Air King MQFAM Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Air King MQFAM (12 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 230 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/12
www.airkinglimited.com6728092 Rev. E 4/22 1 of 12
SAVE THESE INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have
questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service panel
and lock the service disconnecting means to prevent power from being
switched on accidentally. When the service disconnecting means cannot
be locked, securely fasten a prominent warning device, such as a tag, to
the service panel.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified person(s)
in accordance with all applicable codes and standards, including fire-
related construction.
b) Sufficient air is needed for proper combustion and exhausting of gases
through the flue (chimney) of fuel burning equipment to prevent back
drafting. Follow the heating equipment manufacturer’s guideline and
safety standards such as those published by the National Fire Protection
Association (NFPA) and the American Society for Heating, Refrigeration,
and Air Conditioning Engineers (ASHRAE), and the local code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE
MATERIALS AND VAPORS.
d) This unit must be grounded.
e) To avoid motor bearing damage and noisy and/or unbalanced impellers,
keep drywall spray, construction dust, etc. off power unit.
f) Read all instructions before installing or using exhaust fan.
g) For residential installations only.
h) Must use suitable weather hood with insect screen to protect air intake.
WARNING: TO REDUCE THE RISK OF FIRE,
REMOVE ANY SHIPPING MATERIAL THAT MAY BE
PRESENT INSIDE THE UNIT.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, DO NOT USE THIS FAN WITH ANY
SOLID-STATE SPEED CONTROL DEVICE.
WARNING: DO NOT USE IN KITCHENS.
WARNING: THE DUCTING FROM THIS FAN TO THE
OUTSIDE OF THE BUILDING HAS A STRONG EFFECT ON THE
AIR FLOW, NOISE AND ENERGY USE OF THE FAN. USE THE SHORTEST,
STRAIGHTEST DUCT ROUTING POSSIBLE FOR BEST PERFORMANCE,
AND AVOID INSTALLING THE FAN WITH SMALLER DUCTS THAN
RECOMMENDED. INSULATION AROUND THE DUCTS CAN REDUCE
ENERGY LOSS AND INHIBIT MOLD GROWTH. FANS INSTALLED WITH
EXISTING DUCTS MAY NOT ACHIEVE THEIR RATED AIRFLOW.
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN
THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should
always be followed to reduce the risk of fire, electric shock and
injury to person, including the following:
Inline Fan
MQFAM, MFAS
IMPORTANT INSTRUCTIONS - OPERATING MANUAL
www.airkinglimited.com6728092 Rev. E 4/22 2 of 12
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
WARNING: TO REDUCE THE RISK OF FIRE, REMOVE ANY
SHIPPING MATERIAL THAT MAY BE PRESENT INSIDE THE UNIT.
SECTION 1
Preparing the Fan
1. Unpack fan from the carton and confirm that all pieces are present. In addition to the fan
you should have:
2 - Collar Assembly (attached) 1 - Controller (attached) (MQFAM only)
2 - Mounting Brackets (attached) 1 - Instruction/Safety Sheet
2. Choose the location for your fan. To ensure the best air and sound performance, it is
recommended that the length of ducting and the number of elbows be kept to a minimum,
the radius of each elbow be as large as possible for the installation, and that insulated hard
ducting be used. This fan will require at least 10" of clearance in the ceiling or wall. The
fan mounts using the provided mounting brackets or can be surface mounted to a wall or
ceiling.
NOTE: The fan must be installed into a location that can be easily accessed once installed.
3. No additional vibration deadening materials are needed for this fan.
SECTION 2
Mounting the Fan
1. Confirm the fan is positioned so the air flow is in the correct direction.
2a. Surface Mounting: Locate at least one stud or joist. Place the fan in position so that the
mounting bracket is centered on the stud or joist and make the location for the four (4)
holes. Remove the fan and install properly rated wall/ceiling anchors for the holes that do
not go directly into a joist or stud. Position fan in place and secure with screws (not
included) (Figure 1).
2b. Mounting to a Joist: Install two - 2 x 4 headers (not included) between the joists. Position
the fan housing on top of the headers and secure the mounting brackets with screws (not
included) to the header .(Figure 2)
2c. Hanging Bar Mounting: Lift unit up onto the threaded rods and secure in place using
appropriate hardware (not included) (Figure 3).
Figure 1
Screws
Stud/Joist Anchor
Air Flow
Figure 2
Joist
2 x 4 Header
Bracket
9"
Figure 3 Bracket
Housing
Threaded Rod
SECTION 3
Ducting
NOTE: 6" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL
BUILDING CODES.
NOTE: The ducting from this fan to the outside of the building has a strong effect on the air
flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for
best performance, and avoid installing the fan with smaller ducts than recommended. Insulation
around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing
ducts may not achieve their rated air flow.
WARNING: MAKE SURE THE FRESH AIR INTAKE PORT COMPLIES WITH
ALL LOCAL AND NATIONAL CODES AND IS LOCATED AT LEAST 6 FEET AWAY
FROM SOURCES OF CONTAMINATION SUCH AS BUT NOT LIMITED TO: DRYER,
FURNACE OR CENTRAL VACUUM EXHAUSTS, GAS APPLIANCES SUCH AS BBQ GRILLS,
GARBAGE BINS OR OTHER EXHAUST PORTS.
NOTE: To ensure quiet operation of in-line and remote fans, each fan shall be installed using
sound attenuation techniques appropriate for the installation. For bathroom and general
ventilation applications, at least 8 feet of insulated flexible duct shall be installed between the
exhaust or supply grille(s) and the fan.
1. Connect the ducting to the fan’s duct collar Seal ducting to housing with (Figure 4).
appropriately rated tape. Use screws or suitable clamps to secure in place. Make sure the
fresh air intake is connected to a properly installed intake port that is a suitable weather
hood with insect screen to protect air intake. It is recommended that low restriction
termination fittings be used.
2. Ensure duct joints and exterior penetrations are sealed with caulk or other similar material
to create an air-tight path to minimize building heat loss or gain and to reduce the potential
for condensation. Place/wrap insulation around duct and/or fan in order to minimize
possible condensation buildup within the duct, as well as building heat loss or gain.
NOTE: At the base of the duct adapter, there is a small diameter test port hole covered with a
plastic cap. Make sure the test port is not covered up with the ducting so that it can be accessed
for pitot tube testing. To access the port, remove the port cover and insert tube.
SECTION 4
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE
IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL
ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL
WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not require the removal of the
fan’s blower assembly.
1. Remove the wire compartment cover screw and place cover in a secure place (Figure 5).
Figure 4
Air Flow
Intake
Ducting
Outlet
Ducting
Test Port
Figure 5
Screw
Wire
Compartment
Cover
Ground
Screw
www.airkinglimited.com6728092 Rev. E 4/22 3 of 12
2. Pull the loose black, white and green wires out from the wire compartment (additional
wires will be present). Install an approved electrical connector to the wire compartment
cover (not included). Run a black (hot), white (neutral), and a green or bare ground wire
from the supply through the electrical connector. Connect all wires from the supply to their
corresponding wires within the wire compartment . Use approved methods for (Figure 6)
all connections.
3. Carefully tuck wires back inside wire compartment and replace wire compartment cover
securing with the screw that was removed earlier.
SECTION 5
Setting the Speed
1. Determine the CFM required. The unit can
be set for 50 CFM or 80 CFM. Remove the
screw securing the access panel cover in
place and open the cover to gain access.
Locate the speed control panel inside the
unit (Figure 7).
2. Locate the rocker switch at the top of the
wiring compartment and set to the desired
CFM - “Low” for 50 CFM or “HIGH” for 80
CFM (Figure 8).
SECTION 6
Optional Air Filter
An air filter (available separately) can be added
to this unit to provide additional filtration of the
intake air. The unit will accept a 9" x 8" x 2" filter.
To install:
NOTE: Adding an air filter will decrease the
airflow of the unit. Filters must be changed
regularly. Refer to the filter manufacturer’s
recommendations to determine how often the
filter should be changed.
1. Remove the screw securing the access panel cover in place and open the cover to gain
access to the controls and filter area.
2. Ensure the filter is facing the correct way and slide the filter into the slot in the housing.
Make sure the filter is seated all the way to the bottom of the housing (Figure 9).
3. Close the access panel and reinstall the screw holding the access panel in place.
SECTION 7
Completing the Installation
NOTE: When fan is mounted inline and no penetration is made into unconditioned spaces, there
is no need to use a sealant appropriate for contact with the building materials present and for the
temperature requirements of the installation to prevent air leakage from unconditioned spaces.
Additional material (backing rod, ceiling material) are also not required.
Figure 6
Supply from house
Black
Neutral (White)
Ground (Green or Bare)
Fan
Neutral (White)
Green
Black
Green
By others
Screw
Figure 7
Rocker
Switch
50 80
Figure 8
Figure 9
Filter
Screw
Air Flow
NOTE: This unit is equipped with a wire mesh insect screen. Confirm that the screen is installed
on the inside of the unit on the inlet ducting side.
1. If the screen is not in place, insert the screen into the tab at the base of the unit (make sure
the wider side of the screen is running side to side inside the unit) (Figure 10).
2. Slide the screen to the side with the larger top tab making sure the screen fits behind the
tab (Figure 10).
3. Slide the screen back over towards the smaller top tab making sure the screen fits behind
the tab (Figure 11).
4. Confirm that the screen is being held in place by both top tabs (Figure 11).
5. Close the access panel and reinstall the screw holding the access panel in place.
6. Restore power and test your installation.
SECTION 8 (MQFAM Only)
Using the Controller
1. On Mode: Fan will run continuously when the ON button ( ) is pressed. If ambient
temperature is lower than 34°F (2°C), the fan will stop and initiate Sampling Mode. Sampling
Mode Cycle: stop 15 mins; run for 5 minutes to determine current air temperature. During
Sampling Cycle, if the temperature is in the accessory heater (optional) control range, the
heater will turn on (if it has been installed). The fan will return to continuous ventilation
once ambient temperature rises above 34°F (2°C).
2. Energy Savings Mode: To enter the Energy Savings mode, press the Energy Savings
button ( ) until appears on the left side of the display. Energy Savings mode
engages the settings configured in . When the unit is on, the display will SECTION 9
show the current conditions (temperature and humidity level) as well as if it is in Energy
Savings mode or not. Other icons/information that may be on the display include:
Fan icon appears when the fan is on.
“HI°F” appears if the intake temperature is above 150°F (65°C).
“Lo°F” appears if the intake temperature is below 15°F (-10°C).
“Lo% appears if the intake humidity is below 10%.
3. Optional Heater Unit: An optional heater unit is available for climates that the air coming into
the unit falls below 54°F (12°C). To install the unit, follow the directions that are included with
that unit. The display will show a thermometer icon with either a “1”( 1) or “1 2” ( 1
2) when
the temperature range is at a level where the heating element would come on if present.
Stage 1 - “1 turns on when the intake air temperature is between 39°F (4°C) and 54°F
(12°C). Stages 1 and 2 “1 2 turn on when the intake air temperature is between 33°F (0°C)
and 39°F (4°C).
Figure 10
Base Tab
Screen
Larger
Top Tab
Figure 11
Screen
Smaller Top Tab
Screen


Product specificaties

Merk: Air King
Categorie: Niet gecategoriseerd
Model: MQFAM

Heb je hulp nodig?

Als je hulp nodig hebt met Air King MQFAM stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Air King

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd