IFM DI0002 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor IFM DI0002 (3 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 19 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/3
Installation instructions
Compact speed monitor
DIA
701092 / 03 09 / 2007
UK
UK
UK
UK
UK
2
1 Functions and features
The Compact speed monitor detects without contact whether a minimum speed is
reached and signals underspeed by means of a switching signal.
Nominal sensing range (Sn) 10 mm; Preset speed adjustable, see type label.
2 Installation
E
A
BC
D
F
A
B
C
³F
³2 x A
½ x Sn
D
E
Fix the unit by means of a mounting device and secure it by means of the nuts
provided so that it cannot work loose. Flush installation.
Adhere to the above dimensions to ensure a correct function.
3 Electrical connection
Disconnect power.
Connect the unit according to the indications on the type label.
Note: insert a miniature fuse according to the technical data sheet, if specified.
Recommendation: check the safe functioning of the unit after a short circuit.
â–º
â–º
â–º
â–º
3
UK
4 Adjustment
1
2
LEDs
Green LED: output switched (actual
speed > preset speed)
Yellow LED (optional for 2-wire AC/DC):
sensor damped
multiturn potentiometer
preset value
1.
2.
Keep the speed to be monitored in the plant on a constant level.
The yellow LED must flash (damping pulses are detected).
Start the adjustment according to A or B when the start-up delay* (AÜ see type
label) has elapsed.
A
Green LED lit
B
Green LED not lit
Turn the pot clockwise until the LED goes
off.
Turn the pot slowly anticlockwise until the
LED is lit.
Turn the pot slowly anticlockwise until the
LED is let.
—
On delivery: pot at the right end stop (except DI5011 = approx. 30 pulses/min).
5 Operation
The operation is maintenance-free. Ensure the following for a correct function:
Keep the sensing face and the open space free of metal deposits and foreign
bodies.
Do not operate units with high field intensity (e.g. walkie-talkies) at close range
to the speed monitor.
*) The start-up delay (AÜ) suppresses an error signal as long as the machine is in
the process of starting and has not yet reached its nominal speed. After applica-
tion of the operating voltage the start-up delay is active only once.
If the drive is often turned on and off, couple the supply voltage of the drive and
the monitor. By doing so, the start-up delay is active every time the drive is turned
on.
â–º
â–º
â–º
â–º


Product specificaties

Merk: IFM
Categorie: Niet gecategoriseerd
Model: DI0002

Heb je hulp nodig?

Als je hulp nodig hebt met IFM DI0002 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd IFM

IFM

IFM TAD981 Handleiding

26 November 2024
IFM

IFM TAD961 Handleiding

26 November 2024
IFM

IFM TAD091 Handleiding

26 November 2024
IFM

IFM TAD181 Handleiding

26 November 2024
IFM

IFM MK5344 Handleiding

15 November 2024
IFM

IFM OL5029 Handleiding

15 November 2024
IFM

IFM EVC284 Handleiding

15 November 2024
IFM

IFM OB5022 Handleiding

15 November 2024
IFM

IFM AL4302 Handleiding

15 November 2024
IFM

IFM AC1006 Handleiding

12 November 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd