PART No. 9378590069-04
AIR CONDITIONER
INSTALLATION MANUAL
INDOOR UNIT (Cassette type)
For authorized service personnel only.
EnglishFrançaisEspañolItalianoΕλληνικάPortuguêsРусскийTürkçe
INSTALLATIONSANLEITUNG
INNENGET (Kassettentyp)
Nur für autorisiertes Fachpersonal.
MANUEL D'INSTALLATION
MANUAL DE INSTALACIÓN
UNITÉ INTÉRIEURE (Type cassette)
Pour le personnel de service agrée uniquement.
UNIDAD INTERIOR (Tipo cassette)
Únicamente para personal de servicio autorizado.
MANUALE D'INSTALLAZIONE
UNITÀ INTERNA (Tipo a cassetta)
A uso esclusivo del personale tecnico autorizzato.
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ ( )Τύπος κασέτας
Μόνο για εξουσιοδοτημένο τεχνικό .προσωπικό
MANUAL DE INSTALAÇÃO
UNIDADE INTERNA (Tipo cassete)
Somente para o pessoal do serviço técnico autorizado.
РУКОВОДСТВО ПО УСТАНОВКЕ
ВНУТРЕННИЙ БЛОК (кассетного типа)
Только для .авторизованного обслуживающего персонала
KURULUM KILAVUZU
İ İÇ ÜN TE (Kaset tipi)
Yalnızca yetkili servis personeli için.
Deutsch
En-2
1. SAFETY PRECAUTIONS
• Be sure to read this manual thoroughly before installation.
• The warnings and precautions indicated in this manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this manual, together with the operating manual, to the customer. Request the
customer to keep them on hand for future use, such as for relocating or repairing the unit.
WARNING Indicates a potentially or imminently hazardous situation which,
if not avoided, could result in death or serious injury.
Installation of this product must be done by experienced service technicians or profes-
sional installers only in accordance with this manual. Installation by nonprofessional or
improper installation of the product may cause serious accidents such as injury, water
leakage, electric shock, or re. If the product is installed in disregard of the instructions
in this manual, it will void the manufacturer’s warranty.
Do not turn on the power until all work has been completed. Turning on the power before
the work is completed can cause serious accidents such as electric shock or re.
To avoid getting an electric shock, never touch the electrical components soon after the
power supply has been turned off. After turning off the power, always wait
10 minutes or more before you touch the electrical components.
If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant is
exposed to a direct ame it may produce a toxic gas.
Do not use this equipment with air or any other unspeci ed refrigerant in the refrigerant
lines. Excess pressure can cause a rupture.
Installation must be performed in accordance with regulations, codes, or standards for
electrical wiring and equipment in each country, region, or the installation place.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they do
not play with the appliance.
To avoid danger of suffocation, keep the plastic bag or thin lm used as the packaging
material away from young children.
CAUTION Indicates a potentially hazardous situation that may result in
minor or moderate injury or damage to property.
Read carefully all safety information written in this manual before you install or use the
air conditioner.
Install the product by following local codes and regulations in force at the place of instal-
lation, and the instructions provided by the manufacturer.
This unit must be installed by quali ed personnel with a capacity certi cate for handling
refrigerant uids. Refer to regulation and laws in use on installation place.
This product is part of a set constituting an air conditioner. The product must not be
installed alone or be installed with non-authorized device by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3 mm for this product.
To protect the persons, earth (ground) the product correctly, and use the power cable
combined with an Earth Leakage Circuit Breaker (ELCB).
The product is not explosion proof, and therefore should not be installed in explosive
atmosphere.
Do not touch the ns of the heat exchanger. Touching the heat exchanger ns could
result in damage to the ns or personal injury such as skin rupture.
This product contains no user-serviceable parts. Always consult experienced service
technicians for repairing.
When moving or relocating the air conditioner, consult experienced service technicians
for disconnection and reinstallation of the product.
Do not place any other electrical products or household belongings under the product.
Condensation dripping from the product might get them wet, and may cause damage or
malfunction of the property.
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the refrigera-
tion cycle. If air enters the refrigeration cycle, the pressure in the refrigeration cycle will
become abnormally high and cause the piping to rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit.
If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and thor-
oughly ventilate the area. If the refrigerant comes in contact with a ame, it produces a
toxic gas.
2.2. Special tool for R410A
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materi-
als that have been manufactured speci cally for R410A use. Because the pressure of
R410A refrigerant is approximately 1.6 times higher than the R22, failure to use dedi-
cated piping material or improper installation can cause rupture or injury. Furthermore, it
can cause serious accidents such as water leakage, electric shock, or re.
Tool name Changes
Gauge manifold
The pressure in the refrigerant system is extremely
high and cannot be measured with a conventional
gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed. It
is recommended to use a gauge manifold with a high
pressure display range of –0.1 to 5.3 MPa and a low
pressure display range of –0.1 to 3.8 MPa.
Charging hose
To increase pressure resistance, the hose material
and base size were changed.
(The charging port thread diameter for R410A is
1/2-20 UNF.)
Vacuum pump
A conventional vacuum pump can be used by install-
ing a vacuum pump adapter.
Be sure that the pump oil does not back ow into
the system. Use one capable for vacuum suction of
–100.7 kPa (5 Torr, –755 mmHg).
Gas leakage detector Special gas leakage detector for R410A refrigerant.
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other
prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall,
water leakage, electric shock, or re.
• The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
INSTALLATION MANUAL
PART No. 9378590069-04
INDOOR UNIT (Cassette type)
Contents
1. SAFETY PRECAUTIONS ......................................................................................... 2
2. ABOUT THIS PRODUCT .......................................................................................... 2
2.1. Precautions for using R410A refrigerant ........................................................... 2
2.2. Special tool for R410A ...................................................................................... 2
2.3. Accessories .......................................................................................................2
2.4. Optional parts....................................................................................................3
3. INSTALLATION WORK ............................................................................................. 3
3.1. Selecting an installation location .......................................................................3
3.2. Installation dimension .......................................................................................3
3.3. Installation the unit ............................................................................................ 4
4. PIPE INSTALLATION ................................................................................................ 5
4.1. Selecting the pipe material................................................................................5
4.2. Pipe requirement............................................................................................... 5
4.3. Flare connection (pipe connection) ...................................................................5
4.4. Installing heat insulation.................................................................................... 6
5. INSTALLING DRAIN PIPES .....................................................................................6
6. ELECTRICAL WIRING ..............................................................................................7
6.1. Wiring system diagram ..................................................................................... 7
6.2. Connection cable preparation ...........................................................................8
6.3. Connection of wiring ......................................................................................... 8
7. REMOTE CONTROLLER SETTING ........................................................................8
7.1. Installing the remote controller .......................................................................... 8
7.2. Setting the dip switches ....................................................................................9
8. CASSETTE GRILLE INSTALLATION ....................................................................... 9
9. FUNCTION SETTING ............................................................................................... 9
9.1. Turning on the power ........................................................................................ 9
9.2. Function setting...............................................................................................10
10. SPECIAL INSTALLATION METHODS .................................................................... 12
10.1. Group control system .................................................................................... 12
10.2. Dual remote controllers ................................................................................. 12
11. TEST RUN ..............................................................................................................12
12. CHECK LIST ...........................................................................................................13
13. OPTIONAL KIT INSTALLATION (OPTION) ............................................................13
14. CUSTOMER GUIDANCE .......................................................................................13
15. ERROR CODES .....................................................................................................13
[Original instructions]
En-3
Name and Shape Q’ty Description
Operating manual
1
Installation manual
1
(This book)
Template
(Carton top) 1
For installing indoor unit
Washer
8
For installing indoor unit
Coupler heat insulation (large)
1
For indoor side pipe joint (Gas pipe)
Coupler heat insulation (small)
1
For indoor side pipe joint
(Liquid pipe)
Insulation
1
For installing drain pipe
Drain hose
1
For installing drain pipe
VP25 (O.D.32, I.D.25)
Hose band
1
For installing drain hose
Drain hose heat insulation
1
For installing drain pipe
Cable tie (large)
3
For electrical wiring
Cable tie (small)
1
For electrical wiring
(Wired remote controller)
Wired remote controller
1
For air conditioner operation
Remote controller cable
1
For connecting the remote controller
Screw (M4 × 16)
2
For installing the remote controller
2.4. Optional parts
Parts name Model No. Summary
IR receiver unit UTY-LRH*A2 For air conditioner opera-
tion
Wired remote controller UTY-RNN*M For air conditioner opera-
tion
Air outlet shutter plate UTR-YDZC
Install the plate at outlet
when carrying out 3-way
direction operation
Insulation kit for high
humidity UTZ-KXRA
UTZ-KXGA
Install when the condition
under the roof is over 80%
in humidity and over 30°C
in temperature.
External connect kit UTY-XWZX For control input/output port
Fresh air intake kit UTZ-VXGA To take fresh air
Wide panel UTG-AGYA-W
Wide panel hides the gap
between the ceiling hole
and the Cassette grille.
Panel spacer UTG-BGYA-W
Installation in a space of
56 mm or greater is possible
by using panel spacer when
the height behind the ceiling
is low.
Wired remote controller is recommended using simultaneous twin or triple connection.
3. INSTALLATION WORK
Especially, the installation place is very important for the split type air conditioner because
it is very dif cult to move from place to place after the rst installation.
3.1. Selecting an installation location
Decide the mounting position together with the customer as follows.
WARNING
Select installation locations that can properly support the weight of the indoor unit.
Install the units securely so that they do not topple or fall.
CAUTION
Do not install the indoor unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts,
causing the parts to fail or the unit to leak water.
Area lled with mineral oil or containing a large amount of splashed oil or steam, such
as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak
water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon bers or
ammable dust, or volatile in ammables such as paint thinner or gasoline. If gas leaks
and settles around the unit, it can cause a re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or ammable gas.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote
control cable at least 1 m away from a television or radio receivers. The purpose of this
is to prevent TV reception interference or radio noise. (Even if they are installed more
than 1 m apart, you could still receive noise under some signal conditions.)
If children may approach the unit, take preventive measures so that they cannot reach
the unit.
Use the “Insulation kit for high humidity” (option), when the condition under the roof
is over 80% in humidity and over 30°C in temperature. Otherwise, there is a risk of
condensation on the ceiling.
(1) Install the indoor unit in a location having suf cient strength to support the weight of
the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Locate where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibration is not ampli ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the lter can be removed.
3.2. Installation dimension
• The ceiling rear height as shown in the gure.
Strong and durable ceiling
3 or more
Floor
Obstruction
Unit: m
1.5 or
more
1.8 or more
1 or more
• This product can be installed at a height of up to 4.2 m (30 model: 3.6 m). However, if
the heights of the ceiling is higher than 3.2 m or lower than 2.7 m, it is necessary to set
the position from remote controller. (See 9.2. Function setting)


Product specificaties

Merk: Fujitsu
Categorie: Airco
Model: AUYG45LRLA
Kleur van het product: Wit
Soort: Binneneenheid airconditioning
Stroom: 25 A
Koelend medium: R410A
Inverter technologie: Ja
Multi-split: Ja
Air conditioner functies: Cooling, Heating
Seizoensgebonden rendement (koeling) (SEER): 6.63
Seasonal efficiency rating (verwarming) (SCOP) (gemiddeld stookseizoen): 4.1
Energie-efficiëntieklasse (verwarming) (gemiddelde stookseizoen): A+
Jaarlijks energieverbruik (koelen): - kWu
Jaarlijks energieverbruik (verwarming) (warmer stookseizoen): - kWu
Jaarlijks energieverbruik (verwarming) (gemiddelde stookseizoen): - kWu
Energie-efficiëntieklasse (koeling): A++
Extern geluidsniveau: - dB
Intern geluidsniveau (hoge snelheid): - dB
Op afstand bedienbaar: Ja
Koelcapaciteit in watt (opgegeven): 12500 W
Verwarmingscapaciteit in watt (opgegeven) (warmer stookseizoen): - W
Verwarmingscapaciteit in watt (opgegeven) (gemiddelde stookseizoen): 14000 W
Verwarmingscapaciteit in watt (opgegeven) (kouder stookseizoen): - W
Energieverbruik per uur (koeling): - kWu
Energieverbruik per uur (verwarming): - kWu
Breedte binnenunit: 840 mm
Diepte binnenunit: 840 mm
Hoogte binnenunit: 288 mm
Koel capaciteit in watt (max): 14000 W
Verwarmingscapaciteit in watt (max): 16200 W
Koeling energie efficientie: 3.22
Verwarming energie efficientie: 3.71
Indoor unit type: Cassette
Indoor eenheid gewicht: 26000 g
Jaarlijks energieverbruik (verwarming) (kouder stookseizoen): - kWu
Ontwerpbelasting (koeling): 12.5 kW
Ontwerpbelasting (verwarming) (warmer stookseizoen): - kW
Ontwerpbelasting (verwarming) (gemiddelde stookseizoen): 9.2 kW
Ontwerpbelasting (verwarming) (kouder verwarmingsseizoen): - kW
Indoor units hoeveelheid: 1
Wifi: Nee
AC-ingangsspanning: 230 V
AC-ingangsfrequentie: 50 Hz
Koelkast medium gewicht: 3350 g
Koelcapaciteit in watt (min): 4000 W
Verwarmingscapaciteit in watt (min): 4200 W
Verkoelende luchtstroom (indoor eenheid): 1900 m³/uur
Stroomsterkte (koeling): 20.5 A
Stroomsterkte (verwarming): 20.5 A