Hager ARF975D Handleiding

Hager Schakelaar ARF975D

Lees hieronder de 📖 handleiding in het Nederlandse voor Hager ARF975D (2 pagina's) in de categorie Schakelaar. Deze handleiding was nuttig voor 2 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
ON
Klack !
1 2
1: FI / RCD
2: AFDD
TEST Diese Anleitung ist für künftige Tests dem Endkunden zu übergeben und von diesem sorgfältig aufzubewahren!
TESTING This guide is to be given to the end customer for future tests, who should keep it in a safe place.
1. Die Einrichtung muss in kurzer Zeit (1 Sekunde)
auslösen.
2. Löst die Einrichtung nicht aus, so muss sie durch eine
Elektrofachkraft* ausgetauscht werden.
3. Die Testtaste T dient ausschließlich zum Prüfen der
Einrichtung. Wenn der Stromkreis unterbrochen werden
soll, betätigen Sie den dafür vorgesehenen Knebel.
1. The device must trip within a short time (1 second).
2. If the device does not trip, then it must be replaced by
a trained electrician*.
3. Test button T is used exclusively for testing the device.
If the circuit is interrupted, operate the toggle provided
for this purpose.
* Eine Person mit geeigneter fachlicher Ausbildung, Kenntnissen und Erfahrung sowie Kenntnis der einschlägigen Normen, so dass sie Gefahren erkennen und vermeiden kann,
die von der Elektrizität ausgehen können.
AFDD und E-Check:
Isolationsprî›™fung in Stromkreisen mit AFDD:
Wo es aus praktischen Grî›™nden nicht sinnvoll ist, zur Isolationsprî›™fung elektrische Betriebsmittel abzuklemmen, darf die Messgleichspannung fî›™r den betrachteten Stromkreis auf
250 V herabgesetzt werden, jedoch muss der Isolationswiderstand mindestens 1 MΩ betragen. (Auszug aus DIN VDE 0100-600).
Schleifenimpedanz-Messung bei Stromkreisen mit AFDD:
Wird eine Schleifenimpedanzmessung an einem Abgangsstromkreis mit AFDD durchgefî›™hrt, muss beachtet werden, dass der dadurch hervorgerufene Differenzstrom 300 mA nicht
überschreitet.
Der AFDD besitzt eine elektronische Differenzstrom- Messung die neben den Anforderungen der Produktnorm den Brandschutz zusätzlich erhöht.
AFDD Isolationsprî›™fung nach DIN VDE 61439:
Prfspannung wird an den Einspeiseklemmen der Niederspannungs- Schaltergerätekombination angelegt:
Bei Prfspannungen ≤ 400 V muss der AFDD ausgeschaltet sein (EN 61439-3).
Bei Prî›™fspannungen > 400 V muss der AFDD abgeklemmt werden (EN 61439-2).
* A person with appropriate technical training, knowledge and experience, as well as knowledge of the relevant standards, in order to identify and avoid risks which can arise from
electricity.
AFDD and E-Check:
Insulation test in circuits with AFDD:
Where it is not appropriate for practical reasons to disconnect electrical equipment for insulation testing, the measuring DC voltage can be reduced to 250 V for the respective
circuit, however the insulation resistance must be at least 1 MΩ. (Extract from DIN VDE 0100-600).
Loop impedance measurement in circuits with AFDD:
If a loop impedance measurement is carried out on an output circuit having an AFDD, then it must be ensured that the resulting differential current does not exceed 300 mA.
The AFDD has an electronic differential current measurement which also increases the re protection in addition to the requirements of the product standard.
AFDD insulation test according to DIN VDE 61439:
Test voltage applied on the supply terminals of the low-voltage switching device combination:
for test voltages ≤ 400 V, the AFDD must be switched off (EN 61439-3).
for test voltages > 400 V, the AFDD must be disconnected (EN 61439-2).
Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com OCOM 135509Hager 06.19 6LE007064Aa2
Es wird empfohlen bei der Inbetriebnahme die FI- und AFDD-Funktion
nacheinander durch entsprechendes Betätigen der Prüftaste zu überprüfen.
Die Versorgungsspannung muss dazu anliegen.
Wird die Prüftaste T länger als eine Sekunde gedrückt, muss die FI- und die
AFDD-Einheit den integrierten Leitungsschutzschalter auslösen, d.h. den
Stromkreis abschalten.
FI + AFDD-Function must be tested after installation, by pressing the test button.
The supply voltage must be present.
If test button T is pressed for longer than one second, the
RCD + AFDD must trigger, i.e. the circuit must switch off.


Product specificaties

Merk: Hager
Categorie: Schakelaar
Model: ARF975D
Breedte: 53.2 mm
Diepte: 70 mm
Hoogte: 83 mm
Certificering: EN 62606, EN 61009-1
Temperatuur bij opslag: -25 - 70 °C
Spanningclassificatie: 230 V
Nominale netspanning: 25 A
Aantal polen: 2
Type uitschakelcurve: Type C
Hoeveelheid modules (max): 3 module(s)
Totaal vermogensverlies: 7.95 W