Hager JK310H Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Hager JK310H (2 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 29 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
JKA Boards
Instructions/Data Sheet
This DBO and Hager devices conform with the following standards:
Meter Direct Fed EN 50470
BS EN 61439-3 including Annex ZB.
Switch-disconnectors: BS EN 60947-3.
Residual Current Circuit Breaker (RCCB): BS EN 61008-1
Residual current operated circuit breaker with integral overload (RCBO): BS EN 61009-1
Miniature Circuit Breaker (MCB): BS EN 60898-1
Installation Instructions:
All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with
the current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work
Act shall be complied with.
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used.
Install in the horizontal plane only.
Important notice:
To prevent potential overheating from loose connections the installer
shall check connections are tight to the torque levels stated in these
instructions prior to energizing this board. This check should include
factory made connections which may have loosened in transit.
Tightening torque values to be applied (Nm)
Switch-disconnector’s: 40A & 63A: 2.8 Nm
Switch-disconnector’s: 100A: 3.6 Nm
RCCB’s 40A & 63A: 2.8 Nm
RCCB’s 80A & 100A: 3.3 Nm
MCBs: 2.8 Nm
RCBO’s: 2.8 Nm
Earth & Neutral terminal bar connections: 2.0 Nm
Single conductors below 1.5mm² need to be doubled back in the
terminal bar
Front metal cover xing screws: 2.0 Nm
Meter torque: 2.4 Nm
Good workmanship and proper materials must be applied by the
installer. The cable entry method shall, as far as reasonably practical,
maintain the non-combustable arrangement of the enclosure.
Account shall be taken of these instructions.
Metalclad units are provided with knockouts for standard 20, 25,
and 32mm conduit and large rear knockouts.
Pull and lift the terminal bar support away from the unit resting
the rail supported by the earth strap. After xing conduit/ cable
glands, locate the rail support and press down.
Note: Only BASEC approved cable should be used
1.0mm2 to 16mm2 for outgoing cables
up to 35.0mm2 for incoming live cables
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
Cable entry facilities: Metal Unit - Removing and replacing the terminal rail for
cabling:
ZD0651 - Issue 4 03-15 - Issue 4 03-15ZD0651
JKA Boards
Instructions Sheet
JKA Boards
Instructions Sheet
ZD0651
ZD0651
ZD0651
ZD0651
4 1
GB
MCB
tripped
Use circuit as
normal
Use circuit as
normal
Unplug faulty
appliance until
repaired. Reset device.
Other appliances m ay
be used
Try & reset device once
Try & reset device once
Turn
OFF
all MCBs devices
Reset RCC B
Turn O N MCBs
devices one at a time
until RCCB trips again,
identifying faulty circuit
Unplug all
appliances from
circuit and reset
device / replace fuse*
Plug in & switch on
appliances one at a time
until device trips / blows,
identifying faulty appliance
What device
is it?
Does device
stay O N ?
Does device
stay O N ?
Does device
stay O N ?
Does device
supply socket
outlets
Does device
stay O N ?
STA R T
YES
YES
YES
YES
YES
MCB
or
RCB O RCC B
N O
N O
N O
N O
N O
T
T
T
ON ON ON
Blank RCCB RCBO (two module) MCB RCBO Switch
(one module)
Painted Metal Enclosure
Dimensions
(mm)
Enclosure Size
8 12 16 22 2x12 2x16 2x22 3x22
A 254 326 398 505 326 398 505 505
B 236 236 236 236 472 472 472 708
C N/A N/A N/A N/A N/A N/A N/A N/A
D 125 125 125 125 125 125 125 125
AD
B
Guidance Notes:
The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral
and earth connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.
A pack is provided to label this DBO, please consult us for spares or replacements.
Operating Instruction leaet is provided overleaf. This leaet should be left for the end user.
Single conductors below 1.5mm² need to be doubled back in the terminal bar.
DBOs incorporating RCDs in TT systems should incorporate an S type (time Delayed) RCCB, e.g. 100 mA s-type RCCB . Alternatively a main
switch with RCBO protection on all outgoing circuits should be used.
Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)
IP Ratings:
Cable access into the DBO must maintain the integrity so far as reasonably practicable. In essence, for surfaces accessible after installation,
this means maintaining the requirement for the horizontal top surface of the enclosure to provide a degree of protection of at least IP4X and
elsewhere, IP30. For rear cable access, the minimum number of knockout(s) shall be removed.
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please
call the technical support number given at the bottom of the page and we will be pleased to help.
For dimensional information and weights please consult the Hager catalogue.
Hager Technical Help Line: 01952 675 689
Hager Technical Fax: 01952 675 557
Website: www.hager.co.uk
E-mail us: info@hager.co.uk
Fitting Hager MCBs and RCBOs:
Only equipment and arrangements specied in Hager’s technical
documentation / catalogue shall be used.
1. Isolate the electrical supply from the DBO.
2. Remove the front cover.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip (g 1.)
5. Locate the device onto the din rail, and busbar. Ensure that the
busbar tooth is within the device terminal cage.
6. Close the bottom device clip.
7. While holding the device rmly onto the busbar, fully tighten the
lower terminal screw.
8. After tting all outgoing devices and connecting all outgoing
cables, please check the tightness of all cable connections. This
should include all factory made connections, which may have
loosened during installation or transit.
g 1.
IP Code Description
IP2XC Protection against access
with a tool (2.5mm diameter,
100mm long) making contact
with live hazardous parts
IP30 Protection against access with
a tool (2.5mm diameter, shall
not penetrate)
IP4X A probe of 1mm diameter
shall not enter the enclosure
ZD0651 - Issue 4 03-15 - Issue 4 03-15ZD0651
JKA Boards
Instructions Sheet
JKA Boards
Instructions Sheet
2 3
Interface characteristics
Rated & operational voltage (Un / Ue)
230V a.c. 50Hz
Rated insulation voltage (Ui)
320V a.c. 50Hz
Rated impulse withstand voltage (Uimp)
4kV
Rated current of the Assembly (InA)
100A, 63A
Note: Dependent upon rating of main incoming device
Rated current of an Outgoing circuit (Inc)
MCB 6A - 63A (marked rated current on device)
RCBO 6A - 50A (marked rated current on device)
Rated current of outgoing unit (Inc)
RCCB 40A -100A (marked rated current on device)
Direct Fed Meter - 100A (marked rated current on device)
Rated conditional short-circuit current of the ASSEMBLY (Icc)
Annex ZB: 16 kA rms at 250V, power factor 0.6 with equipment and arrangements specied in Hager’s technical documentation /
catalogue. (Does not include metered type A distribution boards)
JK A Board DBO Icc = 10kA, Ipk 17kA
Protection against electric shock
Consumer unit shall be installed in an electrical system conforming to the current edition of IEC 60364 / BS 7671
Rated diversity factor (RDF) / Values of assumed loading
1way = 1.0
2way – 3way = 0.8
4way – 5way = 0.7
6way – 9way = 0.6
10way and above = 0.5
Note: RDF only applies to continuously and simultaneously loaded
circuits.
In principle, this means adjacent circuit-breakers having a load
‘on’ time exceeding 30 minutes or where a load not exceeding 30
minutes has an ‘off’ time less than the ‘on’ time, will need to have
the rated diversity factor applied as indicated.
Rated frequency (fn)
50 Hz
Pollution degree
2
Types of system earthing for which the ASSEMBLY is designed
TNC-S, TN-S when installed in an electrical installation complying with BS 7671
Hager recommends for TT systems a 100A type S time delayed RCCB or a main switch with RCBO protection only on all outgoing circuits.
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP2XC with door open and full compliment of outgoing devices and or blanks tted.
IP30 with door closed and full compliment of outgoing devices and or blanks tted.
Note: Where cables are installed through top wall of enclosure, gaps of IP4X to be maintained.
Intended use
Intended for use in domestic (residential) or similar premises.
Electromagnetic compatibility (EMC) classication
EMC Environment B
External design
JKA: Wall-mounted, surface type, enclosed assembly.
Mechanical impact protection
IK 05
The type of construction
Fixed parts
Type A DBO (Distribution board for use by ordinary persons)
ZD0651
ZD0651
ZD0651
ZD0651


Product specificaties

Merk: Hager
Categorie: Niet gecategoriseerd
Model: JK310H

Heb je hulp nodig?

Als je hulp nodig hebt met Hager JK310H stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Hager

Hager

Hager FN296E Handleiding

16 November 2024
Hager

Hager FN117E Handleiding

16 November 2024
Hager

Hager FN097E Handleiding

16 November 2024
Hager

Hager FN367E Handleiding

16 November 2024
Hager

Hager MZN131 Handleiding

16 November 2024
Hager

Hager EG203 Handleiding

16 November 2024
Hager

Hager GS11019016 Handleiding

16 November 2024
Hager

Hager JK132E Handleiding

5 Januari 2024
Hager

Hager JK101SE Handleiding

5 Januari 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd