TEMPRA 24
copper wall-mounted system,
gas fi red boiler for central heating,
fan assisted, room sealed compartment,
electronic fl ame ignition and control
INSTALLATION, SERVICE AND USER INSTRUCTIONS
cod. 3543805/3 - 10/2004
G C N° 41-267-13
2
Tempra 24
CE MARK
CE mark documents that the Ferroli gas appliances comply with the requirement contained in European
directives applicable to them.
In particular, the appliances comply with the following CEE directives and the technical specifications
provided from them:
Gas appliances directive 90/396
Efficiencies directive 92/42
Low tension directive 73/23 (modified from the 93/68)
Electromagnetic compatibility directive 89/396 (modified from the 93/68)
IMPORTANT
Your "benchmark" Installation, Commissioning and Service Record Log Book will be enclosed in
your customer information pack.
"This record must be completed and left with the end user"
"All CORGI Registered Installers carry a CORGI ID card and have a registration number. Both
should be recorded in your central heating log book. You can check with the CORGI register by
calling CORGI on 01256 372300".
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark
has been introduced to improve the standards of installation and commissioning of central heating
systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety
and efficiency. Please see installation and servicing guidelines.
INDEX
1. DESCRIPTION....................................................................................................................................................... 3
2. TECHNICAL AND DIMENSIONAL CHARACTERISTICS...................................................................................... 4
3. INSTALLATION DETAILS ..................................................................................................................................... 9
4. COMMISSIONING AND TESTING..................................................................................................................... 28
5. ADJUSTMENT AND GAS CONVERSION .......................................................................................................... 29
6. MAINTENANCE AND CLEANING .................................................................................................................... 31
7. REPLACEMENT OF PARTS ................................................................................................................................ 33
8. FAULT FINDING................................................................................................................................................. 37
9. ELECTRICAL AND FUNCTIONAL SCHEME ...................................................................................................... 39
10. USER INSTRUCTIONS ...................................................................................................................................... 41
3
Tempra 24
1. DESCRIPTION
1.01 Introduction
The Tempra 24 is defined as a “room sealedboiler, all air required for combustion is taken from outside the
room in which it is installed. It is a new high performance gas fired heat generator for central heating. A special
feature of this boiler is its built-in electronic flame ignition and control unit making burner operation completely
automatic and safe. The main components are as follows:
Copper heat exchanger consisting of four finned tubes specifically shaped for high efficiency.
Ceramic fibre insulated combustion chamber
12 stainless steel bladed burners specifically designed for this boiler.
Fan for discharge of combustion products and intake of combustion air.
Differential air pressure switch. For safety reasons, this ensures the burner ignites only when the fan
is functioning correctly.
Hermetically sealed compartment made from corrosion-resistant steel enclosing the above components.
Combination gas safety valve with modulator, complete with pressure stabiliser.
Pressure relief valve for the central heating circuit set to open at 3 bar.
Built-in Expansion vessel.
Variable speed pump.
Central heating flow temperature adjustment thermostat.
Central heating limit thermostat.
Overheat safety thermostat.
Electronic control unit for automatic flame ignition and control.
Central heating flow temperature sensor.
1.02 Instructions and regulations
Assembly, installation, first start up and maintenance must be carried out by competent persons only, in accordance
with all current technical regulations and directives.
c.o.s.h.h.
Materials used in the manufacture of this appliance are non hazardous and no special precautions are
required when servicing.
3Related Documents
Related documents
This appliance must be installed strictly in accordance with these instructions.
The Gas Safety Regulations (Installations & Use).
The Local Building Regulations.
The Building Regulations.
The Buildings Standards (Scotland - Consolidated) Regulations.
British Standards Codes of Practice:
B.S. 7593 TREATMENT OF WATER IN DOMESTIC HOT WATER CENTRAL HEATING SYSTEMS
B.S. 5546 INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
B.S. 5440 Part 1 FLUES
B.S. 5440 Part 2 AIR SUPPLY
B.S. 5449 FORCED CIRCULATION HOT WATER SYSTEMS
B.S. 6798 INSTALLATION OF GAS FIRED HOT WATER BOILERS
B.S. 6891 GAS INSTALLATIONS
B.S. 7671 IEE WIRING REGULATIONS
B.S. 4814 SPECIFICATION FOR EXPANSION VESSELS
B.S. 5482 INSTALLATION OF LPG
Model Water Bye Laws
For Northern Ireland the rules in force apply


Product specificaties

Merk: Ferroli
Categorie: CV-ketels
Model: Tempra 24

Heb je hulp nodig?

Als je hulp nodig hebt met Ferroli Tempra 24 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden