2.2 Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Active power 1% of range maximum
Reactive power 1% of range maximum
Apparent power 1% of range maximum
Active energy Class 1 IEC62053-21
Class B EN50470-3 (MI D product only)
Reactive energy 1% of range maximum
2.3 Environment
Operating temperature ℃ ℃ -25 to +55
Storage and transportation temperature -40 to +70 ℃ ℃
Reference temperature 23 2 ℃ Β± ℃
Relative humidity 0 to 95%, non-condensing
Altitude up to 2000m
Warm up time 3s
Mechanical environment M1
Electromagnetic environment E2
Degree of pollution 2
2.4 Mechanics
Din rail dimensions 18x119x62 (WxHxD) DIN 43880
Mounting D IN rail 35mm
Sealing IP51 (indoor)
Material self-extinguishingU L94V-0
3 Display
1
2
Initialization Display
When it is powered on, the meter will initialize and do self-checking.
After the self-checking program, the meter screen will display the total active
energy (kWh)
* Note: For the M ID version of SD M120CTM, S DM 120CT MB and S DM120CT P, the
CT ratio can be set only once. Before you set the CT ratio, please check the ratio
of the CT connected to the meter. For example, if the CT is 100/5A, please set CT1
to be 100.
Scroll Display by button
There is a button on the front of the meter. After initialization and self-checking
program , the meter display the measured values . The default page is total
kWh. If the user wants to check other information, he needs to press the scroll
button on the front panel.
Click the button, the LC D display will scroll the
measurements.
Keep pressing the button for 3 seconds, the meter
will enter set-up mode.
1
1-1
Total active energy(kWh)
Display format:0000.00 9999.99β†’
β†’ β†’ β†’10000.0 99999.9 0000.00
Import active energy(kWh)
Display format:0000.00 9999.99β†’
β†’ β†’ β†’10000.0 99999.9 0000.00
Export active energy(kWh)
Display format:0000.00 9999.99β†’
β†’ β†’ β†’10000.0 99999.9 0000.00
1-2
2Voltage (V)
3Current (A)
4Active power (W)
5Frequency (F)
6
7
Power factor ( PF )
8
9
Modbus Address or Primary address
Default: 001
Baudrate Default : 2400bps
Parity
None/Even/Odd are optional
Default: none
10
CT 1
Primary current 1A-9999A Default: 5
* Note: For the MID version of SDM120CTM, SD M120CTM B
and S DM120CT P, the CT ratio can be set only once.
(SDM120CT* only )
11
12
13
14
The display of each model:
3
4
CT 2
Secondary current 1A or 5A ,Default: 5
For S DM 120CT-M V,CT 2 is fixed with 100mV
(SDM120CT* only )
M-Bus secondary address High
M-Bus secondary address Low
(M-Bus version only )
(M-Bus version only )
Software version In kind prevail
Display LCD with white backlit
Max. Reading 99999.9kWh (SDM 120 45A)
999999 kWh (SDM 120 CT)
SDM120M: Total kWh Voltage
Current Power factor
Address
Baudrate
Import kWh Export kWh
Active power Frequency
Parity Software version
SDM120P: Total kWh Voltage
Current Power factor
Import kWh Export kWh
Active power Frequency
Software version
SDM120M B: Total kWh Voltage
Current Power factor
Address
Baudrate Secondary address
Import kWh Export kWh
Active power Frequency
Parity address high
Software version
Secondary
SDM120C TM : Total kWh Import kWh Export kWh Voltage
Current Active power Frequency Power factor
CT 1 CT 2
Address Baudrate Parity Software version
low
Full screen
It will last for 3 seconds.
Software version
It will last for 3 seconds.
Total active energy(kWh)
Ct1
Primary current 1A-9999A
Default: 5
(SDM120CT* only )
5A or 100mV CT Connect
Caution
Qualified personnel
Proper handling
6.2 Installation
Ω‰
5mm
5 IN Rail
6.3 Wiring diagram
G B A
MBUS 1MBUS 2
G B A
P1
S1
+-
P1
S1
MBUS 1 MBUS 2
P1
S1
7 Declaration of Conformity (for the MID approved version meter only).
We Zhejiang Eastron Electronic Co., Ltd. declares under our sole responsibility
as the manufacturer that the single phase multifunction electrical energy meter
SDM120 series correspond to the production model described in the EU-type
examination certificate and the requirements of the Directive 2014/32/EU. Type
examination certificate number 0120/SGS0141. Identification number of the
Notified Body: 0120.
Zhejiang Eastron Electronic Co Ltd ., .
No 1369 Chengnan Rd. .
Jiaxing,
Zhejiang China,
Email sales@eastrongroup com: .
Web www.eastrongroup com: .
Tel:86 573 83698881/83698882
Tel:86 573 83698883
6. Installation
6.1 Safety instruction
Information for your own safety
Warning
5. Dimensions
4. Communication
4.1 Pulse Output
The meter is equipped with 2 pulse outputs, which are fully isolated from
the inside circuit. That generates pulses i n proportion to the measured
energy. The pulse outputs are polarity dependent , passive transistor
output requiring an external voltage source for correct operation. For
this external voltage source, the voltage shall be 5-27V DC, and the
maximum input current shall be 27mA DC.
Please contact us for the detailed Modbus/M-Bus communicaon protocol.
sales@eastrongroup.com
SDM120M SDM120MB SDM120P
SDM120CTM /CT-MV
SDM120CTM B SDM120 CTP
SDM120CT-MV: Total kWh Import kWh Export kWh Voltage
Current Active power Frequency Power factor
CT 1
Address Baudrate Parity Software version
SDM120CT P: Total kWh Import kWh Export kWh Voltage
Current Active power Frequency Power factor
CT 1 CT 2
Software version
ATTENTION:Pule output must be fed as shown in the
wiring diagram below.Scrupulousil respect polarities
and the connection mode. Opto-coupler with
potential-free SPST-NO Contact.
Contact range:5~27VDC Max.current
Input:27mA DC
+-
Uimp
R
O U T P U T
MID
SDM120CT MB: Total kWh Import kWh Export kWh Voltage
Current Active power Frequency Power factor
CT 1 CT 2
Address Baudrate Parity Secondary
Secondary address low Software version
address high
The meter provides a RS485 port for remote communication. Modbus RTU is the
protocol applied. For Modbus RTU, the following RS485 communication parameters
can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
4.5 RS485 output for Modbus RTU (SDM120M and SDM120CTM/CT-MV only)
4.2 Pulse Output 1 ( SDM120M/ MB/CTM/CT-MV/CTM only)
Pulse output 1 is configurable. The pulse output 1 can be set to generate pulses to
represent total / import/ export kWh or kVarh. The pulse constant can be set to
generate 1 pulse per: 0.001 ( default) / 0.01 /0.1 /1kWh /kVarh.
Pulse width: 200 / 100/ 60ms ( default)
4.3 Pulse Output 1 ( SDM120P and SDM120CTP only)
Pulse output 1 is non-configurable. It is fixed up with Export kWh.
The constant is 1000imp/kWh.
4.4 Pulse Output2
Pulse output 2 is non-configurable. It is fixed up with Import kWh. The constant is
1000imp/kWh.
The Pulse width: 60ms
The meter provides an M-Bus port for remote communication. The protocol fully
comply with EN13757-3.The following communication parameters can be configured
via M-bus communication. Baud rate: 300,600, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
M-Bus network primary address: nnn – 3 digits number from 001 to 250
M-Bus network secondary address: 00 00 00 00 to 99 99 99 99
4.6 M-Bus communication EN13757-3 (SDM120MB and SDM120CTMB only)
This manual does not contain all of the safety measures for operation of the
equipment(module,devi ce),because special oper ating conditions,and loc al
code requirements or regulations may necessitate further measures.
However,it does contain inform ation which must be read for your personal
safety and to avoid material damages.This information is highlighted by a
war ning tri angle and is repres ented as follows, depending on the degree of
potential danger.
This means that failure to observe the instruction can result in death,
serious injury or considerable material damage.
Thi s means hazard of electr ic shock and failure to take the
necessary safety precautions will result in death,serious injury or
considerable material dam age.
Operation of the equipment (module, device) described in this manual may
only be performed by qual ified pers onnel . Qualifi ed personnel in this manual
means person who ar e authorized to commission, start up, ground and label
devices,systems and circuits according to safety
and Regulatory standards.
The equipment (device, module) may only be used for the application
specified in the catalogue and the user manual,and only be connected with
devices and components recommended and approved by EASTRON.
Use only insulating tools.
Do not connect while circuit is live (hot).
Place the meter only in dry surroundings.
Do not mount the meter in an explosive area or expose the meter to dust,
mildew and insects.
Make sure the used wires are suitable for the maximum current of this meter.
Make sure the AC wires are connected correctly before activating the
current/voltage to the meter.
Do not connect the meter to a 3 phase - 400VAC - network.
Do not touch the meter connecting clamps directly with your bare
hands, with metal, blank wire or other material as you may get an electrical
shock.
Make sure the protection cover is placed after installation.
Installation, maintenance and reparation should only be done by qualified
personnel.
Never break the seals and open the front cover as this might influence the
functionality of the meter, and will avoid any warranty.
Do not drop, or allow physical impact to the meter as there are high precision
components inside that may break.


Product specificaties

Merk: Eastron
Categorie: Meetapparatuur
Model: SDM120CT

Heb je hulp nodig?

Als je hulp nodig hebt met Eastron SDM120CT stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Meetapparatuur Eastron

Handleiding Meetapparatuur

Nieuwste handleidingen voor Meetapparatuur