Fujitsu ARYG30LMLE Handleiding

Fujitsu Airco ARYG30LMLE

Lees hieronder de 📖 handleiding in het Nederlandse voor Fujitsu ARYG30LMLE (17 pagina's) in de categorie Airco. Deze handleiding was nuttig voor 13 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/17
EnglishDeutschFrançaisEspañolItalianoE vIkλλη άPortuguês
Русский
Turkiçe
INSTALLATION MANUAL
For authorized service personnel only.
INSTALLATIONSANLEITUNG
Nur für autorisiertes Personal.
MANUEL D'INSTALLATION
Pour le personnel agréé uniquement.
MANUAL DE INSTALACIÓN
Solo para personal autorizado.
MANUALE D'INSTALLAZIONE
Ad uso esclusivo del personale autorizzato.
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
Για εξουσιοδοτημένο προσωπικό σέρβις.
MANUAL DE INSTALAÇÃO
Apenas para técnicos autorizados.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для уполномоченного персонала .
KURULUM KILAVUZU
Yetkili servis personeli içindir.
PART NO. 9379127035-02
AIR CONDITIONER
En-1
CAUTION
Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by qualified personnel with a capacity certificate for handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
Th
e installation must be carried out in compliance with regulations in force
in the place
of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or
with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3mm for this unit.
The unit must be correctly grounded and the supply line must be equipped with a
differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Never touch electrical components immediately after the power supply has been turned
off. Electric shock may occur. After turning off the power, always wait 5 minutes before
touching electrical components.
This unit contains no user-serviceable parts. Always consult authorized service
personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation of
the unit.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they do
not play with the appliance.
2. ABOUT THE UNIT
2.1. Precautions for using the R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the
refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become
abnormally high and cause the piping to rupture.
If there is a refrigerant leakage, make sure that it does not exceed the concentration
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leakage occurs during operation, immediately vacate the premises and
thoroughly ventilate the area.
If the refrigerant comes in contact with a ame, it produces a toxic gas.
2.2. Special tool for R410A
WARNING
To install a unit that uses the R410A refrigerant, use dedicated tools and piping
materials that have been manufactured speci cally for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than
the R22, failure to use dedicated piping material or improper installation can cause
rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or
re.
Tool name Contents of change
Gauge manifold
Pressure is huge and cannot be measured with a conventional
gauge. To prevent erroneous mixing of other refrigerants, the
diameter of each port has been changed.
It is recommended to use a gauge manifold with a high pressure
display range –0.1 to 5.3 MPa and a low pressure display range
–0.1 to 3.8 MPa.
Charging hose To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump A conventional vacuum pump can be used by installing a
vacuum pump adapter.
Gas leakage
detector Special gas leakage detector for HFC refrigerant R410A.
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the Operating Manual to the customer.
Request the customer to keep them on hand for future use, such as for relocating or
repairing the unit.
WARNING
This mark indicates procedures which, if improperly performed,
might lead to the death or serious injury of the user.
CAUTION
This mark indicates procedures which, if improperly performed,
might possibly result in personal harm to the user, or damage to
property.
WARNING
Request your dealer or a professional installer to install the indoor unit in accordance
with this Installation Manual. An improperly installed unit can cause serious accidents
such as water leakage, electric shock, or re. If the indoor unit is installed in disregard
of the instructions in the Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning ON the power
before the work is completed can cause serious accidents such as electric shock or re
.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a ame, it produces a toxic gas.
Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units
during operation. It will cause compressor failure as well as water leakage.
First, stop the indoor unit by operating the control unit, converter or external input
device and then cut the breaker.
Make sure to operate through the control unit, converter or external input device.
When the breaker is designed, locate it at a place where the users cannot start and
stop in the daily work.
Contents
1. SAFETY PRECAUTIONS ..........................................................................................1
2. ABOUT THE UNIT .....................................................................................................1
2.1. Precautions for using the R410A refrigerant .......................................................1
2.2. Special tool for R410A ........................................................................................1
2.3. Accessories ........................................................................................................2
2.4. Optional parts .....................................................................................................2
3. INSTALLATION WORK .............................................................................................2
3.1. Selecting an installation location ........................................................................2
3.2. Installation dimension .........................................................................................3
3.3. Installation the unit ..............................................................................................3
4. PIPE INSTALLATION ................................................................................................4
4.1. Selecting the pipe material .................................................................................4
4.2. Pipe requirement ................................................................................................5
4.3. Flare connection (Pipe connection) ....................................................................5
4.4. Installing heat insulation .....................................................................................6
5. INSTALLING DRAIN HOSE .......................................................................................6
6. ELECTRICAL WIRING ..............................................................................................7
6.1. Wiring system diagram .......................................................................................7
6.2. Connection cable preparation .............................................................................8
6.3. Connection of wiring ...........................................................................................8
7. REMOTE CONTROLLER SETTING .........................................................................9
7.1. Installing the remote controller ...........................................................................9
7.2. Setting the DIP switches .....................................................................................9
8. FUNCTION SETTING..............................................................................................10
8.1. Turning on the power ........................................................................................10
8.2. Function setting ................................................................................................10
8.3. Static pressure characteristic ...........................................................................12
8.4. Special installation methods .............................................................................12
9. FRESH AIR INTAKE ................................................................................................13
10. TEST RUN ...............................................................................................................14
11. CHECK LIST ............................................................................................................14
12. OPTIONAL KIT INSTALLATION (OPTION) .............................................................14
13. CUSTOMER GUIDANCE ........................................................................................15
14. ERROR CODES ......................................................................................................15
INSTALLATION MANUAL
PART NO. 9379127035
INDOOR UNIT (Duct Type)
En-2
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall,
water leakage, electric shock, or re.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Do not discard any accessories needed for installation until the installation work has
been completed.
Name and Shape Q’ty Description
Operating manual
1
Installation manual
1
(This book)
Hanger
4
For suspending the indoor unit
from ceiling
Drain hose insulation
1
Insulates the drain hose and
vinyl hose
Cable tie (large)
1
For xing the drain hose
Cable tie (small)
1
For remote controller and re-
mote controller cable binding
Cable tie
2
For electrical wiring
(22,24 model)
Wire clamper 1
For electrical wiring
(22,24 model)
Remote controller
1
For air conditioner operation
Remote controller cable
(*1)
1
For connecting the remote
controller
Screw (M4 × 16)
2
For installing the remote
controller
Coupler heat
insulation (large) 1
For indoor side pipe joint (gas)
Coupler heat
insulation (small) 1
For indoor side pipe joint
(liquid)
Special nut A
(large ange)
4
For suspending the indoor unit
from ceiling
Special nut B
(small ange)
4
For suspending the indoor unit
from ceiling
(*1) Not supplied for ART series
2.4. Optional parts
Parts name Model No. Application
Wired remote controller UTY-RNN*M For air conditioner operation
Wired remote controller UTY-RVN*M For air conditioner operation
Simple remote controller UTY-RSN*M For air conditioner operation
Remote sensor unit UTY-XSZX Room temperature sensor
External connect kit UTD-ECS5A For control input/output port
Square ange UTD-SF045T
Round ange UTD-RF204
Long-life lter UTD-LF25NA
Drain pump unit
UTZ-PX1NBA
3. INSTALLATION WORK
3.1. Selecting an installation location
Especially, the installation place is very important for the split type air conditioner be-
cause it is very dif cult to move from place to place after the rst installation.
WARNING
Select installation locations that can properly support the weight of the indoor. Install
the units securely so that they do not topple or fall.
CAUTION
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
Area lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
Area that generates substances that adversely affect the equipment, such as
sulfuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
Area that can cause combustible gas to leak, contains suspended carbon bers or
ammable dust, or volatile in ammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or ammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote
controller cable at least 1 m away from a television or radio receivers. The purpose of
this is to prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under
some signal conditions.)
Take precautions to prevent the unit from falling.
Decide the mounting position with the customer as follows:
(1) Install the indoor unit in a location having suf cient strength to support the weight of
the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.


Product specificaties

Merk: Fujitsu
Categorie: Airco
Model: ARYG30LMLE
Kleur van het product: Grijs
Soort: Binneneenheid airconditioning
Stroom: 20 A
Koelend medium: R410A
Inverter technologie: Ja
Multi-split: Ja
Air conditioner functies: Cooling, Dehumidifying, Heating
Seizoensgebonden rendement (koeling) (SEER): 5.9
Seasonal efficiency rating (verwarming) (SCOP): 3.9
Energie-efficiëntieklasse (verwarming) (gemiddelde stookseizoen): A
Jaarlijks energieverbruik (koelen): 504 kWu
Jaarlijks energieverbruik (verwarming) (warmer stookseizoen): - kWu
Jaarlijks energieverbruik (verwarming) (gemiddelde stookseizoen): 2868 kWu
Energie-efficiëntieklasse (koeling): A+
Extern geluidsniveau: - dB
Intern geluidsniveau (hoge snelheid): 39 dB
Op afstand bedienbaar: Ja
Koelcapaciteit in watt (opgegeven): 8500 W
Verwarmingscapaciteit in watt (opgegeven) (gemiddelde stookseizoen): 10000 W
Verwarmingscapaciteit in watt (opgegeven) (kouder stookseizoen): - W
Energieverbruik per uur (koeling): - kWu
Energieverbruik per uur (verwarming): - kWu
Breedte binnenunit: 1135 mm
Diepte binnenunit: 700 mm
Hoogte binnenunit: 270 mm
Koel capaciteit in watt (max): 10000 W
Verwarmingscapaciteit in watt (max): 11200 W
Koeling energie efficientie: 3.21
Verwarming energie efficientie: 3.73
Indoor unit type: Luchtafvoer
Indoor eenheid gewicht: 40000 g
Jaarlijks energieverbruik (verwarming) (kouder stookseizoen): - kWu
Ontwerpbelasting (koeling): 8.5 kW
Ontwerpbelasting (verwarming) (warmer stookseizoen): - kW
Ontwerpbelasting (verwarming) (gemiddelde stookseizoen): 10 kW
Ontwerpbelasting (verwarming) (kouder verwarmingsseizoen): - kW
Indoor units hoeveelheid: 1
Wifi: Nee
AC-ingangsspanning: 230 V
AC-ingangsfrequentie: 50 Hz
Koelkast medium gewicht: 2100 g
Koelcapaciteit in watt (min): 2800 W
Verwarmingscapaciteit in watt (min): 2700 W
Verkoelende luchtstroom (indoor eenheid): 1900 m³/uur
Binnenunit geluidsniveau (lage snelheid): 26 dB
Binnenunit geluidsvermogensniveau: 65 dB
Stroomsterkte (koeling): 17 A
Stroomsterkte (verwarming): 17 A

Heb je hulp nodig?

Als je hulp nodig hebt met Fujitsu ARYG30LMLE stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Airco Fujitsu

Handleiding Airco

Nieuwste handleidingen voor Airco