Crestron CLXI-1MC4 Handleiding

Crestron Controller CLXI-1MC4

Lees hieronder de 📖 handleiding in het Nederlandse voor Crestron CLXI-1MC4 (6 pagina's) in de categorie Controller. Deze handleiding was nuttig voor 31 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/6
CLTI- & CLXI-1MC4
Terminal Block & Module Locations (Single-wide Enclosure)
Functional Summary
MODULETERMINAL
BLOCK
GROUNDING
TERMINAL
BLOCK (INSTALL INTO
LOWEST
AVAILABLE
SPACES)
The Crestron 1-Feed, 4-Motor Terminal Block and
Module (CLTI-1MC4 and CLXI-1MC4, respectively), are
considered a single entity and must be used together.
They ship separately to permit termination of the field
wiring to the CLTI-1MC4 prior to installation of the
CLXI-1MC4, as described in this guide. They can be
mounted in any Crestron Automation Enclosure (CAEN
or CAENIB-Series Enclosures). The terminal block is
designed to terminate the circuit feed (LINE and
NEUTRAL) and distribute the controlled circuits (LOAD)
to the motors. The module connects to the terminal block
and performs control of four bi-directional motors. The
maximum load is 8 amps (1 HP) for any controlled
circuit, limited to 13 amps total per module. The unit
requires 230VAC 50 Hz, 1 phase input voltage. An
oversize heat sink dissipates heat efficiently. There are
LEDs on the module to indicate communication to a
Cresnet network, input power to the module, and output
power to the load.
Installation
Terminal block and module must be mounted into a
Crestron Automation Enclosure by a licensed electrician,
in accordance with all national and local codes. Terminal Block & Module Locations (Double-wide Enclosure)
CAUTION: This equipment is for indoor use only and
needs to be air-cooled. Mount in a well-ventilated area.
The ambient temperature must be 0°C to 40°C (32°F to
104°F). The relative humidity must be 0% to 90% (non-
condensing).
GROUNDING TERMINAL BLOCKS
MODULETERMINAL BLOCK
(LEFT)
TERMINAL BLOCK
(RIGHT)
(INSTALL INTO
LOWEST
AVAILABLE
SPACES)
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and
right sides) of double-wide enclosures. Modules are
installed along the right side of single-wide enclosures
and side-by-side in the center of double-wide enclosures.
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so
that they can be properly wired. Refer to the illustrations
shown in the next column when considering the location
of terminal blocks and modules within an enclosure.
NOTE: Modules and terminal blocks must be installed
into the lowest available spaces and continue toward the
top of the enclosure.
Crestron Electronics, Inc. Installation Guide – DOC. 6409A
15 Volvo Drive Rockleigh, NJ 07647 (2013811)
Tel: 888.CRESTRON 11.07
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
Terminal Block & Module Crestron CLTI- & CLXI-1MC4
Terminal Block Installation and Field
Wiring
NOTE: To install a CLTIBN Circuit Breaker Terminal
Block, refer to the latest version of the CLTIBN
Installation Guide (Doc. 6561) which can be downloaded
from the Crestron website (www.crestron.com/manuals).
NOTE: Both left-side and right-side adhesive wiring
labels are provided. The left-side labels are used in both
single and double-wide enclosures. The right-side labels
are only used in double-wide enclosures.
1. Remove the backing from the left or right
adhesive wiring label.
2. Apply the adhesive label by aligning the holes in
the label with the appropriate holes on the
Crestron Automation Enclosure where the
terminal block is to be mounted. For information
on mounting locations, refer to the latest version
of the CAEN Installation Guide (Doc. 5940) or
the CAENIB Installation Guide (Doc. 6562). The
wiring label lies beneath the terminal block as
shown in the two wiring diagrams on this page.
3. Use the two supplied self-tapping pan Phillips
screws (8B x ¼-inch (6 mm) length) to secure
the terminal block to the Crestron Automation
Enclosure.
CAUTION: The jumper on the blue section of the
terminal block ties the neutral in to the neutral outs.
This jumper should never be removed.
NOTE: Use copper conductors only – rated 75°C.
4. With the circuit breaker turned off, connect the
circuit feed (LINE and NEUTRAL) and
controlled circuit (LOAD) wires to the terminal
block per the markings provided on the wiring
label (as shown in the diagrams on this page).
Terminal blocks accept one 2.5 - 6.0 mm
2 wire.
Wires should be stripped to 12 mm. Tighten
terminal blocks to 1 Nm.
NOTE: Only one motor may be wired per circuit.
5. Grounding terminal blocks are available in the
cabinet for termination of ground wires. Tighten
to 4 Nm (2.5 - 6.0 mm2), 4.5 Nm (10.0 mm2), or
5.1 Nm (16 – 25 mm2).
6. Test the circuit for electrical faults by connecting
LINE to OPEN 1. Switch on the circuit breaker
and check that it does not trip and that the load
connected to OPEN 1 is receiving power. Switch
off the circuit breaker, remove the connection
between LINE and OPEN 1, and repeat this step
for CLOSE 1 and then sequentially for each
OPEN and CLOSE motor connection.
NOTE: If installing in a CAENIB, complete the
installation with a CAENIB-BP Blank Plate. Refer to the
latest version of the CAENIB-BP Installation Guide (Doc.
6563) for details.
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Single-wide and Left Side Double-wide Enclosures)
GROUNDING
TERMINAL
BLOCK
GND
NEUTRAL
AREA FOR
MODULE
LOCATION
LABEL
JUMPER
TERMINAL
BLOCK
LEFT SIDE
WIRING LABEL
TO
MOTOR 1
TO
MOTOR 2
TO
MOTOR 3
TO
MOTOR 4
LINE
(FROM 10
OR 16 AMP
CIRCUIT
BREAKER)
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Right Side Double-wide Enclosures)
NEUTRAL
AREA FOR
MODULE
LOCATION
LABEL
JUMPER
TERMINAL
BLOCK
RIGHT SIDE
WIRING LABEL
TO
MOTOR 4
TO
MOTOR 3
TO
MOTOR 2
TO
MOTOR 1
LINE
(FROM 10
OR 16 AMP
CIRCUIT
BREAKER)
GROUNDING
TERMINAL
BLOCK
GND
2 •
•
•
•• Terminal Block & Module: CLTI- & CLXI-1MC4 Installation Guide – DOC. 6409A
Crestron CLTI- & CLXI-1MC4 Terminal Block & Module
Module Installation Wiring Diagram of the Terminal Block to the Module
(Single-wide and Left Side Double-wide Enclosures)
JUMPER INSTALLED
RED
BROWN
YELLOW
RED
YELLOW
RED
YELLOW
RED
YELLOW
JUMPER ON BLUE
SECTION REMAINS
INSTALLED.
BLUE
ENLARG EMENT DETAIL:
CAUTION: Module contains electrostatic sensitive
devices (ESDs); unit must be handled from metal chassis
– do not touch PC board or components.
NOTE: Modules are to be installed after enclosure has
been completely wired. Refer to the terminal block
installation procedure on page 2 for details.
1. Use the four supplied self-tapping pan Phillips
screws (8B x ¼-inch (6 mm) length) to secure
the module to the enclosure.
2. As shown in the wiring diagrams (next column),
connect the wires from the module to the
terminal block. Each wire exits the module
directly in line with, and is the same color as, the
terminal to which it should be connected. Wires
are pre-stripped to 12 mm. Tighten to 1 Nm.
3. If the module is being installed above another
module within the enclosure, attach the supplied
module interconnect cable between the two
modules. The illustration below depicts the area
within a double-wide enclosure where the
corners of four modules meet.
Wiring Diagram of the Terminal Block to the Module
(Right Side Double-wide Enclosures)
NOTE: One wire on the module interconnect cable
may be a different color from the rest. The color has
no bearing on its orientation during installation.
JUMPER INSTALLED
RED
BROWN
BLUE
YELLOW
RED
YELLOW
RED
YELLOW
RED
YELLOW
JUMPER ON BLUE
SECTION REMAINS
INSTALLED.
ENLARGEMENT DETAIL:
Use Module Interconnect Cable to Wire Module to Module
MODULE
INTERCONNECT
CABLE ATTACHED
CONNECTION
NOT
MADE
4. Turn on the circuit breaker and verify that the
green PWR LED on the module lights and the
breaker does not trip.
NOTE: Power must be supplied to LINE for the
module to communicate with the control system or
for any of the circuits to operate.
Installation Guide – DOC. 6409A Terminal Block & Module: CLTI- & CLXI-1MC4 •
•
•
•• 3


Product specificaties

Merk: Crestron
Categorie: Controller
Model: CLXI-1MC4

Heb je hulp nodig?

Als je hulp nodig hebt met Crestron CLXI-1MC4 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Controller Crestron

Handleiding Controller

Nieuwste handleidingen voor Controller