CyberPower OL3000RTXL2UHVN Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor CyberPower OL3000RTXL2UHVN (21 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 69 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/21
User’s Manual
OL1000RTXL2U
OL1000RTXL2UN
OL1500RTXL2U
OL1500RTXL2UN
OL2200RTXL2U
OL2200RTXL2UN
OL3000RTXL2U
OL3000RTXL2UN
OL3000RTXL2UHVN
Cyber Power Systems (USA), Inc.
4241 12th Avenue East Suite 400 Shakopee, MN 55379
Phone: 877-297-6937
Fax: 952-403-0009
www.cyberpowersystems.com
K01-0000500-06
Copyright © 20 Cyber Power Systems, Inc.20
IMPORTANT SAFETY INSTRUCTIONS
1
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual
thoroughly before attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC power
outlet with fuse or circuit breaker protection. DO NOT plug the UPS into
an outlet that is not grounded. If you need to power-drain this equipment,
turn off and unplug the unit.
CAUTION! The battery can power hazardous components inside the
unit, even when the AC input power is disconnected.
CAUTION! The UPS should be placed r the connected equipment nea
and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area, free of conductive
contaminants. (Please see specifications for acceptable temperature and
humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock, do
not remove cover. No user serviceable parts inside. Refer servicing to
qualified service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric shock,
battery circuit is not isolated from AC power source; hazardous voltage
may exist between battery terminals and ground. Test before touching.
CAUTION! To reduce the risk of fire, connect the UPS to a branch
circuit with amperes (OL1000) / 15 amperes L 00) 20 amperes 12 (O 15 /
(OL / 30 amperes (OL3000 XL2U) / 16 amperes 2200) RT
(OL3000 XL2UHV) maximum over-current protection in accordance RT
with the National Electric Code, ANSI/NFPA 70.
CAUTION! The AC outlet where the UPS is connected should be close
to the unit and easily accessible.
CAUTION! Please use only -marked mains cable, (e.g. the mains UL
cable of your equipment), to connect the UPS to the AC outlet.
CAUTION! Please use only -marked power cables to connect any UL
equipment to the UPS.
CAUTION! When installing the equipment, ensure that the sum of the
leakage current of the UPS and the connected equipment does not
exceed 3.5mA.
CAUTION! The OL1 / 000 OL1500 / OL2200 / OL3000 models may
only be installed by qualified maintenance personnel..
CAUTION! Do not unplug the unit from AC Power during operation, as
this will invalidate the protective ground insulation.
CAUTION! To avoid electric shock, turn off and unplug the unit before
installing the input/output power cord with a ground wire. Connect the
ground wire prior to connecting the line wires!
CAUTION! Do not use improper size power cord as it may cause an
damage to your equipment and cause fire hazards.
CAUTION! Wiring must be done by qualified personnel.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT
EQUIPMENT! Under no circumstances this unit should be used for
medical applications involving life support equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce
the risk of fire, do not use with or near aquariums. Condensation from
the aquarium can come in contact with metal electrical contacts and
cause the machine to short out.
CAUTION! Do not dispose of batteries in fire the battery may as
explode.
CAUTION! Do not open or mutilate the battery, released electrolyte is
harmful to the skin and eyes.
CAUTION! A battery can present a risk of electric shock and high short
circuit current. The following precaution should be observed when
working on batteries
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.
CAUTION! The unit has a dangerous amount of voltage. When the
UPS indicators is on, the units may continue to supply power thus the
unit s outlets may have a dangerous amount of voltage even when it s not ’ ’
plugged in to the wall outlet.
CAUTION! Make sure everything is turned off and disconnected
completely before conducting any maintenance, repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor before
any other cables are connect ed.
WARNING! (Fuses): To reduce the risk of fire, replace only with the
same type and rating of fuse.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO
DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE
HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR
DRYERS TO UPS OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR
SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND
THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED
PERSONNEL AWAY FROM BATTERIES!
Copyright © 20 Cyber Power Systems, Inc.20
UNPACKING
2
1K/1.5KVA or 2.2K/3KVA UPS
User’s manual Register card
Rackmount left rail Rackmount right rail
Left hanging bracket Right hanging bracket
Rackmount ears (Stands) (2)
USB communication cable
Serial Interface Cable (RS-232)
M5X7L black at head screws (8)
M5X12L black pan head screws (12)
M5X6L silver pan head screws (6)
Plastic washers (8)
Screw hole dust covers ( ) 12
Rubber pads (12)
PowerPanel management software download card
* PowerPanel® Business Edition software is available
on our website. Please visit
www.cyberpowersystems.com and go the Software to
section for FREE download.


Product specificaties

Merk: CyberPower
Categorie: Niet gecategoriseerd
Model: OL3000RTXL2UHVN
Kleur van het product: Zwart
Gewicht: 30930 g
Breedte: 432 mm
Diepte: 600 mm
Hoogte: 89 mm
Snoerlengte: 3 m
Gewicht verpakking: 36740 g
Breedte verpakking: 558.8 mm
Diepte verpakking: 908.56 mm
Hoogte verpakking: 234.7 mm
Materiaal behuizing: Metaal
LED-indicatoren: Ja
Vormfactor: Rackmontage/toren
Meegeleverde kabels: Stroomingangskabel
Accu/Batterij voltage: 12 V
Aantal Ethernet LAN (RJ-45)-poorten: 1
Geluidsalarm(en): Ja
Responstijd: 0 ms
Duurzaamheidscertificaten: RoHS
Uitgangsvermogen: 2700 W
Batterij capaciteit: 9 Ah
Accu/Batterij oplaadtijd: 4 uur
Temperatuur bij opslag: -20 - 45 °C
ECO mode: Ja
Frequentie: 40/70 Hz
Luchtvochtigheid bij opslag: 0 - 95 procent
Veiligheid: UL 1778 5th Ed. CSA C22.2 NO.107.3-05 FCC Part 15 Class A
Modem (RJ-11) poort: 1
Stekker: NEMA L6-30R
Rackcapaciteit: 2U
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 90 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Type beeldscherm: LCD
Aantal batterijcellen: 6
Surge energy rating: 1335 J
Aantal AC uitgangen: 3 AC-uitgang(en)
Output power capacity: 3 kVA
Ingang operation voltage (min): 120 V
Ingang operation voltage (max): 280 V
Uitgang operation voltage (min): 200 V
Uitgang operation voltage (max): 240 V
Crest factor: 3:1
UPS-topologie: Dubbele conversie (online)
Typische backup tijd op halve lading: 11 min
Typische backup tijd op volledige lading: 3.5 min
Hot-swap batterij: Ja
Output frequentie: 50/60 Hz
Hoorbare alarmstanden: Low battery alarm, Overload alarm
Input vermogensfactor: 0.99
Uitgangsspanningsregeling: 2 procent
EMI/RFI geluidsfiltering: Ja
Spanningsbeveiliging: Ja
Golfvorm: Sinus
Uitgangsfrequentieregeling: 0.25 Hz
Automatic Voltage Regulation (AVR): Ja
Output vermogensfactor: 0.9
Efficiëntie (ECO-modus): 97 procent
Vervangings-batterij cartridge: RB1290X6A

Heb je hulp nodig?

Als je hulp nodig hebt met CyberPower OL3000RTXL2UHVN stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd CyberPower

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd