PRODUCT DATA
The Honeywell Trademark is used under license from Honeywell
International Inc. by Air-Pure Systems.
Honeywell International Inc. makes no representations or warranties
with respect to this product.
F114 and F115 Ceiling Surface
Mounted Media Air Cleaners
GENERAL
The F114 and F115 Ceiling Surface Mounted Media Air
Cleaners use direct-drive, forward curve, blower/motors with
95% D.O.P. particle or HEPA filters to remove airborne
contaminants. The air cleaners are designed for use in
restaurants, conference rooms, lounges and offices where
overhead air cleaning is required. They provide their own air
circulation, so the air cleaners can be used in any situation
that requires the reduction of contamination from an enclosed
area.
FEATURES
• High Efficiency Particulate AIR (HEPA) filter models are
99.97% efficient and the D.O.P. particle filter models are
95% efficient at 0.3 micron particles. Both models are
more efficient on particles smaller and larger.
• F114 two-speed, direct-drive, forward curve, motor/blower
models deliver up to 325 cfm (550 m3/hr).
• F115 single speed models deliver up to 600 cfm
(1020 m3/hr) .
• Select models include CPZ™ disposable canisters for
odor control.
• Light colored covers complement the ceiling finish.
• Available in 120 Vac, 60 Hz or 220-240 Vac,
50/60 Hz models.
•READ AND SAVE THESE
INSTRUCTIONS
Contents
General .............................................................................. 1
Features ............................................................................ 1
Specifications .................................................................... 2
Ordering Information ......................................................... 2
Planning the Installation ................................................... 3
Installation ......................................................................... 4
Operation ........................................................................... 5
Service ............................................................................... 5
Parts List ........................................................................... 6
Warranty ............................................................................. 10
F114
F115
68-0201-3 Revised 06-08
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS
68-0201-3 Revised 06-08 2
ORDERING INFORMATION
If you have additional questions, need further information, or would like to comment on our products or services, please write
or phone:
1. Your local Honeywell Commercial Air Products Distributor.
2. Air-Pure Systems
16873 Fish Point Rd. SE
Prior Lake, MN 55372-1714
Phone: (800) 998-1919
Fax: (800) 221-3248
www.cleanairfacility.com
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
Models:
Refer to Table 1 for model descriptions.
Color:
F114: white cabinet and cover.
F115: white cabinet and cover.
Blower/Motor:
F114: two-speed, direct-drive, forward curve.
F115: single-speed, direct-drive, forward curve.
Table 1. F114 and F115 Description.
Efficiency
Model Voltage Particulates at 0.3
Micron (D.O.P. Test) Approximate CPZâ„¢
components in pounds Air Volume in cfm
(m3/hr)
F114A 120 Vac, 60 Hz, 1PHS, 3.6A 99.97% HEPA N/A HI = 325 (550);
LOW = 180 (306)
220-240 Vac, 60 Hz, 1PHS, 1.7A 99.97% HEPA NA HI = 325 (550)
LOW = 180 (306)
F114C 120 Vac, 60 Hz, 1PHS, 3.6A 95% 7 HI = 350 (595);
LOW = 200 (340)
220-240 Vac, 50/60 Hz, 1PHS, 1.7A 95% 7 HI = 320 (544);
LOW = 165 (280)
F115A 120 Vac, 60 Hz, 1PHS, 7.2A 99.97% HEPA N/A 600 (1020)
220/240 Vac, 60 Hz, 1PHS, 8.6A 99.97% HEPA N/A 600 (1020)
F115C 120 Vac, 60 Hz, 1PHS, 7.2A 95% 12 600 (1020)
220/240 Vac, 50/60 Hz, 1PHS, 3.6A 95% 12 550 to 600
(935 to 1020)
aNot applicable.
F114 AND F115 CEILING SURFACE MOUNTED MEDIA AIR CLEANERS
368-0201-3 Revised 06-08
Installation Weight:
F114: approximately 40 lbs (18 kg).
F115: approximately 80 lbs (36 kg).
Controls:
F114: two speed On/Off switch.
F115: direct wired (optional remote mounted On/Off
switch).
Sound Level at 3.3 ft (1m):
F114: 59 dBA on High speed, 55 dBA on Low speed.
F115: 52 to 56 dBA.
Replacement Parts and Accessories:
See Parts List on page 8.
PLANNING THE INSTALLATION
WARNING
Electrical Shock Hazard.
Power source can cause personal injury.
• Do not damage electrical wiring or hidden utilities
when cutting or drilling into the wall or ceiling.
• Do not install where the media air cleaner can be
reached from a tub or shower.
• Always turn off the power at the service panel.
Lock the panel to prevent the power from being
switched on accidentally when servicing or
cleaning the media air cleaner.
Choose Location
The air cleaner is mounted horizontally and can be used in
almost any air cleaning application. For the most efficient
operation, centrally locate the air cleaner to the area to be
cleaned.
For the best air patterns, avoid discharging the air directly at
an obstruction such as a ceiling beam, decorative cornice or
pillar. The discharge air pattern has a range of 20 to 25 ft
(6 to 7.5m) at full speed.
IMPORTANT
Do not install at heights greater than 16 ft (4.8m).
When multiple air cleaners are needed for a large area,
divide the space into equal areas and centrally mount the air
cleaners. See Fig. 3.
Dimensions:
See Fig. 1 and 2 for dimensions.
Fig. 1. Approximate dimensions of
F114 in in. (mm).
Fig. 2. Approximate dimensions of
F115 in in. (mm).
M12735
37-1/2 (952)
28-7/8 (733)
1-1/4 (31)
POWER INPUT POINT
3/8 IN. (10) DIAMETER
MOUNTING HOLES (2)
34-1/8 (867)
10
(254)
4-3/4
(120)
16-1/8
(410)
20
(508)
3/8 IN. 
MOUNTING
HOLES (4)
16
(406)

34-3/4

(859)
28-7/8 (724)
34-3/4 (859)
POWER INPUT POINT
9-3/4
(248)
M11688
POWER INPUT POINT