CO2 transmitter
eSENSEâ„¢ Slim
General
The IAQ-sensor product eSENSE Slim (sensor in industrial housing) is used to
measure indoor air carbon dioxide concentration. The 300 mm long cable connected
to the PCB makes it possible to place the sensor where the mounting is difficult.
The unit is designed for connecting to Direct Digital Control (DDC) with 0-5V signal
inputs.
Gas and Air Sensors
eSENSE Slim 0-5V
Installation Manual
Document
IMA0274
Rev
5
Page
2 (4)
The eSENSE Slim has a permanently connected cable to the PCB.
Figure 1. The eSENSE-Slim with the cable.
Figure 2. The eSENSE PCB. The brown cable is connected to OUT1 voltage output 0-5VDC
Shrinking tubing
Brown, 0-5V
Red, +24V
Black, GND
Brown, 0-5V
Red, +24V
Black, GND
300(11,8)
Document
IMA0274
Rev
5
Page
3 (4)
Electrical connections
The power supply has to be connected to +~ and . is considered as
system ground. The same ground reference has to be used for the eSENSE unit and
for the DDC/signal receiver.
PLEASE NOTE!
The same ground reference has to be used for the eSENSE
unit and for the control system!
Connection
Terminal
Function
Electrical Data
Remarks
+~
Power (+)
Power ground (-)
24 VAC/DC+ (+-20%),
2W
24 VAC/DC-
Red
Black
OUT 1
OUT 2
Analogue Output 1 (+)
Analogue Output 2 (+)
0-5 VDC
2-10 VDC
Brown
0-2000 ppm CO2
Not connected
Table I. Electrical terminal connections for eSENSE
Output Configurations
The sensors/controllers are supplied from the factory with a 0.-.5VDC linear output
for OUT1 (see Table I).
Self diagnostics
The system contains complete self-diagnostic procedures. A full system test is
executed automatically every time the power is turned on. In addition, constantly
during operation, the sensor probe is checked against failure.
PLEASE NOTE!
The sensor accuracy is defined at continuous operation (at least 3 weeks after
installation)
Product specificaties
Merk: | Senseair |
Categorie: | CO2 Sensor |
Model: | eSENSE Slim |
Heb je hulp nodig?
Als je hulp nodig hebt met Senseair eSENSE Slim stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding CO2 Sensor Senseair
29 Maart 2023
29 Maart 2023
29 Maart 2023
29 Maart 2023
29 Maart 2023
29 Maart 2023
29 Maart 2023
29 Maart 2023
29 Maart 2023
29 Maart 2023
Handleiding CO2 Sensor
- CO2 Sensor Aktivia
- CO2 Sensor Atal
- CO2 Sensor Bresser
- CO2 Sensor Brink Climate
- CO2 Sensor Duco
- CO2 Sensor Econox
- CO2 Sensor Edimax
- CO2 Sensor EnviSense
- CO2 Sensor Sohatech
- CO2 Sensor TechGrow
- CO2 Sensor Zehnder
- CO2 Sensor Orcon
Nieuwste handleidingen voor CO2 Sensor
2 September 2023
30 Juli 2023
8 Augustus 2023
30 Juli 2023
30 Juli 2023
30 Juli 2023
15 November 2022
17 Juni 2023
23 Mei 2023
16 Maart 2023