JG79J919H01 Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
75 mm hole saw
Torque wrench
Wrench (or spanner)
4 mm hexagonal wrench
Flare tool for R32, R410A
Gauge manifold for R32, R410A
Vacuum pump for R32, R410A
Charge hose for R32, R410A
Pipe cutter with reamer
SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
ENGLISH
Model names are indicated in 1-3.
REFRIGERANT
Appropriate personal protective equipment
The installer should ensure they check the respective Work Health
and Safety (WHS) Act within their jurisdiction as the requirements
and obligations may differ.
1. BEFORE INSTALLATION
MEANINGS OF SYMBOLS DISPLAYED ON INDOOR UNIT AND/OR OUTDOOR UNIT
WARNING
5LVNRI¿UH
7KLVXQLWXVHVDÀDPPDEOHUHIULJHUDQW
,IUHIULJHUDQWOHDNVDQGFRPHVLQFRQWDFWZLWK¿UHRUKHDWLQJSDUWLWZLOOFUHDWHKDUPIXOJDVDQGWKHUHLVULVNRI¿UH
Read the OPERATING INSTRUCTIONS carefully before operation.
Service personnel are required to carefully read the OPERATING INSTRUCTIONS and INSTALLATION MANUAL before operation.
Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION MANUAL, and the like.
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
 %HVXUHWRREVHUYHWKHZDUQLQJVDQGFDXWLRQVVSHFL¿HGKHUHDVWKH\LQFOXGHLPSRUWDQWLWHPVUHODWHGWRVDIHW\
After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.
When using this product in Australia, carefully read the Australian Institute of Refrigeration and Flammable refrigerants Safety Guide in Air conditioning and Heating (AIRAH) as well.
CAUTION
WARNING
Do not install the unit by yourself (user).
,QFRPSOHWH LQVWDOODWLRQ FRXOG FDXVH ¿UH HOHFWULF VKRFN
injury due to the unit falling, or leakage of water. Consult
the dealer from whom you purchased the unit or a quali-
¿HGLQVWDOOHU
Perform the installation securely referring to the in-
stallation manual.
,QFRPSOHWH LQVWDOODWLRQ FRXOG FDXVH ¿UH HOHFWULF VKRFN
injury due to the unit falling, or leakage of water.
When installing the unit, use appropriate protective
equipment and tools for safety.
Failure to do so could cause injury.
Install the unit securely in a place which can bear the
weight of the unit.
If the installation location cannot bear the weight of the
unit, the unit could fall causing injury.
Do not alter the unit.
 ,WPD\FDXVH¿UHHOHFWULFVKRFNLQMXU\RUZDWHUOHDNDJH
(OHFWULFDOZRUNVKRXOGEHSHUIRUPHGE\DTXDOL¿HG
experienced electrician, according to the installation
manual. Be sure to use an exclusive circuit. Do not
connect other electrical appliances to the circuit.
 ,IWKHFDSDFLW\RIWKHSRZHUFLUFXLWLVLQVXI¿FLHQWRUWKHUH
LVLQFRPSOHWHHOHFWULFDOZRUNLWFRXOGUHVXOWLQD¿UHRUDQ
electric shock.
Earth the unit correctly.
Do not connect the earth to a gas pipe, water pipe, light-
ning rod, or telephone earth. Defective earthing could
cause electric shock.
Do not damage the wires by applying excessive
pressure with parts or screws.
 'DPDJHGZLUHVFRXOGFDXVH¿UHRUHOHFWULFVKRFN
Be sure to cut off the main power in case of setting
up the indoor P.C. board or wiring works.
Failure to do so could cause electric shock.
 8VH WKH VSHFL¿HG ZLUHV WR FRQQHFW WKH LQGRRU DQG
RXWGRRUXQLWVVHFXUHO\DQGDWWDFKWKHZLUHV¿UPO\WR
the terminal block connecting sections so the stress
of the wires is not applied to the sections. Do not
extend the wires, or use intermediate connection.
 ,QFRPSOHWHFRQQHFWLQJDQGVHFXULQJFRXOGFDXVH¿UH
'RQRWLQVWDOOWKHXQLWLQDSODFHZKHUHLQÀDPPDEOH
gas may leak.
If gas leaks and accumulates in the area around the unit,
it could cause an explosion.
Do not use intermediate connection of the power
cord or the extension cord and do not connect many
devices to one AC outlet.
 ,WFRXOGFDXVHD¿UHRUDQHOHFWULFVKRFNGXHWRGHIHFWLYH
contact, defective insulation, exceeding the permissible
current, etc.
%HVXUHWRXVHWKHSDUWVSURYLGHGRUVSHFL¿HGSDUWV
for the installation work.
The use of defective parts could cause an injury or leak-
DJHRIZDWHUGXHWRD¿UHDQHOHFWULFVKRFNWKHXQLWIDOO-
ing, etc.
When plugging the power supply plug into the outlet,
make sure that there is no dust, clogging, or loose
parts in both the outlet and the plug. Make sure that
the power supply plug is pushed completely into the
outlet.
If there is dust, clogging, or loose parts on the power
supply plug or the outlet, it could cause electric shock or
¿UH ,IORRVH SDUWVDUH IRXQG RQ WKH SRZHU VXSSO\SOXJ
replace it.
Attach the electrical cover to the indoor unit and the
service panel to the outdoor unit securely.
If the electrical cover of the indoor unit and/or the service
panel of the outdoor unit are not attached securely, it
FRXOG UHVXOW LQ D ¿UH RU DQ HOHFWULF VKRFN GXH WR GXVW
water, etc.
When installing, relocating, or servicing the unit,
make sure that no substance other than the speci-
¿HGUHIULJHUDQW5HQWHUVWKHUHIULJHUDQWFLUFXLW
Any presence of foreign substance such as air can
cause abnormal pressure rise and may result in explo-
sion or injury. The use of any refrigerant other than that
VSHFL¿HG IRU WKH V\VWHP ZLOO FDXVH PHFKDQLFDO IDLOXUH
system malfunction, or unit breakdown. In the worst
case, this could lead to a serious impediment to securing
product safety.
Do not discharge the refrigerant into the atmos-
phere. If refrigerant leaks during installation, venti-
late the room. Check that the refrigerant does not
leak after installation has been completed.
 ,IUHIULJHUDQWOHDNVDQGFRPHVLQFRQWDFWZLWK¿UHRUKHDW-
ing part of such a fan heater, kerosene heater, or cooking
stove, it will create harmful gas.
Use appropriate tools and piping materials for instal-
lation.
The pressure of R32 is 1.6 times more than R22. Not
using appropriate tools or materials and incomplete in-
stallation could cause the pipes to burst or injury.
When pumping down the refrigerant, stop the com-
pressor before disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the com-
pressor is running and the stop valve is open, air could
be drawn in and the pressure in the refrigeration cycle
could become abnormally high. This could cause the
pipes to burst or injury.
When installing the unit, securely connect the refrig-
erant pipes before starting the compressor.
If the compressor is started before the refrigerant pipes
are connected and when the stop valve is open, air could
be drawn in and the pressure in the refrigeration cycle
could become abnormally high. This could cause the
pipes to burst or injury.
)DVWHQDÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HG
in this manual.
,IIDVWHQHG WRR WLJKW D ÀDUHQXW PD\ EUHDNDIWHU DORQJ
period and cause refrigerant leakage.
The unit shall be installed in accordance with na-
tional wiring regulations.
:KHQXVLQJ D JDVEXUQHU RURWKHUÀDPHSURGXFLQJ
equipment, completely remove all of the refrigerant
from the air conditioner and ensure that the area is
well-ventilated.
,I WKH UHIULJHUDQW OHDNV DQG FRPHV LQ FRQWDFW LQ ¿UH RU
heating part, it will create harmful gas and there is risk of
¿UH
Do not use means to accelerate the defrosting pro-
cess or to clean, other than those recommended by
the manufacturer.
The appliance shall be stored in a room without con-
tinuously operating ignition sources (for example:
RSHQÀDPHVDQRSHUDWLQJJDVDSSOLDQFHRUDQRSHU-
ating electric heater.
Do not pierce or burn.
Be aware that refrigerants may not contain an odour.
Pipe-work shall be protected from physical damage.
The installation of pipe-work shall be kept to a mini-
mum.
Compliance with national gas regulations shall be
observed.
Keep any required ventilation openings clear of ob-
struction.
In Australia, only technicians that possess the ap-
propriate license issued by the Australian Refrigera-
tion Council (ARC) should install this product.
Install an earth leakage breaker depending on the
installation place.
If an earth leakage breaker is not installed, it could cause
electric shock.
Perform the drainage/piping work securely according
to the installation manual.
If there is defect in the drainage/piping work, water could
drop from the unit, soaking and damaging household goods.
 'RQRWWRXFKWKHDLULQOHWRUWKHDOXPLQXP¿QVRIWKH
outdoor unit.
This could cause injury.
Do not install the outdoor unit where small animals
may live.
If small animals enter and touch the electric parts inside the
XQLWLWFRXOGFDXVHDPDOIXQFWLRQVPRNHHPLVVLRQRU¿UH
Also, advise user to keep the area around the unit clean.
Do not operate the air conditioner during interior
FRQVWUXFWLRQDQG¿QLVKLQJZRUNRUZKLOHZD[LQJ
WKHÀRRU
Before operating the air conditioner, ventilate the room
well after such work is performed. Otherwise, it may cause
volatile elements to adhere inside the air conditioner,
resulting in water leakage or scattering of dew.
(Could lead to serious injury in particular environments when operated incorrectly.)
(Could lead to death, serious injury, etc.)
1-2. SELECTING THE INSTALLATION LOCATION
1-3. SPECIFICATIONS
*1 Connect to the power switch which has a gap of 3 mm or more when open to interrupt the
source power phase. (When the power switch is shut off, it must interrupt all phases.)
*2 Use wires in conformity with design 60245 IEC 57.
*3 Use wires in conformity with design AS/NZS 5000.2.
1HYHUXVHSLSHVZLWKWKLFNQHVVOHVVWKDQVSHFL¿HG7KHSUHVVXUHUHVLVWDQFHZLOOEHLQVXI-
¿FLHQW
*5 Use a copper pipe or a copper-alloy seamless pipe.
*6 Be careful not to crush or bend the pipe during pipe bending.
*7 Refrigerant pipe bending radius must be 100 mm or more.
*8 If pipe length exceeds 15 m, additional refrigerant (R32) charge is required. (No additional
charge is required for pipe length less than 15 m.)
Additional refrigerant = A × (pipe length (m) – 15)
,QVXODWLRQPDWHULDO+HDWUHVLVWLQJIRDPSODVWLFVSHFL¿FJUDYLW\
%HVXUHWR XVH WKHLQVXODWLRQ RIVSHFL¿HGWKLFNQHVV ([FHVVLYHWKLFNQHVVPD\ FDXVH
LQFRUUHFWLQVWDOODWLRQRIWKHLQGRRUXQLWDQGLQVXI¿FLHQWWKLFNQHVVPD\FDXVHGHZGULSSDJH
Model Power supply *1 :LUHVSHFL¿FDWLRQV Pipe size
(thickness *4, *5) Maximum amount of
refrigerant charge
Indoor unit Outdoor unit Rated Voltage Frequency Breaker
capacity
Power
supply *2
Indoor/outdoor con-
necting wire *2
Demand control signal
transmission cable *3 Gas / Liquid
MSZ-GS50VFD
MSZ-GS60VFD
MUZ-GS50VFD
MUZ-GS60VFD 230 V 50 Hz 16 A 3-core
2.0 mm2
4-core
1.0 mm20.5 - 1.5 mm2ø12.7 / 6.35 mm
(0.8 mm) 1350 g
Note:
When operating the air conditioner in low outside temperature, be sure to follow the instruc-
tions described below.
Never install the outdoor unit in a place where its air inlet/outlet side may be exposed
directly to wind.
To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.
 7RSUHYHQWH[SRVXUHWRZLQGLWLVUHFRPPHQGHGWRLQVWDOODEDIÀHERDUGRQWKHDLURXWOHW
side of the outdoor unit.
Avoid the following places for installation where air conditioner trouble is liable to occur.
 :KHUHÀDPPDEOHJDVFRXOGOHDN
Where there is much machine oil.
 :KHUHRLOLVVSODVKHGRUZKHUHWKHDUHDLV¿OOHGZLWKRLO\VPRNHVXFKDVFRRNLQJDUHDV
and factories, in which the properties of plastic could be changed and damaged).
Salty places such as the seaside.
 :KHUHVXO¿GHJDVLVJHQHUDWHGVXFKDVKRWVSULQJVHZDJHZDVWHZDWHU
Where there is high-frequency or wireless equipment.
Where there is emission of high levels of VOCs, including phthalate compounds, for-
maldehyde, etc., which may cause chemical cracking.
The appliance shall be stored so as to prevent mechanical damage from occurring.
Pipe length and height difference
Max. pipe length 30 m
Max. height difference 15 m
Max. number of bends *6, *7 10
Refrigerant adjustment A *8 20 g/m
Insulation thickness *9, *10
8 mm
INDOOR UNIT
 :KHUHDLUÀRZLVQRWEORFNHG
Where cool(or warm) air spreads over the entire room.
Rigid wall without vibration.
Where it is not exposed to direct sunshine. Do not expose to direct sunshine also during
the period following unpacking to before use.
Where easily drained.
At a distance 1 m or more away from your TV and radio. Operation of the air conditioner
PD\LQWHUIHUHZLWKUDGLRRU79UHFHSWLRQ$QDPSOL¿HUPD\EHUHTXLUHGIRUWKHDIIHFWHG
device.
 ,QDSODFHDVIDUDZD\DVSRVVLEOHIURPÀXRUHVFHQWDQGLQFDQGHVFHQWOLJKWV,QRUGHUWR
make the infrared remote control can operate the air conditioner normally. The heat from
the lights may cause deformation or the ultraviolet may cause deterioration.
 :KHUHWKHDLU¿OWHUFDQEHUHPRYHGDQGUHSODFHGHDVLO\
Where it is away from the other heat or steam source.
REMOTE CONTROLLER
Where it is easy to operate and easily visible.
Where children cannot touch it.
 6HOHFW D SRVLWLRQ DERXW PDERYH WKHÀRRUDQG FKHFNWKDW VLJQDOVIURP WKH UHPRWH
controller are surely received by the indoor unit from that position (‘beep’ or ‘beep beep’
receiving tone sounds). After that, attach remote controller holder to a pillar or wall and
install wireless remote controller.
Note:
,QURRPVZKHUHLQYHUWHUW\SHÀXRUHVFHQWODPSVDUHXVHGWKHVLJQDOIURPWKHZLUHOHVVUHPRWH
controller may not be received.
OUTDOOR UNIT
Where it is not exposed to strong wind.
 :KHUHDLUÀRZLVJRRGDQGGXVWOHVV
Where rain or direct sunlight can be avoided as much as possible.
Where neighbours are not annoyed by operation sound or hot air.
Where rigid wall or support is available to prevent the increase of operation sound or
vibration.
Where there is no risk of combustible gas leakage.
When installing the unit at a high level, be sure to secure the unit legs.
Where it is at least 3 m away from the antenna of TV set or radio. Operation of the air
conditioner may interfere with radio or TV reception in areas where reception is weak. An
DPSOL¿HUPD\EHUHTXLUHGIRUWKHDIIHFWHGGHYLFH
Install the unit horizontally.
Please install it in an area not affected by snowfall or blowing snow. In areas with heavy
VQRZSOHDVHLQVWDOODFDQRS\DSHGHVWDODQGRUVRPHEDIÀHERDUGV
Note:
It is advisable to make a piping loop near outdoor unit so as to reduce vibration transmit-
ted from there.
WARNING
7KHXQLWVKRXOGEHLQVWDOOHGLQURRPVZKLFKKDYHWKHÀRRUVSDFHVSHFL¿HGEHORZ
GS50/60: 3.4 m² or larger
When the indoor unit is connected to the multi type outdoor unit of R32 refrigerant,
SOHDVHFRQVXOW\RXUGHDOHUDERXWWKHÀRRUVSDFHVSHFL¿HG
As for the details, please refer to the Installation Service Manual for New Refriger-
ant System.
(G)
(E)
(C)
(4)
(D)
(F)
(2)
(1)
(3)
(5)
(6)
(7)
133 mm
or more
111
mm or more/
132
mm or more
for left/left rear piping
(using spacer)
1-4. INSTALLATION DIAGRAM
When the piping is to be attached to a wall containing metals (tin plated)
or metal netting, use a chemically treated wooden piece 20 mm or thicker
between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape
around the piping.
To use existing piping, perform COOL operation for 30 minutes and pump
GRZQEHIRUHUHPRYLQJWKHROGDLUFRQGLWLRQHU5HPDNHÀDUHDFFRUGLQJWR
the dimension for new refrigerant.
Appearance of the outdoor unit may differ from some models.
168
mm
or more
10 mm
or more
1.8 m or more from
WKHÀRRU8SWRP
is recommended.
clear *2
100 mm
or more
100 mm
or more
350 mm
or more
200 mm *3
or more
Air inlet
Air outlet
Outdoor unit installation
40 mm2-10 mm × 21 mm slot
800 mm
150 mm
500 mm
344.5 mm
285 mm
304-325 mm
*2 100 mm or more when front and
sides of unit are clear
Note:
*1 Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 1 m away
from the TV antenna wire.
*3 When any 2 sides of left, right and rear of
unit are clear Drain piping for outdoor unit
Provide drain piping before indoor and
outdoor piping connection.
Connect drain hose (I) I.D.15 mm as shown
in the illustration.
Make sure to provide drain piping with a
GRZQKLOOJUDGHIRUHDV\GUDLQÀRZ
Note:
Install the unit horizontally.
Do not use drain socket (8) in cold regions. Drain may freeze and
make the fan stop.
The outdoor unit produces condensate during the heating operation.
Select the installation place to ensure to prevent the outdoor unit and/
or the grounds from being wet by drain water or damaged by frozen
drain water.
IMPORTANT NOTES
Units should be installed by licensed contractor according to local code
requirements.
To comply with the requirements of Australian standard AS/NZS 3000
electrical installations (wiring rules), the electrical wiring required between
the indoor and outdoor units must be installed by a licenced electrical
contractor.
Check that cabling will not be subject to wear, corrosion, excessive pres-
sure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
After the leak test, apply insulating material tightly so
that there is no gap.
WARNING
7RDYRLGULVNRI¿UHÀDUHFRQQHFWLRQVKRXOGEHLQVWDOOHGRXWGRRUV
5HXVDEOHPHFKDQLFDOFRQQHFWRUVDQGÀDUHGMRLQWVDUHQRWDOORZHG
indoors.
WARNING
7RDYRLGULVNRI¿UHHPEHGRUSURWHFWWKHUHIULJHUDQWSLSLQJ
([WHUQDOGDPDJHRQWKHUHIULJHUDQWSLSLQJFDQEHFDXVHRI¿UH
Be sure to use wall hole
sleeve (C) to prevent in-
door/outdoor connecting
wire (A) from contacting
metal parts in the wall
and to prevent damage by
rodents in case the wall
is hollow.
Indoor unit
Wall hole
sleeve (C)
Cut off the
extra length. 3LSH¿[LQJEDQG(
Wall hole cover (D)
Seal the wall hole gap
with putty (H).
Fix the pipe to wall
ZLWKSLSH¿[LQJEDQG
(E).
Fixing screw (F)
(8) (I)
PARTS TO BE PROVIDED AT YOUR SITE
(A)
Indoor/outdoor unit connecting wire*1
1
(B) Extension pipe 1
(C) Wall hole sleeve 1
(D) Wall hole cover 1
(E) 3LSH¿[LQJEDQG 2 to 5
(F) Fixing screw for (E) 4 × 20 mm 2 to 5
(G) Piping tape 1
(H) Putty 1
(I)
Drain hose
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
1 or 2
(J) Refrigeration oil 1
(K) Power supply cord*1 1
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate 1
(2) ,QVWDOODWLRQSODWH¿[LQJVFUHZ
4 × 25 mm 5
(3) Wireless remote controller 1
(4) Felt tape
(For left or left-rear piping) 1
(5) Remote controller holder 1
(6) Fixing screw for (5) 3.5 × 16 mm
(Black) 2
(7) Battery (AAA) for (3) 2
<Outdoor unit>
(8) Drain socket 1
Air inlet


Product specificaties