Honeywell FCPS-24FS6 Handleiding
Lees hieronder de đź“– handleiding in het Nederlandse voor Honeywell FCPS-24FS6 (48 pagina's) in de categorie Detector. Deze handleiding was nuttig voor 43 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/48
J2
P/N 51883-L8:J2 ECN 14-570
Document 51883-L8
7/11/2014 Rev:
2FCPS-24FS Series Instruction Manual — P/N 51883-L8:J2 7/11/2014
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notifi-
cation capability—can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of
an automatic fire alarm system (as described above) and a life
safety communication system that may include an autonomous
control unit (ACU), local operating console (LOC), voice commu-
nication, and other various interoperable communication meth-
ods—can broadcast a mass notification message. Such a
system, however, does not assure protection against property
damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premises following
the recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of
System Smoke Detectors, which is made available at no charge
to all installing dealers. This document can be found at http://
www.systemsensor.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United
States government) indicated that smoke detectors may not go
off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-floor
or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, chim-
neys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reach-
ing the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at var-
ious levels of smoke density. If such density levels are not cre-
ated by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing cham-
bers tend to detect smoldering fires better than flaming fires,
which have little visible smoke. Detectors that have ionizing-type
sensing chambers tend to detect fast-flaming fires better than
smoldering fires. Because fires develop in different ways and
are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide
adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn-
ing of fires caused by arson, children playing with matches
(especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi-
als, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detec-
tors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for
the connection of alarm transmission wiring, communications,
signaling, and/or power. If detectors are not so located, a devel-
oping fire may damage the alarm system, compromising its abil-
ity to report a fire.
Audible warning devices such as bells, horns, strobes,
speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device
may fail to alert people with a disability or those who have
recently consumed drugs, alcohol, or medication. Please note
that:
• An emergency communication system may take priority over
a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be designed to meet intelligi-
bility requirements as defined by NFPA, local codes, and
Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis-
seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear
a fire alarm signal, do not respond to or comprehend the
meaning of the signal. Audible devices, such as horns and
bells, can have different tonal patterns and frequencies. It is
the property owner's responsibility to conduct fire drills and
other training exercises to make people aware of fire alarm
signals and instruct them on the proper reaction to alarm sig-
nals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat-
ible with the control panel. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem-
ises to a central monitoring station may be out of service or tem-
porarily disabled. For added protection against telephone line
failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is
inadequate maintenance. To keep the entire life safety system in
excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFPA 72 shall be fol-
lowed. Environments with large amounts of dust, dirt, or high air
velocity require more frequent maintenance. A maintenance
agreement should be arranged through the local manufacturer's
representative. Maintenance should be scheduled monthly or as
required by National and/or local fire codes and should be per-
formed by authorized professional life safety system installers
only. Adequate written records of all inspections should be kept.
Limit-D-1-2013
FCPS-24FS Series Instruction Manual — P/N 51883-L8:J2 7/11/2014 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software. Re-
acceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49Âş
C/32-120º F and at a relative humidity 93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27Âş C/60-80Âş F.
Verify that wire sizes are adequate for all initiating and indi-
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-
tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Product specificaties
Merk: | Honeywell |
Categorie: | Detector |
Model: | FCPS-24FS6 |
Kleur van het product: | Rood |
Breedte: | 368.3 mm |
Diepte: | 69.85 mm |
Hoogte: | 381 mm |
Stroom: | 3.2 A |
Certificering: | ULC |
Aantal per verpakking: | 1 stuk(s) |
Ingangsspanning: | 120 V |
Soort apparaat: | Bedieningspaneel brandmelding |
Frequentie: | 60 Hz |
Totaal vermogen: | - W |
Triggerstroom: | 2 mA |
AC-ingangsspanning: | 120 V |
AC-ingangsfrequentie: | 60 Hz |
Type product: | Voeding |
Maximale ingangsstroom (@110V): | 3.2 A |
Hulpstroom: | 500 mA |
Triggerspanning: | 9 - 32 V |
DC contactclassificatie: | 5 A at 24 VDC |
Oplaadcapaciteit van batterij: | Ja |
Heb je hulp nodig?
Als je hulp nodig hebt met Honeywell FCPS-24FS6 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Detector Honeywell
11 Juni 2023
8 April 2023
2 April 2023
Handleiding Detector
- Detector Bosch
- Detector Garmin
- Detector Gigaset
- Detector Pioneer
- Detector Abus
- Detector Alecto
- Detector Amprobe
- Detector AngelEye
- Detector Astralpool
- Detector Axis
- Detector Beha-Amprobe
- Detector Brennenstuhl
- Detector BRK
- Detector Denver
- Detector Dometic
- Detector Duro
- Detector Ebode
- Detector Elro
- Detector Extech
- Detector Ferguson
- Detector Ferrex
- Detector FireAngel
- Detector Flir
- Detector Fluke
- Detector Gamma Scout
- Detector Gossen
- Detector Grothe
- Detector Hager
- Detector Hikvision
- Detector Iget
- Detector Konig
- Detector Laserliner
- Detector Maginon
- Detector Marquant
- Detector Mercury
- Detector Metrix
- Detector National Geographic
- Detector Nedis
- Detector Netatmo
- Detector PCE Instruments
- Detector Powerfix
- Detector Pyle
- Detector Royal Sovereign
- Detector Sanwa
- Detector Satel
- Detector Siedle
- Detector Silverline
- Detector Skil
- Detector Smartwares
- Detector Steinel
- Detector Techno Line
- Detector Toolcraft
- Detector Trotec
- Detector Uniden
- Detector V-Tac
- Detector Velleman
- Detector Voltcraft
- Detector X4-Tech
- Detector Xavax
- Detector Joy-it
- Detector Jung
- Detector Olympia
- Detector Optex
- Detector Black And Decker
- Detector Schwaiger
- Detector Soler And Palau
- Detector Safescan
- Detector Cobra
- Detector Sauter
- Detector Sun Joe
- Detector Techly
- Detector DSC
- Detector Fisher
- Detector Garrett
- Detector Genie
- Detector Tripp Lite
- Detector Nexa
- Detector EVOLVEO
- Detector Whistler
- Detector Vemer
- Detector Ei Electronics
- Detector FireX
- Detector GEV
- Detector AcuRite
- Detector Testo
- Detector System Sensor
- Detector Testboy
- Detector IFM
- Detector Kyoritsu
- Detector Dahua Technology
- Detector Busch-Jaeger
- Detector Popp
- Detector Homematic IP
- Detector X-Sense
- Detector Kreator
- Detector ORNO
- Detector Multimetrix
- Detector Vimar
- Detector Escort
- Detector ZKTeco
- Detector Inovonics
- Detector Guardian Avionics
- Detector Thitronik
- Detector Cavius
- Detector Chauvin Arnoux
- Detector Pentatech
- Detector Flow Smoke Detector
- Detector Benewake
- Detector BeeSecure
- Detector Resideo
- Detector SureCall
- Detector Schabus
- Detector Zircon
- Detector STI
- Detector HT Instruments
- Detector BlendMount
- Detector K40
- Detector Gewiss
- Detector Seco-Larm
- Detector Seaward
- Detector Silent Knight
- Detector S.E. International
- Detector Rocky Mountain
- Detector Skyscan
- Detector Bearware
- Detector Winland
- Detector Noyafa
Nieuwste handleidingen voor Detector
30 November 2024
18 November 2024
17 November 2024
17 November 2024
16 November 2024
16 November 2024
15 November 2024
15 November 2024
15 November 2024
5 November 2024