ay Control Card
RELAYIO500
User’s Manual
K01-0000416-01
Internal Circuit
RELAYIO500 Card Pinout
Pin
Assignment Function I/O
Pin1 UPS FAULT O/P
Pin2 SUMMARY ALARM O/P
Pin3 GND (Common for Pin4) Power GND
Pin4 REMOTE SHUTDOWN Power + Vcc
Pin5 COMMON (For Relays) O/P
Pin6 BYPASS
1
/ UPS OFF O/P
Pin7 BATTERY LOW O/P
Pin8 UPS ON O/P
Pin9 UTILITY LINE FAIL O/P
Note: All relay contacts are normally open (N.O.) except for Pin6.
Acceptable Power + Vcc for Pin4 is 7.5 – 12V, 0.0672W Max.
1
For OL series UPS models only
1
6
2
7
3
4
5
8
9
UPS FAULT
SUMMARY ALARM
GND (Common for Pin4)
REMOTE SHUTDOWN
COMMON (For Relays)
BYPASS1 / UPS OFF
BATTERY LOW
UPS ON
UTILITY LINE FAIL
GND
Overview
The CyberPower Relay Control Card (RELAYIO500) offers users the
solution for UPS status monitoring via 5 output relays. In addition, the
RELAYIO500 card provides 1 input contact to perform UPS shutdown in
battery mode. This card is compatible with most CyberPower UPS devices
with expansion slot.
Installation Guide
The RELAYIO500 card is hot-swappable and can be installed while the
UPS is on.
1. Remove the two retaining screws on the expansion slot cover, and then
remove the cover.
2. Install the CyberPower RELAYIO500 card into the expansion slot.
3. Re-install and tighten the retaining screws.
Technical Specifications
RELAYIO500
Electrical
External S/D Voltage 7.5V – 12V
Power Dissipation 1.35W Max
(Default 12V input)
Physical
Dimensions (WxHxD) 41.8 x 14.2 x 81mm
(1.65 x 0.6 x 3.2 in)
Weight 52g (1.92oz)
Environmental
Operating Temperature 0°C – 40°C (32°F - 104°F)
Operating Humidity 0% – 95% (Non-condensing)
Output Relay Rating
Maximum
Voltage Current
30VDC / 125VAC 3A (per relay)
Function Description
Status Condition
Pin1 short to Pin5
UPS fault (Inverter Fault / DC Bus Fault / Over
Temperature / Output Short / Battery Over Charge /
Battery Test Fail
1
/ Fan Error
1
)
Pin2 short to Pin5
Summary alarm (Inverter Fault / DC Bus Fault /
Output Short / Over Temperature / Over Load /
Battery Missing / Battery Over Charge / Battery Low /
Wiring Fault / Runtime Low
2
/ Battery Test Fail
1
/
Load Over Setting Level
1
/ Fan Error
1
)
Pin6 short to Pin5 UPS is OFF. / UPS is in Bypass Mode.
1
Pin7 short to Pin5 Battery Low
Pin8 short to Pin5 UPS is on.
Pin9 short to Pin5 Utility Line Fail
1
For OL series UPS models only
2
For PR/OR series UPS models only
Example Application
Supply 12VDC to the COMMON contact and connect LEDs to the DB-9
port pins 1, 2 and 6 to 9. Connect a push button to COMMON (Pin5) and
REMOTE SHUTDOWN (Pin4). Pressing the button for at least 5 seconds
will shutdown the UPS when it is on battery.
Note: When the UPS is on battery, the REMOTE SHUTDOWN input (Pin4
& Pin3) accepts at least 5 seconds of high level signal (+12VDC) to perform
the UPS shutdown. UPS output power will turn off after 120 seconds.
1
6
2
7
3
4
5
8
9
UPS FAULT
SUMMARY ALARM
GND (Common for Pin4)
REMOTE SHUTDOWN
COMMON (For Relays)
BYPASS1 / UPS OFF
BATTERY LOW
UPS ON
UTILITY LINE FAIL
12V
Conformance Approvals
FCC Compliance Statement
This device complies with part 15 of the FCC rules. Operation is subject to
the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment to an outlet on a circuit different from that to
which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Important: Changes or modifications not expressly approved by the party
responsible for compliance could void the user's authority to operate the
equipment.
Canadian Compliance
CAN ICES-3 (B)/NMB-3(B)
CyberPower Systems, In
Website: www.cyberpowe
nc.
er.com


Product specificaties

Merk: CyberPower
Categorie: Niet gecategoriseerd
Model: RELAYIO500
Gewicht: 52 g
Breedte: 41.8 mm
Diepte: 81 mm
Hoogte: 14.2 mm
Gewicht verpakking: 160 g
Breedte verpakking: 168 mm
Diepte verpakking: 162 mm
Hoogte verpakking: 58 mm
Certificering: RoHS
Interface: UPS
Duurzaamheidscertificaten: RoHS
Plug and play: Ja
Temperatuur bij opslag: -10 - 50 °C
Intern: Ja
Luchtvochtigheid bij opslag: 0 - 95 procent
Compatibiliteit: OR Series UPS systems, PR Series UPS systems, OL1000RTXL2U, OL1500RTXL2U, OL1500RTXL2UN, OL3000RTXL2UHV
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 90 procent