Midea MOX103-12HFNX Handleiding

Midea Airco MOX103-12HFNX

Lees hieronder de 📖 handleiding in het Nederlandse voor Midea MOX103-12HFNX (12 pagina's) in de categorie Airco. Deze handleiding was nuttig voor 10 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/12
SAFETY MANUAL
IMPORTANT NOTE:
Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save
this manual for future reference.
Precautions
Read Safety Precautions Before Operation and Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury.
13. When a FLAMMABLE REFRIGERANT is used, the requirements for installation space
of appliance and /or ventilation requirements are determined according to
-- the mass charge amount(M) used in the appliance,
--the installation location,
--the type of ventilation of the location or of the appliance.
1. Installation (Space)
- That the installation of pipe-work shall be kept to a minimum.
- That pipe-work shall be protected from physical damage.
- Where refrigerant pipes shall be compliance with national gas regulations.
- That mechanical connections shall be accessible for maintenance purposes.
- In cases that require mechanical ventilation, ventilation openings shall be kept
clear of obstruction.
- When disposing of the product is used, be based on national regulations, properly
processed.
2. Servicing
- Any person who is involved with working on or breaking into a refrigerant circuit
should hold a current valid certificate from an industry-accredited assessment
authority, which authorises their competence to handle refrigerants safely in
accordance with an industry recognised assessment specication.
3. Maintenance and repair requiring the assistance of other skilled personnel shall be
carried out under the supervision of the person competent in the use of flammable
refrigerants.
4. Do not use means to accelerate the defrosting process or to clean, other than
those recommended by the manufacturer.
5. The appliance shall be stored in a room without continuously operating ignition
sources (for example: open ames,an operating gas appliance or an operating
electric heater)
6. Be more careful that foreign matter(oil, water,etc) does not enter the piping. Also,
when storing the piping, securely seal the opening by pinching, taping, etc.
7. Do not pierce or burn.
8. Be aware that refrigerants may not contain an odour.
9. All working procedure that aects safety means shall only be carried by competent
persons.
10. Appliance shall be stored in a well -ventilated area where the room size corresponds
to the room area as speciec for operation.
11. The appliance shall be stored so as to prevent mechanical damage from occurring.
12. Joints shall be tested with detection equipment with a capability of 5 g/year of
refrigerant or better, with the equipment in standstill and under operation or under a
pressure of at least these standstill or operation conditions after installation.
Detachable joints shall NOT be used in the indoor side of the unit(brazed, welded
joint could be used).
SAFETY PRECAUTIONS
WARNING
01
Where.
m is the allowable maximum charge in a room, in kg;
M is the refrigerant charge amount in appliance, in kg;
A is the required minimum room area, in m ;
A is the room area, in m ;
LFL is the lower flammable limit, in kg/m ;
h is the release height, the vertical distance in metres from the floor to the point of
release when the appliance is installed;
h = (hinst+hrel) or 0,6 m whichever is higher
hrel is the release oset in metres from the bottom of the appliance to the point of
release
hinst is the installed height in metres of the unit
Reference installed heights are given below:
0.0 m for portable and floor mounted;
1.0m for window mounted;
1.8m for wall mounted;
2.2m for ceiling mounted;
If the minimum installed height given by the manufacturer is higher than the
reference installed height, then in addition Amin and mmax for the reference installed
height have to be given by the manufacturer. An appliance may have multiple
reference installed heights. In this case, Amin and mmax calculations shall be provided
for all applicable reference installed heights.
For appliances serving one or more rooms with an air duct system, the lowest opening
of the duct connection to each conditioned space or any opening of the indoor unit
greater than 5 cm , at the lowest position to the space, shall be used for h0. However,
h0 shall not be less than 0,6 m. Amin shall be calculated as a function of the opening
heights of the duct to the spaces and the refrigerant charge for the spaces where
leaked refrigerant mayow to, considering where the unit is located. All spaces shall
have a floor area more than Amin.
m = 2,5 x (LFL) x h x (A)
The maximun charge in a room shall be in accordance with the following:
max
max
min
(5/4)
0
1/2
min
0
A = (M/(2,5 x (LFL) x h ))
min
(5/4)
0
2
2
2
3
or the required minumumoor area to install an applicance with refrigerantA
charge M(kg) shall be in accordance with following:
0
2
02


Product specificaties

Merk: Midea
Categorie: Airco
Model: MOX103-12HFNX

Heb je hulp nodig?

Als je hulp nodig hebt met Midea MOX103-12HFNX stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Airco Midea

Handleiding Airco

Nieuwste handleidingen voor Airco