Honeywell Home THM6000R7001/U Handleiding

Honeywell Thermostaat Home THM6000R7001/U

Lees hieronder de 📖 handleiding in het Nederlandse voor Honeywell Home THM6000R7001/U (16 pagina's) in de categorie Thermostaat. Deze handleiding was nuttig voor 107 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/16
Prestige® IAQ
with Equipment Interface Module
Installation Guide
TM
TM
TM
OR
2 Wires for Power
2 Wires for Power
RedLINK to Equipment Interface Module
RedLINK to rTrueZONE Wireless Adapte
2
Current display. Button pressed in
signifies current display
Mode control buttons. Use to change
settings for Fan or System Heat/Cool.
Menu. Select options to: set schedules,
view equipment status, change IAQ
settings, access installer options*, etc.
Current schedule. Shows desired
temperature and schedule status.
Indoor conditions. Shows indoor
temperature and humidity.
Current date and time.
Current status. Shows system mode
(heat/cool), outdoor temperature
and humidity (with optional outdoor
sensor).
USB port. Use USB device to load
settings and dealer information.
Reference to key features
* Password is date code.
Getting started
Follow these basic steps to install this
thermostat, link it with the equipment
interface module (EIM) and wireless
accessories and
set installer options.
1 Installing the Equipment Interface
Module (EIM)
2 Installing the thermostat
3 Powering optional RedLINK accessories
4 Performing initial setup
5 Finding your password (Date Code)
• To add or remove RedLINK accessories
• To make changes to Installer Setup
• To perform an Installer Test
• To view Data Logs
1624
1624
Thermostat (back view)
Password
(Date Code)
3
NOTE: If an EIM is mounted inside a metal cabinet, it is recommended to
use a THM4000R1000 Wireless Adapter for extended wireless range. Mount
the Wireless Adapter outside the metal cabinet and connect to the ABCD
terminals at the EIM.
NOTE: When installing multiple
thermostats and EIMs, mount
the EIMs at least 2 feet apart for
best RedLINK performance.
1.1 Mount EIM.
Mount the EIM near the HVAC
equipment or on the equipment
itself.
Use screws and anchors as
appropriate for the mounting
surface.
1.2 Wire EIM as shown.
Refer to the table and wiring diagrams on pages 3-5.
NOTE: If you are installing discharge and return air sensors, refer to the
mounting instructions in the Alerts and Delta T Diagnostics Installation
Instructions packed in the kit.
1
Installing the equipment interface module (EIM)
Terminal Designations
Conventional System Heat Pump
Terminal Description Terminal Description
CCommon wire from 24 VAC
transformer. CCommon wire from 24 VAC
transformer.
R* Power wire from 24 VAC
transformer. RPower wire from 24 VAC
transformer.
RH* Heating power. RH Heating power.
RC* Cooling power. RC Cooling power.
W Heat Stage 1 O/B Changeover valve for heat pumps.
W2 Heat Stage 2 AUX 1 Backup Heat Stage 1/Emergency
Heat Stage 1
W3 Heat Stage 3 AUX 2 Backup Heat Stage 2/Emergency
Heat Stage 2
Y Compressor Stage 1 Y Compressor Stage 1
Y2 Compressor Stage 2 Y2 Compressor Stage 2
G Fan Relay G Fan Relay
AConnect to Economizer Module or
Lighting Panel (TOD). L/A
Connect to Compressor Monitor,
Zone Panel, Economizer Module
or Lighting Panel (TOD).
* Remove jumpers when separate transformers are used.
R
C
Y
Y2
G
W
O/B
W2
AUX1
W3
AUX2
A
L/A


Product specificaties

Merk: Honeywell
Categorie: Thermostaat
Model: Home THM6000R7001/U

Heb je hulp nodig?

Als je hulp nodig hebt met Honeywell Home THM6000R7001/U stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Thermostaat Honeywell

Handleiding Thermostaat

Nieuwste handleidingen voor Thermostaat