing the cables or •
screwing on the socket to avoid soiling.
3
UK
Special conditions for safe operation
For units with terminal chamber (cable gland) and for cabled units sufficient strain relief •
must be ensured or the cable must be firmly laid.
Do not disconnect the cables of units with terminal chamber while live.•
For units with connector the connector must be secured so that it cannot be separated •
without using a tool. To do so, use lock rings. They are available as accessories (order no.
E11532 for M12 sockets with max. 11 mm wide nut).
As an alternative ifm sockets with hexagonal nut can be used. Secure the connector by •
tightening the nut sufficiently (tightening torque: minimum 0.6 Nm, maximum 0.8 Nm).
If you do not use ifm sockets, ensure by means of a sufficient tightening torque that the nut •
cannot be loosened manually.
Do not disconnect the connector while live.•
Apply a durable warning in suitable form close to the connector reading: „Do not separate •
plug while energized“ or use the enclosed label if you can ensure a durable marking.
Note: insert a miniature fuse according to the technical data sheet, if specified. Place the •
fuse outside the hazardous area.
Maintenance / Repair
The unit must not be modified nor can it be repaired.
In case of a fault please contact the manufacturer.
If you need the technical data sheets and the CE declaration of conformity covering the units
please contact the manufacturer. Always indicate the article number.
Recommendation: check the unit for reliable function after a short circuit.


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: IN503A

Heb je hulp nodig?

Als je hulp nodig hebt met IFM IN503A stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM MK5344 Handleiding

15 November 2024
IFM

IFM OL5029 Handleiding

15 November 2024
IFM

IFM EVC284 Handleiding

15 November 2024
IFM

IFM OB5022 Handleiding

15 November 2024
IFM

IFM AL4302 Handleiding

15 November 2024
IFM

IFM AC1006 Handleiding

12 November 2024
IFM

IFM AC1345 Handleiding

12 November 2024
IFM

IFM CR3122 Handleiding

12 November 2024
IFM

IFM DV1531 Handleiding

12 November 2024
IFM

IFM DV1501 Handleiding

12 November 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd