Samsung AG070KSVGNH Handleiding
Lees hieronder de 📖 handleiding in het Nederlandse voor Samsung AG070KSVGNH (2 pagina's) in de categorie Airco. Deze handleiding was nuttig voor 13 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/2
1 2 3 4
8765
3 Press K1 shortly to display the number for selected option.
4 Press K2 shortly to display the number for set value of the selected option.
5 Finish the option setting.
fPress K2 long to nish the setting with all option values determined and saved.
fPress K1 long to nish the setting with all option values cancelled and keep the values as before entering the setting.
• In option setting, press K4 long to initialize all option values.
No. Option item Option
value
Factory
default Option Denition Setting unit
Module control
setting option
Note1)
1Operation On/Off input method 0·1 0 0 Module control/DMS Main unit of group
Note2)
1 External contact
2 Temperature setting input method 0·1 0 0 Module control/DMS Main unit of group
Note2)
1 External contact
3 Operation mode (Cool/Heat, normal/hot water) input method 0·1 0 0 Module control/DMS Main unit of group
Note2)
1 External contact
4 Demand control input method 0·1 0 0 Module control/DMS Main unit of group
Note2)
1 External contact
5 3Demand level 0 ~ 11
0 Default (100 %)
Main unit of module O
1 95 %
2 90 %
3 85 %
4 80 %
5 75 %
6 70 %
7 65 %
8 60 %
9 55 %
10 50 %
11 Not applied (No limit)
6 0Quiet function input method 0·1 0 Module control/DMS Main unit of group
Note2)
1 External contact
7 Forced fan function input method 0·1 0 0 Module control/DMS Main unit of group
Note2)
1 External contact
8 Water law input method 0·1 0 0 Module control/DMS Main unit of group
Note2)
1 External contact
9 0Pump operation when thermo off 0·1 0Pump OFF when thermo OFF and operation
pattern is not standard control Main unit of module
1 Pump ON always when thermo OFF
10 Remote error reset input 0·1 0 0 Disuse Main unit of module
1 Use
11
Setting unit address
• Module address must be set. (Refer to installation
manual of module controller.)
0 ~ 15 (Not set) Setting unit address Each unit
12 Quiet function level 0 ~ 3 1
0 Default (100 %)
Main unit of module O
1 Level1
2 Level2
3 Level3
13 Conrm delay for unsecured ow rate when operating 10 ~
240 30 Delay for inspecting no input for pump
interlock and unsecured ow rate (by seconds) Main unit of module
14 Using exterior water outlet temperature sensor 0/1 0 0 Disuse Main unit of group
Note2)
1 Use
15 Water law control standard 0/1 0
0 Outdoor temperature Main unit of group
Note2) O
1Room temperature (external room temperature
sensor installation necessary)
16 AirCool1 (For water law) 0 ~ 20 Standard 1 outdoor temperature for cooling10
Main unit of group
Note2) O
17 AirCool2 (For water law) 30 ~ 40 Standard 2 outdoor temperature for cooling35
18 RoomCool1 (For water law) 15 ~ 24 Standard 1 room temperature for cooling20
19 RoomCool2 (For water law) 25 ~ 35 Standard 2 room temperature for cooling30
20 Tcool1 (For water law) -10 ~
25 15 Standard 1 set temperature for cooling
21 Tcool2 (For water law) -10 ~
25 7 Standard 2 set temperature for cooling
22 AirHeat1 (For water law) -20 ~ 5 Standard 1 outdoor temperature for heating-10
23 AirHeat2 (For water law) 10 ~ 20 Standard 2 outdoor temperature for heating15
24 RoomHeat1 (For water law) 15 ~ 24 Standard 1 room temperature for heating20
25 RoomHeat2 (For water law) 25 ~ 35 Standard 2 room temperature for heating30
26 Theat1 (For water law) 35 ~ 55 Standard 1 set temperature for heating45
27 Theat2 (For water law) 35 ~ 55 Standard 2 set temperature for heating35
28 Operation ON/OFF by external contact 0/1 0 0 Recognize usual signal Main unit of group
Note2)
1 Recognize instant signal
29 ~ 33 Function expansion available
34 Using low temperature function 0/1 0 0 Disuse Each unit
1 Use
35 ~ 37 Function expansion available
Note1) For options that can be selected by module control and main option, the option value selected for last time will be saved.
Note2) Main unit of module when group is not available
Setting hydro unit option and key function (Continued)
Function description
No. Description
1
Select operation On/Off input method of module/group
2
Select temperature setting input method of module/group
3
Select operation mode (Cool/Heat, Hot water/Cool storage) input method of
module/group
4
Select demand control input method of module/group
5
Select demand level
• Current will be limited below the set level when "Perform" command
is transmitted.
6
Select quiet function input method of module
7
Select forced fan function input method of module
• Forced fan: Removes accumulated snow by operating the fan of
stopped unit in low frequency
• Snow accumulation prevention, which operates occasionally when
outdoor temperature is below zero, is basic function.
8
Select water law input method of module/group
9
Select pump operation status when thermo OFF
10
Select to use error clear function by external contact
11
Setting CHILLER unit address: identical with channel address used by DMS
12
Select quiet function level
• Quiet function will start in set level when "Perform" command is
transmitted.
• Level comparison: Level3 > Level2 > Level1
13
Conrm delay for unsecured ow rate when operating: Delay for inspecting
no input for pump interlock and unsecured ow rate
• Compressor will not operate until water ow is detected.
14
Set when controlling water outlet temperature by installing extra water
temperature gauge on water pipe header or tank
• External water outlet temperature sensor should be installed on main
unit of group (or module when group is not available).
• Standard for water outlet temperature depends on external water
outlet temperature sensor except when operation pattern is standard
control.
15
Setting water law standard
• To set room temperature as stnadard, external room temperature
sensor should be installed.
• Room temperature sensor should be installed on main unit of group (or
module when group is not available).
16 ~ 27
Water law control constant: Refer to water law operation graph.
28
Recognition of external control operation ON/OFF
• 0 (recognizing usual signal): Constantly inspects ON/OFF status of
contact and set operation ON/OFF
• 1 (recognizing instant signal): Set operation ON/OFF when contact
ON/OFF signal is input (when external contact is consisted of button
click)
34
Select to use low temperature function
• The function will operate when set simultaneously with product
option of module control (Seg23 of installation option 02 = 'E')
• Low temperature function: Expands water outlet usage range in Cool/
Cool stoarge mode ( 5 ~ 25 °C -10 ~ 25 °C)
• When using low temperature function, use brine and maintain the
concentration under freezing point.
MICOM version display
fPress and hold K3 and K5 for 3 seconds to enter the view mode.
fPress K3 to change view mode in order of the table.
fCancelling view mode display
- Press and hold K3 for 3 seconds.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Remarks Data
Source
Address
setting
mode
0 1 0 1 1 2 Hydro
controller
Main
MICOM
version
M n 1 5 1 1
ex) ver
151101
1511
Inverter
controller
Hub MICOM
version H b 1 3 0 2
ex) ver
130228
1302
Inverter
controller
Inverter 1
version I 1 1 3 0 2
ex) ver
130228
1302
Inverter
controller
Inverter 2
version I 2 1 3 0 2
ex) ver
130228
1302
Inverter
controller
Fan 1
version F 1 1 3 0 2
ex) ver
130228
1302
Inverter
controller
Fan 2
version F 2 1 3 0 2
ex) ver
130228
1302
Inverter
controller
EEP version E P 1 5 1 1
ex) ver
151101
1511
Inverter
controller
Hydro
version H d 1 5 1 1
ex) ver
151101
1511
Hydro
controller
Setting inverter controller option
Basic segment display
Step Display contents
Display
SEG1 SEG2 SEG3 SEG4
At initial power
supply
Checking segment
display 8 8 8 8
Setting
communication
(Addressing)
- A d 0 1
After communication
setting (usual
occasion)
Transmit/Reception
address
Hydro
controller:
A
Hydro
controller:
0
0 0
Installing and setting the option with tact
switch and functions
1 Press and hold K2 for 3 seconds. (Only available when the operation is
stopped)
fThe display will show the following.
fIf you have set the Emergency operation for compressor malfunction, 1
or 2 will be displayed on Seg 4.
- Seg 1 and Seg 2 will display the number for selected option.
- Seg 3 and Seg 4 will display the number for set value of the
selected option.
2 If you have entered option setting, you can shortly press the K1 switch
to change the value of the Seg 1 and Seg 2 to select desired option.
fRefer to the table for the Seg number of the function for each option.
3 If you have selected desired option, you can shortly press the K2 switch
to change the value of the Seg 3 and Seg 4 to change the functional
setting for the selected option.
fRefer to the table for the Seg number of the function for each option.
4 After selecting the function for options, press and hold the K2 switch
for 2 seconds. Entire 7-segment will blink to begin tracking mode and
value of the option will be be saved. If you do not end the setting mode
properly, option will not be saved.
Option item Input
unit SEG1 SEG2 SEG3 SEG4 Function of the
option Remarks
Emergency
operation for
compressor
malfunction
Individual 0 0
0 0 Disabled E560 will occur
when all the
compressors
are set as
malfunction
state.
0 1 Set compressor 1 as
malfunction state
0 2 Set compressor 2 as
malfunction state
Oil collection
interval Main 0 4
0 0 Factory default
0 1 Shorten the interval
by 1/2
Temperature
to trigger
defrost
operation
Main 0 5
0 0 Factory default
0 1
Apply setting when
the product is being
installed in humid
area such as near
river or lake
Outdoor unit
fan speed
correction
Individual 0 6
0 0 Factory default
0 1 Increase fan speed
Increase the
outdoor unit
fan speed to
maximum value
Snow
accumulation
prevention
function Note1)
Main 1 4
0 0 Enabled (Factory
default)
During snow
accumulation,
the fan may spin
even when the
unit is not in
operation
0 1 Disabled
Maximum
cooling
capacity
restriction
Note2)
Main 1 8
0 0 Enabled
0 1 Disabled
Note1)
Snow accumulation prevention function: Operates fan periodically to
prevent show compiling on the fan while the product is stopped
Note2)
Maximum cooling capacity restriction: Limits operation capacity of
compressor according to indoor load
Setting key operation and checking the view
mode with tact switch
K1 K2 K3 K4
K1
(Number
of press)
KEY operation Display on 7-Segment
1 time Refrigerant charging in Heating mode
2 times Trial operation in Heating mode
3 times Refrigerant discharging in Heating mode
4 times Disuse
5 times Disuse
6 times Disuse
7 times Vacuum
8 times Disuse
9 times Disuse
10 times Disuse
11 times Disuse
12 times End KEY operation -
K2 (Number
of press) KEY operation Display on 7-Segment
1 time Refrigerant charging
in Cooling mode
2 times Trial operation in
Cooling mode
3 times Pump down all units
in Cooling mode
4 times Auto trial operation
5 times Checking the amount
of refrigerant
X X
(Display of last two digits may differ depending
on the progress)
6 times Discharge mode of
DC link voltage
7 times Forced defrost
operation
8 times Forced oil collection
9 times Inverter compressor
1 check
10 times Inverter compressor
2 check
11 times Fan 1 check
12 times Fan 2 check
13 times End KEY operation -
fTo use key operating function for service and maintenance when
installing module/group, set as main control or cancel in module/group.
fDuring Discharging mode, voltage of Inv1 and Inv2 will be displayed
alternately.
fEven when the power is off, it is dangerous when you come in contact
with inverter PCB, fan PCB since high pressure DC voltage is charged to
those parts.
fWhen replacing or repairing the PCB, cut-off the power and wait until
the DC voltage is discharged before replacing/repairing them.
- Wait for more than 15 minutes to allow those parts to be fully
discharged.
fWhen there is error, Discharge mode of DC link voltage may not have
been effective. Especially when E464 and E364 error is displayed,
power element might be damaged so do not use the Discharge mode of
DC link voltage.
K3 (Number
of press) KEY operation Display on 7-Segment
1 time Intialize (Reset) operation Same as initial state
K4 (Number
of press) Display contents
Display
SEG1 SEG2, 3, 4
1 time Capacity depending on
horsepower 1
AG042KTTT 0, 1, 5
AG056KTTT 0, 2, 0
AG070KTTT 0, 2, 5
2 times Order frequency (Compressor 1) 120 Hz 1, 2, 02
3 times Order frequency (Compressor 2) 120 Hz 1, 2, 03
4 times High pressure (MPa) 1.52 MPa 1, 5, 24
5 times Low pressure (MPa) 0.43 MPa 0, 4, 35
6 times Discharge temperature
(Compressor 1) 6 87°C 0, 8, 7
7 times Discharge temperature
(Compressor 2) 7 87°C 0, 8, 7
8 times IPM temperature (Compressor 1) 8 87°C 0, 8, 7
9 times IPM temperature (Compressor 2) 9 87°C 0, 8, 7
10 times CT sensor value (Compressor 1) 2 A 0, 2, 0A
K4 (Number
of press) Display contents
Display
SEG1 SEG2, 3, 4
11 times CT sensor value (Compressor 2) 2 A 0, 2, 0B
12 times Suction 1 temperature C -42°C 0, 4, 2
13 times COND Out temperature -, 4, 2D -42°C
14 times Temperature of liquid pipe E -42°C -, 4, 2
15 times TOP temperature (Compressor 1) F -42°C -, 4, 2
16 times TOP temperature (Compressor 2) G -42°C -, 4, 2
17 times Outdoor temperature H -42°C -, 4, 2
18 times EVI inlet temperature I -42°C -, 4, 2
19 times EVI outlet temperature J -42°C -, 4, 2
20 times Main EEV 1 step 2000 steps K 2, 0, 0
21 times Main EEV 2 step 2000 steps L 2, 0, 0
22 times EVI EEV step 300 steps 3, 0, 0M
23 times H/R EEV step 300 steps 3, 0, 0N
24 times Fan step (SSR or BLDC) 13 steps 0, 1, 30
25 times Current frequency
(Compressor 1) P 120 Hz 1, 2, 0
26 times Current frequency
(Compressor 2) Q 120 Hz 1, 2, 0
27 times Suction 2 temperature R -42°C -, 4, 2
28 times Main Hydro controller address S
Main Hydro controller not
selected BLANK, N, D
If Hydro controller No.1 is
selected as the main unit
0, 0, 1
29 times Snow accumulation sensor
voltage T 1.80 V 1, 8, 0
30 times Total suction temperature U -42°C -, 4, 2
K4 (Number
of press)
(Press and
hold the
K4 for 3
seconds to
enter the
setting)
Display contents
Display
Page1 Page2
1 time Main version Version (ex.: 1412)MAIN
2 times Hub version Version (ex.: 1412)HUB
3 times Inverter compressor 1 check Version (ex.: 1412)INV1
4 times Inverter compressor 2 check Version (ex.: 1412) INV2
5 times Fan 1 check Version (ex.: 1412)FAN1
6 times Fan 2 check Version (ex.: 1412)FAN2
7 times EEP version Version (ex.: 1412)EEP
8 times Automatically assigned
address of the units AUTO
Seg1 Seg2 Seg3, 4
Hydro
controller:
A
Hydro
controller:
0
Address
(ex.: 07)
9 times Manually assigned address
of the units MANU
Seg1 Seg2 Seg3, 4
Hydro
controller:
A
Hydro
controller:
0
Address
(ex.: 15)
A-T/B B-T/B
C-T/B
1 3 5 7 9 11 13 15 17 192 4 6 8 10 12 14 16 18 20
1 3 5 7 9 11 13 15 17 192 4 6 8 10 12 14 16 18 20
1 3 5 7 9 11 13 15 17 192 4 6 8 10 12 14 16 18 20
A-T/B
B-T/B
C-T/B
External contact wiring work
Installation date
YY / MM / DD
Trial operation date (YY) (MM) (DD)
Installation company
Name
Installer
Name
Contact Contact
Installer CODE
Quality guidance Name Quality instructor Name
Contact Contact
Model Purpose □Room temp.
□Low temp.
□How water
□Others
Serial number
Cooling
Rated capacity kW
Remarks Chiller water
condition
Outlet: °C Inlet: °C
Chilled water storage: l/min Pump pressure: kPa
Outdoor temp.
condition °CDB °CWB
Water pipe equipment installation
Heating
Rated capacity kW
Installation date
YY / MM / DD
Heating water
condition
Outlet: °C Inlet: °C
Trial operation date
YY / MM / DD Chilled water storage: l/min Pump pressure: kPa
Water pipe installation
company
Name
Outdoor temp.
condition °CDB °CWB
Contact
Contact
Pump included/excluded □excluded □included
Brine spec.
Type
Pump type Primary (Cooler) □Fixed □Inverter
Secondary (Load) □Fixed □Inverter
Concentration
f
Samsung's product is irrelevant to any installation or performance problem of the water pipes and boiler.
f
This installation specications of the Samsung products will be managed as a reference for follow-up management.
Installation manager self-maintenance list
Preparation
Parts Description Standard
Results
Cabinet panel
board Is power withdrawn by auxiliary circuit breaker? Must use auxiliary circuit breaker
Power Is outdoor cable conncected in order of RST power? Visual check
Is power cable fastened with rated torque value by solderless ring terminal? Ring terminal and tighteing torque (by visual check)
Communication Is module control connected to F3/F4 of hydro PBA?
Cooler
Is service area around the product appropriate? Check standard in installation manual
Is installation location Check standard in installation manual
Are supporting base and vibration-isolation pad applied properly according to installation manual? Visual check
Are drain valves installed? Visual check
Is option switch setting for each type of heat source water appropriate? (heat source water / brine) Visual check
Water supply
system
Is there no leakage on water pipe? Visual check
Are temperautre gauges and pressure gauges installed on water pipe inlet/outlet? Visual check (4)
Air valves and exible joints installed on water pipe inlet/outlet? Visual check (4)
Check cleaning of foreign materials inside the water supply system and welding slugs Check if ushing is done/Water quality check
Is strainer cleaned on water pipe inlet? Cleaning
Are air vent valves and drain valves installed for drainage? Visual check
Is there countermeasure for balancing supplying ow rate?
Visual check for reverse return pipe or rated ow rate valve components
Is expansion tank installed? Visual check
Is water supplied according to standard of supply water quality? Check water quality
Trial operation Cooler
Is temperature of inlet/outlet appropriate? Check temperature gauge (according to installation manual) ( )°C
Is ow rate within the range of max./min. supplying ow rate? Check standard in installation manual ( ) LPM
Is pressure difference between inlet/outlet on water pipe pressure sensor? Check standard in installation manual ( ) kPa
DVM CHILLER condition check card
Installation check card
Installation date (YY) (MM) (DD)
Outdoor unit model
Outdoor unit serial number
Outdoor unit circuit breaker
Circuit breaker capacity [A]
Power cable [mm2]
Remarks
Trial operation date (YY) (MM) (DD)
Installer
Name
Contact
Installer CODE
Installation
company
Name
Contact
Quality
instructor
Name
Contact
Product
outline
Name
Site
Route
Period
Spec.
Purpose □
General □Yearly □
Process □
Others
A
Cooling
Rated capacity kW
Chilled water
condition
Outlet: °C Inlet: °C
Chilled water storage: l/min
Pump pressure: kPa
Outdoor
temperature
condition
°CDB °CWB
Heating
Rated capacity kW
Heating water
condition
Outlet: °C Inlet: °C
Chilled water storage: l/min
Pump pressure: kPa
Outdoor
temperature
condition
°CDB °CWB
B
Power
□
50Hz □
60Hz
□
3 Phase 200V □
Others (Phase V)
Pump type □
Individual (included/excluded) □
Assembled
Special condition □
Public building □
Chloride corrosion
□
Sea water □Brine □
Split division
Electrical parts list
□
Max. capacity limit
□
Pump capacity ( kW)
□
Assembling active lter(5kVA)
□
Power cable kit
□Fin protection
□Others( )
Piping type □
1 pump (Pump on heat source: Fixed. Variable.)
□
2 pump (Pump on heat source: Fixed. Variable)
Number of control unit □
Classifying maker (module control)
□
Classifying electrical parts maker ( )
Error display
fSegment will display error code (4 digit).
HYDRO-UNIT_MODULE_CHILLE
K1 K2 K3 K4 K5 K6
88-SEG DISPLAY
Display Description
101
Communication error between hydro controller and inverter controller (If
not received for 3 minutes from outdoor unit)
108
Error due to repeated setting address
109
Communication error of hydro controller address not complete
122
Error on hydro Evap in Sensor (Open/Short)
123
Error on hydro Evap out Sensor (Open/Short)
128
Error on hydro Evap in Sensor (Detached)
129
Error on hydro Evap out sensor (Detached)
144
Error on hydro pipe temperature 2 sensor
145
Error on hydro EVA OUT 2 sensor
151
Hydro EEV open error (2nd detection)
152
Error due to closed EEV of hydro (2nd detection)
153
Error on hydro oating switch (2nd detection)
162
Inverter controller EEPROM error
163
Hydro controller EEPROM option setting error
198
Error due to disconnected thermal fuse (Temperature of terminal block
increases.)
201
Communication error between hydro controller and outdoor unit
202
Communication error between hydro controller and inverter controller
(When there is no response from indoor units after tracking is completed)
203
Communication error of Main and sub MICOM of inverter controller
205
Communication error of inverter controller main PBA - sub PBA (Sub PBA
communication all not received)
206
Communication error of inverter controller main PBA - sub PBA (Sub PBA
communication partially not received)
Specication of PBA display for actual communication error
C001: Hub PCB communication error
C002: Fan PCB communication error
C003: INV1 communication error
C004: INV2 communication error
221
Error on outdoor temperature sensor (Short or Open)
231
Error on COND outlet sensor (Short or Open)
241
COND outlet sensor is detached
251
Error on discharge temperature of COMP1 (Short or Open)
257
Error on discharge temperature of COMP2 (Short or Open)
262
Discharge temperature sensor of COMP1 is detached
263
Discharge temperature sensor of COMP2 is detached
266
Top1 temperature sensor is detached
267
Top2 temperature sensor is detached
269
Suction temperature sensor is detached
270
Suction 2 temperature sensor is detached
276
Error on Top 1 temperature sensor (Short or Open)
277
Error on Top 2 temperature sensor (Short or Open)
291
Error on high pressure sensor (Short or Open)
296
Error on low pressure sensor (Short or Open)
308
Error on Suction sensor (Short or Open)
311
Error on double layer pipe sensor (Short or Open)
321
EVI inlet temperature
322
EVI outlet temperature
323
Error on Suction 2 sensor (Short or Open)
326
Error on Total suction sensor (Short or Open)
346
Operation failure of Fan2
347
Unconnected error of Fan2
348
Lock error on Fan2
353
Overheated motor of Fan2
355
Error due to overheated IPM of Fan2
361
INV2 Comp starting error
364
INV2 DC Peak error
365
INV2 Comp Vlimit error
366
INV2 DC-Link voltage under/over error
Display Description
367
INV2 Comp Rotation error
368
Error due to full current of INV2
369
INV2 DC Link sensor error
371
INV2 DataFlash error
374
INV2 IPM Heat Sink error
378
Error due to overcurrent of Fan2
383
Error due to special overcurrent of Fan2
385
INV2 input current error
386
Error due to over voltage/low voltage of Fan2
387
Hall IC error of Fan2
389
Outdoor fan2 overload stop
391
Fan2 Date Flash error
393
Fan2 DC output sensor error
396
Fan2 DC Link voltage sensor error
399
Heat sink temperature sensor error of Fan2
400
INV2 IPM OverHeat error
407
COMP down due to high pressure
410
COMP down due to low pressure
416
COMP down due to discharge temperature
425
Phase reversal or phase failure
428
COMP down due to compressor not controlled
438
EVI EEV open error
439
Error due to refrigerant leakage (Examine when system off)
440
Restriction of heating operation by outdoor temperature
441
Restriction of cooling operation by outdoor temperature
442
Restriction of heating charging operation by outdoor temperature
443
Operation prohibited due to low pressure
445
Error due to self-diagnosis of CCH
446
Operation failure of Fan1
447
Unconnected error of Fan1
448
Lock error on Fan1
452
Instant blackout error
453
Overheated motor of Fan1
455
Error due to overheated IPM of Fan1
461
INV1 Comp starting error
462
Compressor stop due to full current control or error due to low current
on CT2
464
INV1 DC Peak error
465
INV1 Comp Vlimit error
466
INV1 DC-Link voltage under/over error
467
INV1 Comp Rotation error
468
Error due to full current of INV1
469
INV1 DC Link sensor error
471
INV1 Date Flash error
474
INV1 IPM Heat Sink error
478
Error due to overcurrent of Fan1
483
Error due to special overcurrent of Fan1
485
INV1 input current error
486
Error due to over voltage/low voltage of Fan1
487
Hall IC error of Fan1
489
Outdoor fan1 overload stop
491
Fan1 DataFlash error
493
Fan1 DC output sensor error
496
Fan1 DC Link voltage sensor error
499
Heat sink temperature sensor error of Fan1
500
INV1 IPM OverHeat error
560
Switch option setting error
901
Hydro inlet temperature sensor (Tw1) Short/Open
902
Hydro outlet temperature sensor (Tw2) Short/Open
907
Frozen damage error
908
Error when freeze prevention Comp Off occurs 4times
909
Error when freeze prevention Comp Off occurs 3times
910
Error on hydro outlet temperature (Tw2) sensor (Detached)
911
Flow switch option error
913
Flow switch error (E911) occurs 6 times
918
Error on pump magnetic switch malfunction
971
External sensor (WaterOut Setting Device/ WaterLaw Room Temp sensor)
is open/Short
972
Water inlet side pressure sensor is open/short
973
Water outlet side pressure sensor is open/short
974
External WaterOut sensor is open/short
Error Code Setting hydro unit option and key function
Setting hydro unit option and key function
View mode display
fPress and hold K3 and K4 for 3 seconds to enter the view mode.
fPress K3 to change view mode in order of the table.
fPress K4 to change view mode in reverse order of the table.
fCancelling view mode display
- Press and hold K3 for 3 seconds.
K1 K2 K3 K4 K5 K6
88-SEG DISPLAY
TACT S/W
DIP S/W
Number of press KEY operation SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Remarks
1 time Water In ex) -5°C0 1 - 0 5 0
2 times Water Out ex) -11°C0 2 - 1 1 0
3 times Outdoor temperature ex) -11.2°C0 3 - 1 1 2
4 times High pressure ex) 29.3 kgf/cm0 4 2 9 3 2G
5 times Low pressure ex) 7.5 kgf/cm0 5 0 7 5 2G
6 times Comp 1 current frequency ex) 110Hz0 6 1 1 0
7 times Comp 2 current frequency ex) 113Hz0 7 1 1 3
8 times Discharge 1 temperature ex) 101.8°C 0 8 1 0 1 101 (Drop)
9 times Discharge 2 temperature ex) 101.8°C 0 9 1 0 1 101 (Drop)
10 times Top 1 temperature ex) 101.8°C 1 0 1 0 1 101 (Drop)
11 times Top 2 temperature ex) 101.8°C 1 1 1 0 1 101 (Drop)
12 times Total suction temperature ex) -11.2°C1 2 - 1 1 2
13 times Suction 1 temperature ex) -11.2°C1 3 - 1 1 2
14 times Suction 2 temperature ex) -11.2°C1 4 - 1 1 2
15 times COND Out temperature ex) -11.2°C1 5 - 1 1 2
16 times Liquid Temperature ex) 35°C1 6 3 5 0
17 times EVA In 1 temperature ex) 35°C1 7 3 5 0
18 times EVA Out 1 temperature ex) 50°C1 8 5 0 0
19 times EVA In 2 temperature ex) 35°C1 9 3 5 0
20 times EVA Out 2 temperature ex) 50°C2 0 3 5 0
21 times EVI In temperature ex) 35°C2 1 3 5 0
22 times EVI Out temperature ex) 35°C2 2 3 5 0
23 times IPM 1 temperature ex) 80°C2 3 8 0 0
24 times IPM 2 temperature ex) 80°C2 4 8 0 0
25 times CT 1 ex) 11A2 5 1 1 0
26 times CT 2 ex) 11A2 6 1 1 0
27 times Operation mode S:Thermal/Cool storage / C:Cooling, H:Heating2 7 Blank/S C/H
28 times Set temperature ex) -5°C2 8 - 0 5 0
29 times Pump output 2 9 0 n/F Blank/F On/Off
30 times Fan Step ex) 24step 3 0 0 2 4
31 times Hydro EEV 1 ex) 1007step 3 1 1 0 0 100 (Drop "/10")
32 times Hydro EEV 2 ex) 1007step 3 2 1 0 0 100 (Drop "/10")
33 times Main EEV 1 ex) 1007step 3 3 1 0 0 100 (Drop "/10")
34 times Main EEV 2 ex) 1007step 3 4 1 0 0 100 (Drop "/10")
35 times EVI EEV ex) 473step 3 5 4 7 3
36 times PHE inlet pressure ex) 1.2 kgf/cm3 6 0 1 2 2G
37 times PHE outlet pressure ex) 0.4 kgf/cm3 7 0 0 4 2G
38 times Capacity (Cooling) ex) 70 kW3 8 0 7 0
39 times (Exterior) Room temperature ex) 25.5°C3 9 2 5 5
40 times (Exterior) Water outlet temperature ex) -11°C4 0 - 1 1 0
41 times Pressure difference calibration ex) -0.2 kg/cm4 1 - 0 0 2 2
How to set hydro controller option
Option No. Option value
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Operation On/Off input method
0 1 - - - 0
Temperature setting input method
0 2 - - - 0
1 Turn on the product.
2 Press and hold the K2 to enter the option setting.
fIn option setting, other key input (forced fan, temperature setting, etc.) is not received.
DB68-05937A-01
No. Name Signal Function Contact Short Contact Open Signal
recognition Setting unit
A-T/B
1-2 Cooling/Heating display
Zero
voltage
contact
Display when operates in heating mode Heat Cool - -
3-4 Operation display Display when operates Operate Stop - -
5-6 Warning display Display when error occurs Error occurred No error - -
7-8 Defrost operation display Display when defrosting Deforst ON Defrost OFF - -
9-10 Pump operation display Display when pump operates Pump ON Pump OFF - -
11-12 Comp operation display Display when compressoroperates Compressor ON Compressor OFF - -
13-14 Pump operation Signal of pump operation Pump signal ON Pump signal OFF - -
15-16 Freeze protection display Display when freeze protection operates Pump ON for freeze
protection Others - -
17-18 Disuse - - - -
19-20 Disuse - - - -
B-T/B
1-2 Disuse - - - - - -
3-4 Disuse - - - - - -
5-6 Disuse - - - - - -
7-8 Pump interlock
Zero
voltage
contact
Signal about pump operation
• Pump interlock error (E918) occurs if ON is not input when operating pump Pump ON Pump OFF Usual input Each unit
9-10
Operation ON/OFF Controlling operation ON/OFF Usual/instant
input Main unit of group
11-12
13-14 Operation mode Selecting cool/heat mode Usual input Main unit of groupHeat Cool
15-16 Hot water (Coolstorage)
mode
Entering hot water (cool storage) mode by external control
• Cool + ON: Cool storage
• Heat + ON: Hot water
Coolstorage/Hot
water Cool/Heat Usual input Main unit of group
17-18 Hot water (Coolstorage)
control standard
Control depending on set temperature when ON
Control depending on external hot water (cool storage) thermostat when OFF
Control by set
temperature
Control by
thermostat Usual input Main unit of group
19-20 Hot water (Coolstorage)
thermostat signal
When thermostat is set as standard for hot water (cool storage) mode
• Thermo ON when ON (Not over range of water outlet temperature)
• Thermo OFF when OFF
Thermo ON Thermo OFF Usual input Main unit of group
C-T/B
1-2 Quiet function
Zero
voltage
contact
Operate quiet function in level set by main option or module control Quiet function Usual input Main unit of group-
3-4 Demand function Operate demand function (current limet control) in level set by main opetion or module
control Demand function Usual input Main unit of group-
5-6 Forced fan function Operate forced fan function Forced fan function Usual input Main unit of group-
7-8 Unusual condition reset Reset on error occurred status
• Operates only when remote error reset input function is set to use Reset error Instant input- Main unit of
module
9-10 Disuse - - - - -No use (N/A)
11-12 Water law
Zero
voltage
contact
Operate water law Water law control Water outlet set
temperature control Usual input Main unit of group
13-14 Disuse - - - - -No use (N/A)
15-16 Disuse - - - - -No use (N/A)
17-18 Set temperature/room
temperature sensor
Analog
current
Recognize water outlet set temperature by external input (4~20mA)
Recognize value of room temperature sensor (4 ~ 20 mA) when standard for water law
is room temperautre
- - Current input Main unit of group
19-20 External water outlet
temperature
Analog
current Recognize external water outlet temperature by external temperature sensor (4 ~ 20 mA) Current input Main unit of group- -
Product specificaties
Merk: | Samsung |
Categorie: | Airco |
Model: | AG070KSVGNH |
Heb je hulp nodig?
Als je hulp nodig hebt met Samsung AG070KSVGNH stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Airco Samsung
18 November 2024
18 November 2024
18 November 2024
18 November 2024
18 November 2024
18 November 2024
18 November 2024
18 November 2024
18 November 2024
15 November 2024
Handleiding Airco
- Airco Electrolux
- Airco Bosch
- Airco Candy
- Airco Delonghi
- Airco Panasonic
- Airco LG
- Airco AEG
- Airco Bauknecht
- Airco BEKO
- Airco Daewoo
- Airco Grundig
- Airco Honeywell
- Airco Inventum
- Airco Karcher
- Airco Medion
- Airco Remeha
- Airco Siemens
- Airco Toshiba
- Airco Unold
- Airco Vaillant
- Airco Whirlpool
- Airco Zanussi
- Airco Zibro
- Airco Adler
- Airco Airwell
- Airco Akai
- Airco Amana
- Airco Amcor
- Airco Apc
- Airco Arcelik
- Airco Argo
- Airco Balay
- Airco Bartscher
- Airco Bavaria
- Airco Be Cool
- Airco Bestron
- Airco Blaupunkt
- Airco Blumfeldt
- Airco Bodin
- Airco Bomann
- Airco Brandt
- Airco D-Let
- Airco Daikin
- Airco Daitsu
- Airco Defy
- Airco Dimplex
- Airco Dometic
- Airco Domo
- Airco Duracraft
- Airco Duux
- Airco Easy Home
- Airco Eco-De
- Airco Eden
- Airco Edgestar
- Airco Edy
- Airco Einhell
- Airco Emerio
- Airco Emerson
- Airco Eurom
- Airco Everglades
- Airco Evolar
- Airco Exquisit
- Airco Fairland
- Airco Ferroli
- Airco Finlux
- Airco Firstline
- Airco Fral
- Airco Frigidaire
- Airco Frilec
- Airco Fronius
- Airco Fuave
- Airco Fuji Electric
- Airco Fujitsu
- Airco G3 Ferrari
- Airco GE
- Airco General Electric
- Airco GlobalTronics
- Airco Gorenje
- Airco Gree
- Airco Gutfels
- Airco H.Koenig
- Airco Haier
- Airco Hisense
- Airco Hitachi
- Airco Holland Electro
- Airco Home Electric
- Airco Hotpoint
- Airco Hotpoint-Ariston
- Airco HQ
- Airco Hyundai
- Airco Iceberg
- Airco Innoliving
- Airco Insignia
- Airco Itho
- Airco Kalorik
- Airco Kelvinator
- Airco Kenmore
- Airco Klarstein
- Airco Koenic
- Airco Kogan
- Airco Korona
- Airco Lanaform
- Airco Lavorwash
- Airco Livington
- Airco Livoo
- Airco Logik
- Airco Maiko
- Airco Manta
- Airco Master
- Airco Maxicool
- Airco Meaco
- Airco Meireles
- Airco Melissa
- Airco Mesko
- Airco Mestic
- Airco Midea
- Airco Mistral
- Airco Mitsubishi
- Airco Moa
- Airco MPM
- Airco MundoClima
- Airco Nabo
- Airco Nedis
- Airco Philco
- Airco Prem-i-air
- Airco Primo
- Airco Princess
- Airco Profile
- Airco Progress
- Airco Proklima
- Airco Proline
- Airco Protector
- Airco Qlima
- Airco RCA
- Airco REMKO
- Airco Rotel
- Airco Rowenta
- Airco Royal Sovereign
- Airco Russell Hobbs
- Airco Sanyo
- Airco Sauber
- Airco Saunier Duval
- Airco Sencor
- Airco Sencys
- Airco Sharp
- Airco Sigma
- Airco SMC
- Airco Sonnenkonig
- Airco SPT
- Airco Starlyf
- Airco Stirling
- Airco Suntec
- Airco Tarrington House
- Airco Taurus
- Airco TCL
- Airco Team
- Airco Technisat
- Airco Teco
- Airco Tectro
- Airco Telefunken
- Airco Termozeta
- Airco Thomson
- Airco Tomado
- Airco Tosot
- Airco Toyotomi
- Airco Trilec
- Airco Tristar
- Airco Tronix
- Airco Trotec
- Airco Truma
- Airco Ufesa
- Airco Vestel
- Airco Vivax
- Airco Waeco
- Airco Westinghouse
- Airco White Knight
- Airco Whynter
- Airco Woods
- Airco Zelmer
- Airco Jocca
- Airco Jocel
- Airco Just Fire
- Airco OK
- Airco Olimpia Splendid
- Airco OneConcept
- Airco Oregon Scientific
- Airco Ozito
- Airco Becken
- Airco Black And Decker
- Airco Camry
- Airco Clatronic
- Airco Concept
- Airco ECG
- Airco Elba
- Airco Essentiel B
- Airco Guzzanti
- Airco Heinner
- Airco Khind
- Airco Orbegozo
- Airco Profilo
- Airco Trisa
- Airco Vox
- Airco Wilfa
- Airco Anslut
- Airco Kunft
- Airco Soler And Palau
- Airco Conrad
- Airco Ansonic
- Airco Aspes
- Airco Comfee
- Airco Corberó
- Airco Danby
- Airco Equator
- Airco Esatto
- Airco IFB
- Airco Infiniton
- Airco Koldfront
- Airco Listo
- Airco Orima
- Airco Svan
- Airco Ardes
- Airco Eldom
- Airco Premium
- Airco Teesa
- Airco Alpatec
- Airco ElectriQ
- Airco Heylo
- Airco HTW
- Airco Prime3
- Airco Avidsen
- Airco SereneLife
- Airco DCG
- Airco Kubo
- Airco Malmbergs
- Airco Challenge
- Airco Calor
- Airco Riffel
- Airco Broan
- Airco RIDGID
- Airco KDK
- Airco Bimar
- Airco Climadiff
- Airco Tripp Lite
- Airco Mabe
- Airco Equation
- Airco Godrej
- Airco Milectric
- Airco Orava
- Airco Simplicity
- Airco Cecotec
- Airco Baxi
- Airco Thermex
- Airco Keystone
- Airco Sanus
- Airco Carrier
- Airco Furrion
- Airco Rinnai
- Airco Carson
- Airco Artrom
- Airco Carrefour Home
- Airco Céliera
- Airco Commercial Cool
- Airco Coolix
- Airco Hokkaido
- Airco Kibernetik
- Airco Norpole
- Airco Senville
- Airco SHE
- Airco CyberPower
- Airco Perfect Aire
- Airco Be Quiet!
- Airco Ariston Thermo
- Airco Element
- Airco Dantherm
- Airco Argoclima
- Airco DEXP
- Airco Chigo
- Airco Elgin
- Airco Evapolar
- Airco EcoFlow
- Airco Liebert
- Airco Avalon Bay
- Airco NewAir
- Airco Braemar
- Airco ActronAir
- Airco Klimaire
- Airco Consul
- Airco SEEGER
- Airco LERAN
- Airco Friedrich
- Airco Aerian
- Airco Polocool
- Airco Convair
- Airco Companion
- Airco Volteno
- Airco Arcoaire
- Airco AFINTEK
- Airco Brivis
- Airco MRCOOL
- Airco B-Air
- Airco Monzana
- Airco Kaden
- Airco Geist
- Airco GoldAir
- Airco Avallon
- Airco Ravanson
- Airco Create
- Airco Columbia Vac
- Airco TURBRO
- Airco House & Luft
- Airco Daizuki
- Airco Bonaire
- Airco Evapcool
- Airco Vostok
- Airco American Comfort
- Airco Ocean Breeze
- Airco Quirky
- Airco Krone
- Airco KwiKool
- Airco Big Ass Fans
- Airco Arctic King
- Airco Omega Altise
- Airco Climachill
- Airco Heat Controller
- Airco Luma Comfort
- Airco AireMax
- Airco Kaco
- Airco Middle Atlantic
- Airco Goodwe
- Airco Swegon
- Airco InAlto
- Airco JHS
- Airco FREONIC
- Airco ARCTIC WIND
- Airco Electroline
- Airco BLUEPALM
- Airco KuulAire
- Airco Cool-Space
- Airco BOSFOR
- Airco Aconatic
- Airco VänEE
- Airco Mayer
- Airco Yamazen
- Airco Corona
Nieuwste handleidingen voor Airco
20 November 2024
20 November 2024
19 November 2024
19 November 2024
19 November 2024
19 November 2024
19 November 2024
19 November 2024
19 November 2024
19 November 2024