Camille Bauer Sineax A230 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Camille Bauer Sineax A230 (24 pagina's) in de categorie Meetapparatuur. Deze handleiding was nuttig voor 29 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/24
1
Safety notes
The installation and commissioning should only be carried out by trained
personnel.
Check the following points before commissioning:
that the maximum values for all the connections are not exceeded, see
the “Technical data” section,
that the connection wires are not damaged, and that they are not live
during wiring,
that the power fl ow direction, and the phase rotation are correct.
The instrument must be taken out of service if safe operation is no lon-
ger possible (e.g. visible damage). In this case, all the connections must
be switched off. The instrument must be returned to the factory or to an
authorized service dealer.
It is forbidden to open the housing and to make modifi cations to the instru-
ment. The instrument is not equipped with an integrated circuit breaker.
During installation check that a labeled switch is installed and that it can
easily be reached by the operators.
Unauthorized repair or alteration of the unit invalidates the warranty.
Contents Page
Brief description 2
Technical data 2
Commissioning 3
Electrical connections 3
Measured value display 5
Operation 9
Display window 10
Programming 13
Programming charts 20
Dimensional drawing 22
Camille Bauer LTD
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Phone +41 56 618 21 11
Fax +41 56 618 21 21
info@camillebauer.com
www.camillebauer.com
The instruments must only be disposed of in the
correct way!
A 230 / A230s Be 154 807-10 03.13
Operating Instructions
Multifunctional Power
Monitor with System Analysis
SINEAX A 230 / A 230s
2
Brief description
Panel mounting instrument A230 with dimensions 144x144x46 mm
resp. A230s with dimensions 96 x 96 x 46 mm. Four-quadrant mea-
surement for power system and consumption analysis in single and
multi-phase AC systems. Three large LED displays with four digits
plus sign. The converter data are included for direct display and
further processing. Confi gurable display settings for user specifi c
presentation, integrated energy meters, impulse counters, and limit
value indication. Comprehensive average value and max./min. value
functions. Harmonic analysis and THD measurement. Determination
of the neutral wire current. Asymmetry factor and neutral point vol-
tage shift. Two switched outputs for the control of impulse counters,
or for signalling limit alarms.
Technical data
(for more detailed information please see datasheet, download under
www.camillebauer.com)
Measuring inputs
Nominal frequency: 50, 60 Hz
Nominal input voltage: Phase-phase: 500 V
Phase - N: 290 V
Nominal input current: 5 A or 1 A
Continuous thermal rating of inputs
10 A at 346 V in single-phase AC system
10 A at 600 V in three-phase system
Short-time thermal rating of inputs
Input variable Number of
inputs
Duration
of
overloads
Interval between
two overloads
577 V LN 10 1 s 10 s
100 A 10 1 s 100 s
100 A 5 3 s 5 min
Measuring ranges
U, I, S: ≤ 120% of nominal value
P, Q: ≤ ± 120% of nominal value
F: 45 to 65 Hz
cosϕ: ± 1
Display
The measurement display is 4 digit (frequency) and right justi ed.
Energy values are displayed with 8 digits.
Zero value suppression
PF resp cos Display ---, if Sx < 0.2% Snennϕ:
Currents: Display 0, if Ix < 0.1% Inenn
unb. U: Display 0, if Ø U < 5% Unenn
Pulse/Limit value outputs
Depending on the function selected, the two digital outputs can
be used either as pulse outputs for actual and reactive energy or
as limit signals.
The outputs are passive, and are galvanically isolated from all the
other circuits by opto-couplers. They are suitable to drive tariff
devices (S0-standard DIN 43 864), or 24 V relais.
Uext ≤ 40 V DC (OFF: leakage current ≤ 0.1 mA)
IL ≤ 150 mA (ON: terminal voltage ≤ 1.2 V)
t
U
U
e.g. energy import
e.g. limit value output
R
L
R
L
SO2
SO1
20
21
22
U
ext
Limit value outputs
The measured values can be freely allocated.
Pulse outputs
Active and reactive energy pulses can be generated for the control
of electronic and electromechanical counters.
Power supply
DC-, AC power pack 50 to 400 Hz
100 to 230 V AC/DC ±15% or 24 to 60 V AC/DC ±15%
(UL) 85 bis 125 V DC
Power consumption: 3 VA (without extension module)
A marked and easily accessible current limiting
switch has to be arranged in the vicinity of the device
for turning off the power supply. Fusing should be
10 Amps or less and must be rated for the available
voltage and fault current.
Reference conditions
acc. to IEC 688 resp EN 60 688
Sine 50 - 60 Hz, 15 - 30°, application group II
Measurement accuracy (related to nominal value)
Current, voltage ± 0.2%
Power ± 0.5%
Power factor ± 0.5%
Energy ± 0.5%
Frequency ± 0.02 Hz (abs.)
Environmental conditions
Operating temperature: -10 to +55 °C
Storage temperature: -25 to +70 °C
Humidity relative: ≤ 75%
Altitude: 2000 m max.
Indoor use statement
Safety
Protection class: II (voltage inputs with protection
impedances)
Measuring category: III
Pollution degree: 2
Measurement voltage: 300 V
Test voltage: Between current inputs, power
supply, digital outputs, terminals
of the plugged-in module: 3700 V /
50 Hz / 1 min.
On voltage inputs:
4.25 kV 1.2/50 μs
Module connections: The pin rail at the back is connected
to the voltage inputs via a protec-
tion impedance. Only the permitted
modules can be plugged-in!
Enclosure protection: IP 20
3
Commissioning
The multifunctional power monitor is made operational by switching
on the power supply. The following appears sequentially on the
display:
1. Segment tests: all the segments of the displays and all the LEDs
are lit for 2 s.
2. Version of the software : e.g. A 230 1.04
3. The 3 line voltages at switching on.
Loss of the power supply
All the values confi gured remain during a loss of the power sup-
ply.
On reconnecting the power supply, the last mode selected is dis-
played.
Note of maintenance
No maintenance is required.
Electrical connections
Safety Disconnects
The mains supply power to the instrument must be
installed downstream from a switched current limiting
device.
The circuit protection device should be 20 Amps or
less, and must be rated for the available voltage and
fault current; 5 Amp fuses are preferred.
WARNING
All mains supply power to the instrument must be
installed downstream from a switched current limiting
device.
The circuit protection device should be 20 Amps or
less, and must be rated for the available voltage and
fault current; 5 Amps are preferred.
The national provisions (e.g. in Germany VDE 0100
“Conditions concerning the erection of heavy current
facilities with rated voltages below 1000 V”) have to
be observed in the installation and material selection
of electric lines!
When using external PT’s or CT’s refer to the
manufacturer’s information for connections for volta-
ge and current monitoring.
The electrical connections are identical for the SINEAX A 230 and
A 230s.
U1
I1
U2
I2
U3
I3
N
Power supply
Pulse /
Limit value output
Measuring input, acc. to measuring mode
Jumper
1 2 +
No. 1
2022 21
1 2
SO
LOCK
Camille Bauer AG
Switzerland
14 15
11
N
9
I3
8
U3
7
I3
6
I2
5
U2
4
I2
3
I1
2
U1
1
I1
SINEAX A230s
UL: 3~300V 5A 50/60Hz CAT III
IEC: 3~500/290V 5A 50/60Hz CAT III
Ord: 010/123456/010/001
Man: 10/02
NLBxxxx
100-230V AC
85-125V DC
50-400Hz 3VA
230S-121200
Connecting modes
L1
N
k l
K L
2 11 31
Single phase
AC system
L1
N
v
V
u
U
k l
K L
2 11 31
System/
application Terminals
L1
L2
L3
5 182 3
L1
L2
L3
k l
K L
5 182 3
L1
L2
L3
u
U
v
V
v
V
u
U
k l
K L
5 182 3
3-wire
3-phase
symmetric
load
I: L1
Connect the voltage according to the following
table for current measurement in L2 or L3:
Current Terminals 2 5 8
transf.
L2 1 3 L2 L3 L1
L3 1 3 L3 L1 L2
L1
N
2 11 31
Symbol Meaning
Device may only be disposed of in a professional
manner!
Double insulation, device of protection class 2
CE conformity mark. The device ful lls the require-
ments of the applicable EC directives.
Products with this mark comply with both the
Canadian (CSA) and the American (UL) requirements
Caution! General hazard point. Read the operating
instructions.
General symbol: Input
General symbol: Output
General symbol: Power supply
CAT III Measurement category CAT III for current and vol-
tage inputs


Product specificaties

Merk: Camille Bauer
Categorie: Meetapparatuur
Model: Sineax A230

Heb je hulp nodig?

Als je hulp nodig hebt met Camille Bauer Sineax A230 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Meetapparatuur Camille Bauer

Handleiding Meetapparatuur

Nieuwste handleidingen voor Meetapparatuur