Hager JKD146TM Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Hager JKD146TM (3 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 28 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/3
Pozidrive PZ2 4.5mm
All product(s) must be installed by a suitably competent electrician
giving consideration to their intended use and in accordance with the
current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work
Act shall be complied with.
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used
Install in the vertical plane only.
Notice:
To prevent potential overheating from loose connections the installer
shall check connections are tightened to the torque levels stated in
these instructions prior to energising this board. This check should
include factory made connections which may have loosened in transit.
JKD1***TM Notice d’instructions
User instructions
Bedienungsanleitung
Instrucciones de uso
Instruções
Bruksanvisning
Gebruiksaanwijzing
Pozidrive PZ2
2.5
Designation H W D
JKD146TM 1100 465 165.5
JKD166TM1100 465 165.5
JKD164TM1100 465 165.5
JKD168TM1250 465 165.5
JKD188TM
1250
465 165.5
JKD186TM1250 465 165.5
JKD1416TM1400 465 165.5
JKD1164TM1400 465 165.5
JKD1812TM1400 465 165.5
JKD1128TM1400 465 165.5
JKD11212TM1400 465 165.5
Warranty
This distribution board is offered with a 24 month warranty against
defective material or manufacture. If a warranty claim is necessary,
please call the technical support number given at the bottom of the page
and we will be pleased to help.
Interface Characteristics
Rated & operational voltage (U
n / Ue)
415V a.c. 50Hz
Rated insulation voltage (U
i)
690V a.c. 50Hz
Rated impulse withstand voltage (U
imp)
4kV
Rated current of the Assembly (I
nA)
JKD1xx 125ATM
Rated current of an Outgoing circuit (I
nC)
MCB 0.5A - 63A (marked rated current on device)
RCBO 6A - A (marked rated current on device)45
Rated Current of Pan Assembly
Upper Pan I
nc =125A
Lower Pan = 125AInc
Rated conditional short-circuit current of the ASSEMBLY (I
cc)
10kA
1 with equipment and arrangements specied in Hager’s technical
documentation / catalogue.
MCB/RCBO 10kA rating applied as BS EN 61439-3 is intended for use
by ordinary persons.
1
Current limitation characteristics specied in Hager’s technical
documentation / catalogue
Protection against electric shock
DBO shall be installed in an electrical system conforming to IEC 60364 /
BS 7671
Rated diversity factor (RDF)
10 way - 24 way = 0.7
Note: RDF only applies to continuously and simultaneously loaded
circuits.
Rated frequency (fn)
50 Hz
Pollution degree
2
Types of system earthing for which the ASSEMBLY is designed
TNC-S, TN-S and TT when installed in an electrical system conforming
to BS 7671
Intended locations
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP3XD with Door Closed
IP2XC with Door Open and compliment of outgoing devices and or
blanks tted.
Intended use
Distribution boards intended to be operated by ordinary persons (DBO)
Electromagnetic compatibility (EMC) classification
EMC Environment B
External design
Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection
IK05
The type of construction
Fixed parts
DBO Type
Type B DBO
Accessories
JK01B Single Pole Blank
JK222PK JK1 / JK2 Door Lock Kit
JK1PLATEM Gland Plate + Drill Markings
Hager Technical Help Line: 01952 675 689
Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk
E-mail us: info@hager.co.uk
Twitter: @hageruk
GB
ZD0895ZD0895 14
ZD0895ZD0895
Invicta 3
JK1 SP01 D* Type I/2 Surge protection Kit
JK1 P02S D* Type II Surge Protection Kit
Power & Lighting Boards
Width
Height
Depth
T =
Min. 2.8Nm
Max. 3.5Nm
L1
L2
1
2
7
8
ISOLATE SUPPLY
BEFORE REMOVING COVER
L1
L2
1
7
8
9
ISOLATE SUPPLY
BEFORE REMOVING COVER
Lighting
Supply
Sockets
First Floor
L1
L2
L3
1
2
3
7
8
9
L1
L2
L3
4
5
6
10
11
12
Pozidrive PZ2
Pozidrive PZ2
Points with central
‘easy t’ xing point
Drill centre mark provided when tting SWA or conduit
Removal of gland plate
Cable protection
built into end plate
for trunking entry
Protected cable whilst
drawing into board without
need for SRBP / Paxolin
laminated sheet
Pozidrive PZ2
Fitting MCB / RCBO
Ability to number outgoing ways
on busbar stack Ability to write on with
pencil when installing.
Dedicated label pack
for front cover way
labelling
32 ZD0xxx
ZD0xxx


Product specificaties

Merk: Hager
Categorie: Niet gecategoriseerd
Model: JKD146TM

Heb je hulp nodig?

Als je hulp nodig hebt met Hager JKD146TM stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Hager

Hager

Hager FN296E Handleiding

16 November 2024
Hager

Hager FN117E Handleiding

16 November 2024
Hager

Hager FN097E Handleiding

16 November 2024
Hager

Hager FN367E Handleiding

16 November 2024
Hager

Hager MZN131 Handleiding

16 November 2024
Hager

Hager EG203 Handleiding

16 November 2024
Hager

Hager GS11019016 Handleiding

16 November 2024
Hager

Hager JK132E Handleiding

5 Januari 2024
Hager

Hager JK101SE Handleiding

5 Januari 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd