Festo SPAU Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Festo SPAU (6 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 4 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/6
Translation of the original instructions
1 About this document
The operating instructions describe the entire function range. The function range
is limited, depending on the product variant. You can find detailed specifications
for the product, the device description file (IODD) with a description of the IO-
Link®. parameters and the declaration of conformity www.festo.com.è
1.1 Applicable documents
All available documents for the product www.festo.com/pk.è
2 Safety
2.1 General safety instructions
– The product may only be used in its original status without unauthorised
modifications.
– Only use the product if it is in perfect technical condition.
– Take into consideration the ambient conditions at the location of use.
– Operate the product only with compressed air of the specified air quality class
è13 Technical data
– Observe the specifications on the product labelling.
– Work on the product should only be conducted by qualified personnel.
2.2 Intended use
The pressure sensor SPAU is intended for monitoring pressure of compressed air
and inert gases in the piping.
2.3 Area of application and approval
In combination with the UL inspection mark on the product, the information in this
section must also be observed in order to comply with the certification conditions
of Underwriters Laboratories Inc. (UL) for USA and Canada.
UL approval information
Product category code QUYX, QUYX7
File number E322346
Considered standards UL 61010-1
CAN/CSA C22.2 No. 61010-1
UL mark
Tab. 1
Only for connection to a NEC/CEC Class 2 supply.
Raccorder Uniquement a un circuit de NEC/CEC Classe 2.
WARNING!
The unit shall be supplied by a power source which fulfils the requirements on a
limited-energy circuit in accordance to IEC/EN/UL/CSA 61010-1 or on a Limited
Power Source (LPS) in accordance to IEC/EN/UL/CSA 60950-1 or IEC/EN/UL/CSA
62368-1 or a Class 2 circuit in accordance to NEC or CEC.
3 Service
– Contact the regional Festo contact if you have technical problems.
èwww.festo.com.
4 Accessories
– Accessories www.festo.com/catalogue.è
5 Product overview
1Display
2Pneumatic connection
3B pushbutton
4Electrical connection
5Edit button
6A pushbutton
Fig. 1 Display variant without front panel mounting. Representation of other vari-
ants can deviate from this.
6 Function
The sensor converts pneumatic pressure values (relative pressure) into electrical
signals, which can be used for control or regulating functions. Measurements are
carried out using a piezoresistive sensor element with a following electronic eval-
uation unit. Connection to the higher-level system is provided by 1 or 2 switching
outputs, an analogue output and/or an IO-Link interface. The switching outputs
can be configured for monitoring of a threshold value, a pressure range or a differ-
ential pressure. For each output, PNP or NPN and normally open (NO) or normally
closed (NC) can optionally be set. Through the IO-Link® interface, process values
can be read out and parameters changed and transmitted to additional devices.
6.1 Operating statuses
Operating status Function
RUN mode – Basic status after the operating voltage is
switched on
– Display of the current measured value
SHOW mode – Display of the current settings
– Display and resetting of the minimum and
maximum values
EDIT mode Setting or modification of parameters
TEACH mode Acceptance of the current measured value to
determine switching points
Tab. 2
6.2 Switching functions
6.2.1 Threshold value comparator for monitoring of a pressure threshold _|¯
Function NO (normally open) NC (normally closed)
Switching function:
– 1 switching point (SP)
TEACH mode:
– 2 teach points (TP1, TP2)
– SP = ½ (TP1+TP2)
TP1 TP2
HY
1
0
Out
p
SP
TP1 TP2
SP
HY
1
0
Out
p
Tab. 3
6.2.2 Window comparator for monitoring of a pressure range _|¯|_
Function NO (normally open) NC (normally closed)
Switching function:
– 2 switching points (SP.Lo,
SP.Hi)
TEACH mode1):
– 2 teach points (TP1, TP2)
– TP1 = SP.Lo, TP2 = SP.Hi
HY HY
TP1=SP.Lo TP2=SP.Hi
1
0
Out
p
HY HY
TP1=SP.Lo TP2=SP.Hi
1
0
Out
p
1) SP.Lo = smaller pressure/vacuum value, SP.Hi = larger pressure/vacuum value, dependent on the Teach
sequence
Tab. 4
6.2.3 Auto difference monitoring d_|¯|_
This function permits monitoring of a pressure value for constancy. The applied
pressure is constant in the range between [SP.Lo] and [SP.Hi], so the reference
8111089
SPAU
Pressure sensor
8111089
2019-04b
[8111091]
Instructions|Operating
Festo & Co. KGSE
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
pressure P
Ref
is automatically determined. The result is a switching operation at
the output. The signal change signals the start of pressure monitoring. If the pres-
sure remains in the monitoring range [d.SP] around PRef, the pressure is stable.
When the monitoring range is left (e.g. caused by a leakage in the system), the
output switches back.
1Reference value is determined
2Measured value deviates by
[d.SP] from the reference value
3Monitoring range
Fig. 2
The parameters [SP.Lo], [SP.Hi], [t.obS] and [d.SP] can be configured by the user.
The greater [t.obS] is set, the more constant the pressure signal must be to estab-
lish the reference value PRef.
Function NO (normally open) NC (normally closed)
Switching function:
– 2 switching points (SP.Lo,
SP.Hi) for setting the valid
work range
– 1 switching point (d.SP)
for determination of the
monitoring area
TEACH mode1):
– 2 teach points (TP1, TP2)
– TP1 = SP.Lo, TP2 = SP.Hi
SP.Lo PRef
SP.Hi
d.SP
1
0
Out
p
1
SP.Lo PRef
SP.Hi
d.SP
0
Out
p
1) SP.Lo = smaller pressure value, SP.Hi = larger pressure value, independent of the Teach sequence
Tab. 5
7 Installation
7.1 Mechanical and pneumatic
NOTICE!
An unfavourable mounting position can impair the function of the product.
• Mount the sensor so that no condensation from the compressed air lines can
gather in the device.
• Install the sensor so that it cannot be heated above the maximum permissible
operating temperature (plan for convection possibilities).
Installation
SPAU-...-T
– Seal connecting thread.
Tightening torque: max. 10Nm
(tightening torque M5 female thread: max. 2 Nm)
Tightening torque: max. 7Nm
SPAU-...-H SPAU-...-A
Screws: M3
Tightening torque: max. 0.5Nm
Mounting bracket hole pattern Fig.3è
Installation
SPAU-...-W
1.
Wall mounting hole pattern Fig.3è
2.
SPAU-...-F
34 ±
0,3
61 ±0,3
Front panel cut-out in mm – Guide sensor from the front into the cut-out
on the front panel.
– Attach the clamping plate and press until
the fastening slide clips in.
Screws: M3
Tightening torque: max. 0.7Nm
s < 2 mm: remove 1 washer<
s < 1 mm: remove 2 washers<
SPAU-...-MS...
1. 2.
Tightening torque: max. 1Nm
Tab. 6
7.1.1 Hole patterns
Fig. 3 Left wall mounting, right mounting bracket
7.2 Electric
WARNING!
Risk of injury due to electric shock.
• For the electric power supply, use only PELV circuits that ensure a reliable
electric disconnection from the mains network.
• Observe IEC60204-1/EN60204-1.
Long signal lines reduce the immunity to interference.
• Adhere to the maximum permissible cable length of 30 m (20 m for IO-Link).
Maximum tightening torque of plug connector: M8 = 0.3Nm, M12 = 0.5Nm
Connection -M8 Connection -M12 Pin Function Core colour
1 Operating voltage
+24 V DC
Brown (BN)
2 Switching output OutB
or analogue output
OutD
White (WH)
3 0 V DC Blue (BU)
4 Switching output OutA
IO-Link (C/Q line)
Black (BK)
Tab. 7
Circuit diagrams
SPAU-...-L-... with display SPAU-...-LK-V-.../SPAU-…-
LK-B-… without display,
analogue voltage output
on pin 2
SPAU-…-LK-A-… without
display, analogue current
output on pin 2
Usable output according to factory setting
Tab. 8
8 Commissioning
8.1 LCD display
1Output display
2Main display (e.g. measurement
value)
3Bar graph for analogue output
(only visible for scaled analogue
output)
4Lower display (e.g. unit)
5Status information
6Input display
7Bar graph for input signal
Fig. 4
Example for LCD display Meaning
Output display
 [OutA] Switching output OutA selected
[OutA]
Switching output OutA set
[OutB] Switching output OutB selected
[OutB]
Switching output OutB set
[OutD] Analogue output OutD selected
Information / input display
[InA]
Input signal InA: graphic display of the current measured value
related to the maximum measured value of the measuring range
Analogue output OutD with activated scaling
Example for LCD display Meaning
[Lock] Security code activated
[Spec] Special menu activated
Tab. 9
Example for LCD display
Main display Lower display Meaning
Measured value indicator and unit in the RUN mode
[– 0.53] [bar] Measured value indicator (here: negative value) and unit
Menu for the switching outputs (OutA and OutB)
[Edit] [bin] Edit menu for the switching outputs (binary)
_|¯ [Fctn] Threshold value comparator
d_|¯|_ [Fctn] Auto difference monitoring
_|¯|_ [Fctn] Window comparator
[1.80] [SP] Switching point value
[2.45] [SP.Lo] Value of lower switching point
[6.45] [SP.Hi] Value of upper switching point
[0.50] [HY] Hysteresis value
[18] [t.obS] / [MSEC] Time interval for determination of a mean value, which is
used to determine the pressure change and establish the
reference value.
[0.25] [d.SP] Threshold value of the differential pressure with auto dif-
ference monitoring
[NO] [logic] Switching characteristics: [NO] = normally open contact,
[NC] = normally closed contact
[bLUE] [COLR] Display colour:
[bLUE] = blue, colour change function is deactivated
[R.ON] = red when switching output set
[R.OFF] = red when the switching output is not set
Note: Independent of the settings [COLR], the red colour
change appears with some malfunctions.
Extreme values (only SHOW mode)
[1.64] [MIN] Minimum measured pressure since switch-on or the last
reset
[8.50] [MAX] Maximum measured pressure since switch-on or the last
reset
Menu for the analogue output (OutD)
[Edit] [ANLG] Edit menu for the analogue output
[1 _ 5] [Out] / [V] Output function of the analogue output
[93] [In.Hi] / [%] Scaling of the analogue output in percent of the final value
of the pressure measuring range
[3] [In.Lo] / [%] Scaling of the analogue output in percent of the initial
value of the pressure measuring range
Menu for device settings (Spec)
[Edit] [MENU] Edit menu for additional settings
[16] [Filt] / [MSEC] Value of the filter time constant for the pressure measure-
ment signal
[bar] [Unit] Unit for the pressure indicator
[OFF] [Z.AdJ] [OFF] = zero point synchronisation (zero adjust) deactiv-
ated
[ON] = offset correction for measured value indicator,
switching points and analogue output possible
[Unit] [Sub.d] Settings of the lower display in RUN mode: selected unit or
switching point of OutA or bar graph
[40] [Eco] / [SEC] Economy mode: period after which the display background
lighting is switched off
[PNP] [bin] / [Out] Shift of the switching outputs (binary) between PNP and
NPN
[bin] [Pin2] / [Out] Shift between switching output (binary) and analogue out-
put (lnA) at Pin 2
[OFF] [Code] Activation and determination of the security code (lock)
[OFF] [MASt] Activation of the IO-Link® master function for replication of
parameters
Tab. 10
For device variants without LCD display:
• LED illuminated green: normal operation
• LED illuminated or flashes red: malfunction
8.2 Switch on sensor (RUN mode)
• Switch on the operating voltage.
ÄCurrent measured value is displayed. The sensor is in the basic status
(RUN mode).
The basic status can be reached from other modes by:
– Pressing Edit button for 3 seconds
– Expiration of a monitoring time (timeout)
8.3 Displaying parameters (SHOW mode)
Requirement: The sensor is ready for operation (RUN mode).


Product specificaties

Merk: Festo
Categorie: Niet gecategoriseerd
Model: SPAU

Heb je hulp nodig?

Als je hulp nodig hebt met Festo SPAU stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Festo

Festo

Festo VPPI Handleiding

21 November 2024
Festo

Festo SFAB Handleiding

21 November 2024
Festo

Festo SFAH Handleiding

21 November 2024
Festo

Festo DRRD-12 Handleiding

21 November 2024
Festo

Festo SDE3 Handleiding

21 November 2024
Festo

Festo SFTE Handleiding

21 November 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd