Apc APDU1335TH Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Apc APDU1335TH (2 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 30 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
990-91601 4/2022
© 2022 Schneider Electric. All rights reserved.
Worldwide Customer Support
Customer support and warranty information is available at
www.apc.com
NetShelter Rack PDU Advanced
Temperature and Temperature and
Humidity Sensors
APDU1335T, APDU1335TH, APDU1335T3H
Installation
IMPORTANT INFORMATION
The Temperature and Humidity sensors are designed to add comprehensive
environmental monitoring to a NetShelter® Rack PDU Advanced. To provide greater
data accuracy, the sensors contain an embedded microchip that converts analog signals
before sending the data to the NetShelter Rack PDU Advanced. The design enables
easy plug and play installation. An RJ45 quick disconnect coupler and a RS–485
extension cable are included in each kit to allow for convenient location of sensors.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
The Temperature Sensor and Temperature/Relative Humidity Sensors are designed to
connect only to a NetShelter Rack PDU Advanced. Connecting the sensors to another
device may result in damage.
Failure to follow these instructions can result in equipment damage.
NOTICE
An APDU1300 Sensor Hub (not provided) can be used to connect the APDU1335T
Temperature Sensor Assembly or the APDU1335TH Temperature/Humidity Sensor
Assembly to the NetShelter Rack PDU Advanced. Connecting the APDU1335T3H
Temperature/Humidity Sensor Assemble to an APDU1300 Sensor Hub is not
recommended.
Inventory
APDU1335T3H Temperature and Humidity Sensor Assembly. The
assembly includes the temperature and humidity sensor, two (2)
temperature probes, and the RS–485 cable (2m) with RJ45 connector.
APDU1335TH Temperature and Humidity Sensor Assembly. The
assembly includes the temperature and humidity sensor and RS–485
cable (2m) with RJ45 connector.
APDU1335T Temperature Sensor Assembly. The assembly includes the
temperature sensor and the RS–485 cable (2m) with RJ45 connector.
RS–485 Extension Cable with RJ45 connector (Qty 1)
RJ45 Quick Disconnect Coupler (Qty 1)
Cable Ties (Qty 6)
Installation
APDU1335T and APDU1335TH
1. Secure the Sensor box to the perforated rack enclosure door with a Cable Tie . 
The sensor box contains a magnet inside to help secure the sensor.NOTE:
2. Plug the RJ45 Connector on the Sensor Cable into Port 1 or Port 2 of the    
NetShelter Rack PDU Advanced.
3. Secure the Sensor Cable along the desired path to the NetShelter Rack PDU 
Advanced using the remaining Cable Ties .
NOTE: It may take from one (1) to three (3) minutes for the NetShelter Rack PDU
Advanced to recognize the sensor.
APDU1335T3H
1. Secure the two (2) Temperature Probes and near the top and bottom of the  
perforated rack door using the provided Cable Ties .
2. Secure the Temperature/Humidity Sensor box to its desired location with the Cable 
Ties provided.
3. Secure the Sensor Cable to the interior of the rack with the provided Cable Ties . 
4. Plug the RJ45 Connector into Port 1 or Port 2 on the NetShelter Rack PDU   
Advanced.
NOTE: It may take from one (1) to three (3) minutes for the NetShelter Rack PDU
Advanced to recognize the sensor.
Installation Options
1. Use the RJ45 Quick Disconnect Coupler and the provided 1.8m RS–485 Extension 
Cable or to serve as an easy disconnect point if the rack door is removed.
NOTE: A longer RS–485 cable with RJ45 connectors (not provided) may be used if
required instead of the 1.8m RS–485 Extension Cable included in the kit.
2. Plug the RJ45 Connector on the RS–485 Extension Cable into Port 1 or   
Port 2 on the NetShelter Rack PDU Advanced.
NOTE: It may take from one (1) to three (3) minutes for the NetShelter Rack PDU
Advanced to recognize the sensor.


Product specificaties

Merk: Apc
Categorie: Niet gecategoriseerd
Model: APDU1335TH

Heb je hulp nodig?

Als je hulp nodig hebt met Apc APDU1335TH stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Apc

Apc

Apc C2C Handleiding

17 September 2024
Apc

Apc AP7868 Handleiding

17 September 2024
Apc

Apc P8VNTG Handleiding

17 September 2024
Apc

Apc P62 Handleiding

17 September 2024
Apc

Apc AP7898 Handleiding

17 September 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd